7
800-473-0213 ~ [email protected] ~ www.mierproducts.com
DA-500 and Connection Using Dry Contacts and External Power
DA-500 and Connecting a DA-500LKA for Additional Contacts
DA-500 and Connecting the DA-052 Whistle, Bells or DA-091 Power Horns
1 2 3 4 5 6 7 8
SENSOR
RELAY
BELL
DA-500 Whistle Switch
MUST be OFF
External Power
Capacitor
0.1 Microfarads 100 Volt (min)
Maximum current linited to 1 AMPERE
Maximum Voltage - 24 VOLTS (
DO NOT
apply 120VAC to terminals)
Sensor Wires:
Red to #1
Black to #2
Silver Shiield to #3
NOTE: Keep the DA-500 Whistle Switch on. However, if internal piezo whistle is not wanted, move the DA-500 Whistle Switch to the
OFF position and connect the jumper b24 and the C Terminal
External 24VDC Whistle, Bell or Horn
with the DA-500 Whistle Switch ON
Blac
k Outer Cable J
acket
Sensor Wires:
Red to #1
Black to #2
Silver Shiield to #3
BELL
or
1N4004 DIODE/Capacitor 0.1 Microfarads 100 Volt (min)
Adding a capacitor extends the life of the relay.
DA-052
Note: Limit of two (2) Bells.
Limit of two (2) DA-091 Power Horns.
Limit of five (5) DA-052 Whistles
External Relay Hookup
24VDC
To AC operated
CHIMES/ALARMS
1 2 3 4 5 6 7 8
SENSOR
RELAY
Sensor Wires:
Red to #1
Black to #2
Silver Shield to #3
DA-500LKA
Red to #6, NO, Normally Open
Black to #4 NEG/Ground
DA-500 Whistle Switch
MUST be ON
1 2 3 4 5 6 7 8
SENSOR