13
|
MIJAR
–
WATER TREATMENT |
| Azotowa 15b | 41-503 Chorz
ów |
Poland | Tel./fax. 32 2899674 | email: [email protected] | www.mijar.eu |
Too long time of refilling the water in brine
tank
Decrease the time of refilling the water in brine tank
(unscrew the back side of steering valve)
Leakage between the brine valve (air check)
and the steering valve
Check the connections between the brine valve (air check)
and steering valve. Remove the hose connecting the steering
valve from the brine valve and check if valve sucks the brine
during the Brine Slow Rinse cycle
Power failure during refilling water in the
brine tank
Check power supply
Improperly connected softener
Check the softener connections. IN
–
raw water inlet, OUT
–
treated water outlet (see picture 2 page 7)
Resin tank leakage
Check the tank for leaks
Clogged restrictor DLFC
Clean the DLFC restrictor
Water from the sewage system goes back and
pours through the overflow (on the side of
the softener) to the brine tank
Provide drain for overflow below the overflow elbow and
the air gap between the drain pipe and the drain hose (see
picture 1 page 6)
Leakage from the connections (not tightened
hoses for raw supplying water and treated
water)
Check the connections (inlet and outlet) for leaks
11. The device does
not draw brine
Blocked or damaged injector
Clean or replace the injector
Leakage between the brine valve (air check)
and the steering valve
Check the connections between the brine valve (air check)
and steering valve. Remove the hose connecting the steering
valve from the brine valve and check if valve sucks the brine
during the Brine Slow Rinse cycle
Too low pressure in the water mains
Increase water pressure at the inlet to the water softener to a
minimum of 2,0 bar.
Blocked hose or a brine valve (air chek)
supplying brine to the driver
Check a brine hose and remove any lock impeding the flow
Cracked ball in the brine valve (air check)
Replace the brine valve (air check)
The drain is clogged.
-Check the drain hose. If it is bent, collapsed broken or
clogged, remove the hose from the drain pipe check if
nothing is blocking it. Clean the drainage, if necessary,
replace the hose
- Make sure nothing is blocking the sewage pipe, clean the
drainage
Lack of water in the brine tank
See problem 12
„ S V f k w