Electrical connection Ireland
All electrical work must be carried out
by a suitably qualified and competent
person, in strict accordance with na-
tional and local safety regulations.
This washer-extractor is supplied as
standard for connection to 230 V 50 Hz
single phase supply, and is not convert-
ible. Fuse rating 25A.
Connection should be made via a suit-
able isolator which complies with na-
tional and local regulations and the
on/off switch should be easily accessi-
ble for servicing work.
For extra safety it is advisable to install
a residual current device (RCD) with a
trip current of 30 mA (in accordance
with DIN VDE 0664, VDE 0100 Section
739).
When switched off there must be an
all-pole contact gap of 3 mm in the iso-
lator switch (including switch, fuses and
relays acc. to VDE 0660).
The voltage, rated load and fuse rating
are given on the data plate. Please en-
sure these match the site mains supply.
WARNING
THIS APPLIANCE MUST
BE EARTHED
Installation
47