2.7 

Operation Logic

When the signal (main) pressure is higher than the setting pressure level, the signal pressure 
pushes the upper diaphragm (

), and the pressure will be directed to lower chamber and 

pushes lower diaphragm (

).  Lower diaphragm (

) pushes the pusher (

12

) and the seat 

(

15

),  and  the  air  channel  to  OUT1  port  will  be  opened,  and  the  supply  pressure  will  be 

directed to OUT1 port.  When the signal (main) pressure is lower than the setting pressure 
level, the upper diaphragm (

10

) will be pushed down and will block the channel to the lower 

chamber.  Pressure  from  the  lower  chamber  will  be  exhausted  through  the  hole  in  the 
middle of the upper diaphragm (

), and as the pressure gets lower in the lower chamber, 

the lower diaphragm (

) will be lifted, and the pusher (

12

) and seat (

15

) will be disconnected.   

The supply pressure will be directed to OUT2 port through the seat (

15

).

Содержание YTC YT-520 Series

Страница 1: ...SANP ACTING RELAYS PRODUCT MANUAL YT 520 525 SERIES VERSION 1 01 ...

Страница 2: ...t Description 4 2 1 General 4 2 2 Main Features and Functions 4 2 3 Label Description 4 2 4 Product Number 4 2 5 Product Specification 5 2 6 Parts and Assembly 5 2 7 Operation Logic 6 2 8 Dimension 7 3 Installation 7 3 1 Safety 7 3 2 YT 520 525 Installation 7 3 3 Installation Example 8 4 Maintenance 9 5 Trouble Shooting 9 ...

Страница 3: ...uth Korea 1 2 Manufacturer Warranty For the safety it is important to follow the instructions in the manual Manufacturer will not be responsible for any damages caused by user s negligence Manufacturer will not be responsible for any damages or accidents as a result of any alteration or modification of the product and its parts If any alteration or modifications are necessary please contact Young ...

Страница 4: ... Features and Functions Responses to very small changes to supply pressure with high accuracy Enhanced versatility by having different material of body and options Internal 100 mesh screen filters small dust entering into the product 2 3 Label Description Fig 1 YT 520 525 Body Label A Model Indicates the model number B Air Connection Indicates the connection size C Max Sup Press Indicates maximum ...

Страница 5: ...Output Connection PT NPT 1 4 NPT 1 4 Flow Capacity Cv 0 9 Sensitivity 0 01 MPa Ambient Temperature Standard Temp 20 70 High Option Temp 20 120 Low Option Temp 40 70 Material Aluminum Stainless Steel 316 Weight 0 73 kg 1 2 kg 1 66 kg 3 1 kg Tested under ambient temperature of 20 C absolute pressure of 760mmHg and humidity of 65 Please contact Young Tech Co Ltd for detailed testing specification 2 6...

Страница 6: ...pened and the supply pressure will be directed to OUT1 port When the signal main pressure is lower than the setting pressure level the upper diaphragm 10 will be pushed down and will block the channel to the lower chamber Pressure from the lower chamber will be exhausted through the hole in the middle of the upper diaphragm and as the pressure gets lower in the lower chamber the lower diaphragm wi...

Страница 7: ...cified Use bypass valve or other supportive equipment to avoid entire system shut down Ensure to use filter regulator Use manometer to monitor the pressure level when setting the pressure level 3 2 YT 520 525 Installation YT 520 525 can be installed with or without a bracket depending on the field requirement Please refer to YT 520 525 dimension to build appropriate bracket if required ...

Страница 8: ...8 YT 520 525 series 3 3 Installation Example Double acting linear actuator Single acting rotary actuator ...

Страница 9: ...n the setting pressure level Please check if the setting pressure level is correct If the setting pressure level is extremely high please lower the setting pressure level The factory default setting pressure level is 3 kgf cm2 Supply pressure is not being directed to OUT1 port when the signal pressure is higher than the setting pressure level Please check if the setting pressure level is correct I...