Flexible metal ducting has been used
for the following example. Other duct
types may require additional duct
length (see Table 1.)
Example:
Vent connection left . . . . . . . 39" (1.0 m)
Length (L). . . . . . . . . . . . . . . 47" (1.2 m)
Lower radius (R). . . . . . . . . . 19" (0.5 m)
Height (H). . . . . . . . . . . . . . . 39" (1.0 m)
Upper radius (R) . . . . . . . . . 19" (0.5 m)
Wall pipe w/ grill frame . . . . 149" (3.8 m)
Effective duct length . . . . 312" (8.00 m)
Result:
A duct diameter of 4" (100 mm) is ade-
quate since the effective length is less
than 66 ft. (20 m) as specified in
Table 2.
INSTALLATION INSTRUCTIONS
24