background image

Important:

If the exhaust ducting is to run through
rooms, ceiling space etc. where there
may be great variations in temperature
between the different areas, the prob-
lem of condensation will need to be ad-
dressed.The exhaust ducting will need
to be suitably insulated.

Condensate trap

In addition to insulating the exhaust
ducting, we recommend that a suitable
condensate trap is also installed to col-
lect and evaporate any condensate
which may occur.

Condensate traps are available from
builders merchants.

When installing a condensate trap,
ensure that it is positioned vertically
and if possible directly above the ex-
haust connection.

Connection for air extraction

27

Содержание DA 196-2

Страница 1: ...lation instructions Cooker hoods DA 196 2 DA 199 2 To avoid the risk of accidents or damage to the appliance it is essential to read these instructions before it is installed or used for the first time GiWO M Nr 05 609 480 ...

Страница 2: ...care Housing 11 Grease filters 11 Fitting replacing the active charcoal filters 12 Defective lighting 13 Appliance dimensions Installation 16 Assembly parts 16 Retaining plates 18 Canopy 20 Motor unit 21 Air extraction 21 Recirculation 22 Electrical connection 22 Extension piece 24 Fitting the tower 26 Connection for air extraction 27 Condensate trap 28 Electrical connection 29 After sales service...

Страница 3: ...anger of suffocation Rather than just throwing these materi als away please ensure that they are recycled Disposal of your old appliance Old appliances contain materials which can be reclaimed or recycled Please contact your dealer your local waste collection centre or scrap merchant about potential recycling schemes Ensure that the appliance presents no danger to children while being stored for d...

Страница 4: ...ition at all times Any damage which may be caused by cockroaches or other vermin will not be covered by the appliance guarantee Technical safety Before connecting the appliance to the mains supply make sure that the voltage and frequency details given on the data plate correspond with the on site electricity supply otherwise the appliance could get damaged Consult a qualified electrician if in any...

Страница 5: ...lames into the filter Fat particles drawn into the cooker hood present a fire hazard When using the cooker hood over a gas hob ensure that any burners in use are always covered by a pan otherwise flames could be drawn up by the suction of the cooker hood parts of which could then be damaged Always switch the cooker hood on when a cooking zone is in use oth erwise condensation may collect in the ho...

Страница 6: ...tes rooms with fireplaces If exhaust air is to be extracted into a chimney or ventilation duct no longer used for other purposes seek professional advice Using at the same time as other heat ing appliances that depend on the air from the room Warning danger of toxic fumes Great care should be taken when using the cooker hood at the same time and in the same room or area of the house as another hea...

Страница 7: ...t If adequate ventilation can only be achieved through an open window a window contact switch must be fitted This ensures that the hood can only be operated when the window is opened wide enough The advice of a competent builder must be sought The cooker hood is then ready for use A window contact switch kit is available from good builders mer chants Take care when ventilating the room through an ...

Страница 8: ...Tower c Canopy d Sliding switches e Sliding switches f Lighting for hob g Grease filters h Sliding switch for the lighting i Sliding switch for the fan j Sliding switch for the power setting Description of the appliance 8 ...

Страница 9: ...e When frying or cooking food with a strong aroma you can set the sliding switch j to the Intensive IS setting for a short period After cooking If the air still needs to be cleared after cooking we recommend letting the cooker hood continue to run for a fur ther ten minutes Then switch the appliance off Switching off Set the sliding switch for the fan i to 0 Switching the lighting on and off The h...

Страница 10: ... on the non return flap opens for the cook ing vapours to be blown directly out side air recirculation The air is drawn in and cleaned first by the grease filters and then by a char coal filter The cleaned air is then recirculated back into the kitchen through grilles in the top of the cooker hood extension piece Charcoal filters are available to order through your Dealer or the Miele Spare Parts ...

Страница 11: ...would damage the surface Stainless steel Stainless steel surfaces can be cleaned using a proprietary non abrasive clean ing agent designed specifically for use on stainless steel To help prevent re soiling proprietary conditioning agents for stainless steel can also be used Apply sparingly with an even pressure E Cloth A microfibre E Cloth is available from the Miele UK Spare Parts Department Part...

Страница 12: ...o prevent the risk of these catch ing fire When replacing the grease filters make sure the locking clips are visi ble facing down towards the hob Should the grease filters be put back upside down insert a small screwdriver into the slits to disengage them Do not let them drop on to the hob below Fitting replacing the active charcoal filters If the cooker hood is connected for recirculation two act...

Страница 13: ... is withdrawn or the screw out fuse is removed in countries where this is applicable Unscrew the fixing screw of either the right or left hand holder for the glass cover When doing this push the glass cover upwards so that it does not fall on the hob surface Take off the glass cover holder Take out the glass cover guiding it downwards at an angle When changing the light tube also unscrew the secon...

Страница 14: ...ay be pref erable above electric hobs cookers to give more working space When deciding dimension S ensure that the minimum specified safety dis tance between the hob cooker and the cooker hood is maintained If the hood is fitted flush to the ceiling make sure that the remaining distance to the ceil ing is not greater or less than appliance height H Recirculation H 820 1110 mm Extraction H 800 1020...

Страница 15: ...nts the wall or ceiling area for the vent cut out and for fitting the connection socket For recirculation mode the connection socket may only be fitted in a wall area Connection for extraction C 125 mm Appliance dimensions 15 ...

Страница 16: ...Assembly parts Installation 16 ...

Страница 17: ...eturn valve for fitting into the exhaust connection on the motor unit for extraction mode only g Upper retaining plate B for secur ing the extension piece h Middle retaining plate C for addi tional stability for the tower i Lower retaining plate A for secur ing the canopy and the motor unit 12 large headed screws 5 x 40 mm and 12 S 8 plugs for securing the retaining plates and the canopy 2 M 6 loc...

Страница 18: ...e hob surface upwards see Appliance di mensions This marks the height of the lower rim of the cooker hood DA 196 2 Drill an 8 mm C hole on the middle line 18 mm above the height marked S Insert an S8 plug into the hole DA 199 2 Drill two 8 mm C holes 18 mm above the height marked S and 250 mm right and left of centre Insert S8 plugs Retaining plate A Drill two 8 mm C holes one at S 100 mm and one ...

Страница 19: ...aining plate B Hold retaining plate B to the wall and push up until it is directly below the ceiling Use the notches and the mid dle line to align it horizontally Mark the 4 drill holes on the wall Drill two C 8 mm holes into the wall and push the S8 plugs into the holes Screw on the retaining plate with two 5 x 40 mm screws Retaining plate C Retaining plate C only needs to be fit ted if dimension...

Страница 20: ...w on retaining plate C with two 5 x 40 mm screws Canopy Before fitting the canopy the glass cover of the lighting tube must first be removed see relevant section in Cleaning and care Hang the canopy on the angle brack ets on retaining plate A Secure the canopy with 5 x 40 mm screws into each drilled hole DA 196 2 Secure the canopy with a 5 x 40 mm screw DA 199 2 Secure the canopy with two 5 x 40 m...

Страница 21: ...ction If a non return valve is not present in the venting system the non return flap supplied must be fitted onto the exhaust connection in the motor unit The flaps must open upwards For extraction connection secure a flexible hose or an extraction pipe to the exhaust connection on the motor unit using a hose clip Lead the top end to the open air through the wall or ceiling cut out For further ins...

Страница 22: ...se clips Fit the charcoal filters see Cleaning and Care Electrical connection First push the 6 pole plugs on the canopy connection cable into the ter minals on the motor unit Push the cable into the groove shown Pass the connection cable up to the left of the motor and through the ca ble guide Connect the appliance to the mains via a fused spur or fused socket as appropriate Before connecting the ...

Страница 23: ...on For recirculation the extension piece is fitted with the openings at the top For air extraction the openings are not required In this case the extension piece is fitted with the openings at the bottom They are then covered by the tower Before fitting the extension piece re move the protective foil Bend the top hanging retainers approx 45 inwards This makes fit ting easier Recirculation Extracti...

Страница 24: ...Fit the recirculation grilles into the ex tension piece and into the directional unit behind so that the slats point downwards The paper protective sheets protect the extension piece from being scratched when the tower is fitted They are re moved when fitting is complete Fold each protective sheet at the top Remove the protective foil from around the sticking points Stick the protective sheet to t...

Страница 25: ... slide the tower downwards approx 2 cm into the vapour canopy Align the tower Remove the protective sheets Now secure the tower on both sides with 2 screws 3 9 x 7 5 mm Remove the protective foil from the canopy Before using the appliance for the first time take the grease filter out and remove the protective foil from the fil ter frame Then replace the filter Installation 25 ...

Страница 26: ... than 125 mm or flat ducting were used the noise level of the cooker hood would increase and ex traction would be less efficient Only reduce the diameter of the ducting if absolutely necessary e g where narrower ducting has already been installed Only use wide radius bends Tight bends reduce the air throughput of the cooker hood Only use smooth pipes or flexible hoses made from non flammable ma te...

Страница 27: ...ill need to be suitably insulated Condensate trap In addition to insulating the exhaust ducting we recommend that a suitable condensate trap is also installed to col lect and evaporate any condensate which may occur Condensate traps are available from builders merchants When installing a condensate trap ensure that it is positioned vertically and if possible directly above the ex haust connection ...

Страница 28: ... after in stallation depending on country an additional means of disconnection must be provided for all poles For extra safety it is advisable to install a residual current device RCD with a trip current of 30 mA in accordance with DIN VDE 0664 VDE 0100 Sec tion 739 Do not connect via an extension lead Important UK If the appliance is fitted with a non rewireable plug BS 1363 UK and the socket out...

Страница 29: ...loured green and yellow must be connected to the ter minal in the plug which is marked with the letter E or by the earth sym bol or coloured green or green and yellow The wire which is coloured blue must be connected to the terminal which is marked with the letter N or coloured black For U K IRL The wire which is col oured brown must be connected to the terminal which is marked with the letter L o...

Страница 30: ...rvice Department see back cover for address When contacting the Service Depart ment please quote the model and se rial number of your appliance These are shown on the data plate which is visible when the grease filters are removed Please note that telephone calls may be monitored and recorded to im prove our service After Sales Service 30 ...

Страница 31: ...rating 10 A Test marks Electrical safety C Tick Mark Electrically suppressed according to AS NZS 1044 Fan performance Extraction power according to EN 61591 Extraction system C 125 mm Levels 1 3 200 380 m3 h Intensive level IS 485 m3 h Unrestricted 560 m3 h Recirculation with charcoal filter Levels 1 3 180 340 m3 h Intensive level IS 420 m3 h Charcoal filter Miele Active charcoal filter DKF 6 Tech...

Страница 32: ...Änderungen vorbehalten 0604 Dieses Papier besteht aus 100 chlorfrei gebleichtem Zellstoff und ist somit umweltschonend M Nr 05 609 480 V02 ...

Отзывы: