27
2. Press
or
to scroll to
2. TEST BATTERY
and press
ENTER
.
Note:
You can also start a test by connecting to a jar when the analyzer is turned off.
Attaching the cables
Introduction
After you turn on the analyzer and set the
TEST BATTERY
option, you are ready to test. To test a
string, you need to attach the clamp or probe cables to the first jar in the string.
Note:
The figures in this section show probes connecting to the jar posts or straps. However,
you can connect the clamps in the same positions.
General rules
You should follow these guidelines when testing a jar:
•
Do not place probes or clamps on stainless steel hardware, such as bolt heads, washers, or
threaded posts. Stainless steel hardware can yield low conductance values. If you have to
test on stainless steel, record it in your testing records.
•
The jars might have grease on the terminals and connections to prevent corrosion. You do
not have to wipe off the grease before connecting the probes or attaching the clamps.
•
Test each jar in the same location or position. Changing the location of the test point
might vary test results.
Attaching the cable to jar posts
To attach the cable to the jar:
1. Press the black probe tip against the black (–) terminal. Refer to Figure 7.
2. Press the red probe tip against the red (+) terminal.
CONNECT TO BATTERY
J001A
TO TEST
READY TO TEST
Содержание Celltron Essential
Страница 1: ...INSTRUCTION MANUAL TEC 4500 TEC 4500 BP Stationary Battery String Analyzer...