SPECIFICATIONS
INPUT RANGE
Select any input range within the
following limits
Voltage
Min span 1 V, Max input 250 V
Offset 0 V min, +100% of span max
(example, +10/+20 V)
For negative offsets, use MM1000
Current
Min span 1 mA, Max input 100 mA
Offset 0 mA min, 100% of span max
(example, +50/+100 mA)
For negative offsets, use MM1000.
INPUT IMPEDANCE
Voltage 200 kilohms
Current see table in block diagram
SETPOINT
0 to 100% of span, min.
DEADBAND
1% to 100 % of span, min.
RESPONSE TIME
20 ms typical
ACCURACY
±0.1% of span
COMMON MODE REJECTION
120 dB, DC to 60 Hz
RELAY CONTACTS
(dpdt)
Resistive Load:
5 A max, 150 W max, 220 VAC max,
30 VDC max
Inductive Load:
(Power factor ³ 0.4):
2.5 A max, 75 W max, 220 VAC max,
30 VDC max
OPERATING TEMPERATURE
14°F to 140°F/-10°C to 60°C
TEMPERATURE STABILITY
±0.02% of span/°C max
POWER
(2.5 W max)
115 VAC ±10%, 50 or 60 Hz
230 VAC ±10%, 50 or 60 Hz
(DC Power Option)
12 VDC (limits 10 VDC to 15 VDC)
24 VDC (limits 21 VDC to 32 VDC)
Isolation, DC power supply
to input common: 10 megohms
MOUNTING
The module is designed to plug into a stan-
dard 11-pin relay socket. (MP011) is a
molded plastic socket suitable for mounting
on a flat surface or snap into a 2 3/4 inch wide
PVC track (TRK48).
A hold-down clip (CLP1) is available for
installation where vibration may be a prob-
lem.
A DIN rail mounted socket (DMP011) is avail-
able for 35mm symmetrical DIN rail.
A Killark HK Series explosion-proof housing
with dome and 11 pin socket is available
(HKB-HK2D-11).
WARRANTY
The Mighty Module Series of products carry
a limited warranty of 10 + 5 years. In the
event of a failure due to defective material
or workmanship, during the 10 year period,
the unit will be repaired or replaced at no
charge. For a period of 5 years after the
initial 10 year warranty, the unit will be
repaired, if possible, for a cost of 10 % of
the original purchase price.
Relays are not covered by the warranty.
Specifications are subject to change without notice. © 2007 Wilkerson Instrument Co., Inc. DWG#W102454 3/07
3
4