          MNROSIE7048 MANUAL

 

 
 

54| P a g e                                                                                                     1 0 - 4 3 2 - 1         R E V : -  

 

 

 

 

CSA TABLE 65.1 

 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 

Unit Ratings 

(Per UL1741, Table 65.1) 

Rating Type 

Standalone (SA) 

SA w CC

1

 

Max input voltage (DC) 

68V 

Range of input operating voltage (DC) 

40 to 65VDC 

Max input current (AC or DC) 

210ADC 

Max input short circuit current 

210ADC

 

60AAC 

Output power factor rating 

7000W w/PF=1.0 

Operating voltage range (AC) 

82 to 140VAC 

Operating frequency range or single frequency 

48 to 72Hz 

Nominal output voltage (AC) 

120/240V

RMS

 

Nominal output frequency 

60Hz 

Max continuous output current (AC) 

29.2A

RMS

 

Max continuous output power (AC) 

7000VA 

Max output fault current / duration (AC)

 

62.5AAC 

(

5 secs)

 

5kAAC 

(

10mSec)

 

Max output overcurrent protection (amps) 

60AAC 

300ADC 

Nominal output voltage (DC) 

48VDC 

Charging output voltage (DC) 

40 to 65VDC 

Normal operating temperature range 

-20 to 60°C 

Output power temp derate/max power ambient 

75% derated @ 60°C ambient 

(75°C Internal)

 

Conductor AWG range    

20 to 2 AWG 

2/0 to 4/0 AWG 

All ratings based on 25°C ambient, unless otherwise noted. 
Note

1

: CC is Charge Controller (I

nverter’s internal charger)

 

Содержание MNROSIE7048M

Страница 1: ...4 3 2 1 R E V Rosie Inverter Charger Owner s Manual MNROSIE7048RE MNROSIE7048M This entire manual is printed without color but is available for download with many of the diagrams available in color on...

Страница 2: ...t Ground Fault 15 Special Instructions for MNROSIE7048M Mobile Installations 15 Installation 18 Mounting 20 Wiring the Rosie 20 DC Wiring 20 AC Wiring 22 Grounding 22 Torque Values 25 External Sensors...

Страница 3: ...lay and 120 amp multi stage PFC battery charger This unit is safety listed to UL1741 and CSA The AC IN and OUT Neutrals are NOT common to allow automatic neutral to ground switching for Mobile applica...

Страница 4: ...instructions and cautionary markings The installation instructions are for use by qualified personnel only Do not perform any installation other than that specified in this manual unless you are qual...

Страница 5: ...eakers installed as a part of this Rosie inverter charger system shall comply with CSA C22 2 No 235 and meet all the following o Have a short circuit application code of U3 o Have a tripping current a...

Страница 6: ...ction against overloads There are no user serviceable parts contained in the Rosie Always verify proper wiring prior to starting the inverter The inverter must be properly mounted BATTERY SAFETY Wear...

Страница 7: ...tions always vent batteries from the highest point to the outside Design the battery enclosure to prevent accumulation and concentration of hydrogen gas in pockets at the top of the compartment Remove...

Страница 8: ...pment for Use with Distributed Energy Resources UL 1741 2010 Ed 2 R 15Feb2018 CSA C22 2 107 1 2016 Ed 4 and UL 458 2015Ed 6 Power Converters Inverters and Power Converter Inverter Systems for Land Veh...

Страница 9: ...mple space between cells for cooling We recommend at least one inch between the cells for cooling Ask the battery manufacturer what they recommend Not having enough charge current to properly charge t...

Страница 10: ...to power the system while the batteries recharge Mobile Installations Inverters can also be used to provide power in mobile situations such as in an RV truck or boat In these applications the inverte...

Страница 11: ...proximately every 6 This helps improve the surge capability and reduces the effects of inductance which improves the inverter waveform and reduces wear of the inverter s filter capacitors All wiring t...

Страница 12: ...ttery bank on the positive cable Limit cable length to 6 or less from Rosie to battery bank The battery bank voltage MUST be 48V DC Over Current Protection The NEC requires both over current protectio...

Страница 13: ...also listed to be installed in the sub panel The AC wiring must be protected from short circuits and overloads by an over current protection device UL1077 standards and have a means to disconnect the...

Страница 14: ...onds to a minimum cable size of 6 AWG The AC over current protection device must be a circuit breaker or a fuse disconnect and be properly sized and branch circuit rated for the wire it is protecting...

Страница 15: ...NS Grounding on Boats When installing the MNROSIE7048M on a boat there are several considerations that must be followed when grounding to ensure a safe installation to prevent galvanic corrosion and t...

Страница 16: ...t s AC wiring system is connected to the other side Since transformers do not allow DC currents to pass the problem with galvanic corrosion is eliminated ABYC Inverter Charger Grounding Requirements D...

Страница 17: ...s the utility feed in your home an inverter or a generator This ensures a circuit breaker will activate if a hot wire to ground fault occurs The Standards also require that the AC neutral be connected...

Страница 18: ...ource s neutral INSTALLATION Before installing read the entire installation section to determine how you are going to install your Rosie The more thoroughly you plan in the beginning the better your o...

Страница 19: ...ely mounted MNGP2 MidNite Graphics Panel You will need to access the MNGP2 during and after installation The Rosie should be protected from direct sun exposure or equipment that produces extreme heat...

Страница 20: ...f mating the Rosie with the E panel refer to the E Panel Manual for installation and wiring WIRING THE ROSIE Take note of the terminal blocks and wiring connection points of the Rosie Figures 3 4 Refe...

Страница 21: ...1 P a g e 1 0 4 3 2 1 R E V DC Equipment Ground Figure 6 Figure 3 Battery Terminals External Sensor Terminals AC Terminals AC Equipment Ground DC Equipment Ground Figure 4 Figure 5 AUX Wiring CANBUS B...

Страница 22: ...1 or 240VAC L1 and L2 4 Connect 6 AWG Neutral to the AC electrical panel and the AC OUT terminal block N 5 Torque AC terminal block Page 28 for torque specs Grounding Proper grounding is critically im...

Страница 23: ...or cable that does not carry current and connects the Grounding Electrode GE ground rod to the Grounded Conductor GC and the Equipment Grounding Conductor EGC Grounding Electrode GE ground rod System...

Страница 24: ...Determined by the gauge of the GC AC NEC allows 8 AWG GEC if the GC AC is 6 AWG 4 8 AWG Equipment Grounding Conductor EGC AC Determined by the size of the over current device which is the 60A AC break...

Страница 25: ...it can be disconnected during servicing Torque Values AC Terminal Block o For 6 AWG wire torque to 22 in lbs AC Ground Terminal Block o For 8 AWG wire torque to 40 in lbs o For 4 6 AWG wire torque to...

Страница 26: ...tery case clean that area remove the protective tape and affix the BTS sensor to the battery wall Consult battery manufacturer for optimal placement Current Transformer CT Terminals 3 Two terminals av...

Страница 27: ...WBJr purple wire is pointing to the right as shown then the shunt s big right bolt is connected to the battery bank s master negative terminal There can ONLY be ONE wire connected to this shunt bolt b...

Страница 28: ...or battery bank voltage between the Rosie s Batt and Batt terminals o Battery bank voltage present Yes Good The Rosie will automatically turn on now No Check DC wiring or battery breaker Turn on AC IN...

Страница 29: ...20VAC present Yes Good No Check wiring breakers or connections Voltmeter Measure for 120VAC between AC L2 and AC Neutral terminals at the AC electrical panel o 120VAC present Yes Good No Check wiring...

Страница 30: ...e voltage This comes from the battery manufacturer Sometimes called Bulk Constant Voltage or Boost charge voltage Absorb Time Amount of time the Rosie stays in the Absorb charging cycle Lithium batts...

Страница 31: ...the system which one is connected to the WBJr o Battery Only one WBJr in system monitoring current to from the battery bank o Additive If more than one WBJr in the system the SOC readings are amalgam...

Страница 32: ...IN circuit breaker The Rosie will not allow charging amps to exceed the max ampacity of this AC IN breaker Inverter Specific o AUX Functions Select desired AUX modes for AUX 1 and or AUX 2 o External...

Страница 33: ...he voltage pops above the threshold before the grid becomes valid LBX will be reset and will not connect to grid HBX Set to high Batt V setpoint If the voltage goes above HBX threshold for 1 minute an...

Страница 34: ...r AC OUT to dedicated sub panel or main service without any other AC IN source Parallel Threshold ON or OFF Power setting determines when additional inverters are brought online to power loads Power S...

Страница 35: ...hat data logging is correct USER DISPLAY Contrast Adjust sharpness of letters and numbers Brightness Adjust intensity of LCD backlight Light Timeout Set time to turn off LCD backlight or leave it alwa...

Страница 36: ...MNROSIE7048 MANUAL 36 P a g e 1 0 4 3 2 1 R E V...

Страница 37: ...MNROSIE7048 MANUAL 37 P a g e 1 0 4 3 2 1 R E V...

Страница 38: ...MNROSIE7048 MANUAL 38 P a g e 1 0 4 3 2 1 R E V...

Страница 39: ...MNROSIE7048 MANUAL 39 P a g e 1 0 4 3 2 1 R E V...

Страница 40: ...MNROSIE7048 MANUAL 40 P a g e 1 0 4 3 2 1 R E V...

Страница 41: ...MNROSIE7048 MANUAL 41 P a g e 1 0 4 3 2 1 R E V...

Страница 42: ...MNROSIE7048 MANUAL 42 P a g e 1 0 4 3 2 1 R E V...

Страница 43: ...ium batteries reach the Absorb voltage setpoint they are normally full and done charging Check with your Lithium battery manufacturer for further guidance on the amount of Absorb Time Absorb Charge Ti...

Страница 44: ...ke the same charging and discharging voltages during normal operation For the cells to see the same voltage amongst the cells promotes battery health and longevity Confirm with your battery manufactur...

Страница 45: ...mA thus an external relay is required between the accessory and a power source The AUX circuit will trigger this relay on off The Rosie has many different AUX modes to choose from based on how you wan...

Страница 46: ...ow Y N OFF Batt V Timer till OFF Batt V Timer till ON Batt Temp High Y N ON XX F C XX F C Batt Temp Low Y N OFF XX F C XX F C PCB Temp Y N ON XX F C XX F C FET Temp Y N ON XX F C XX F C FIRMWARE UPDAT...

Страница 47: ...MNROSIE7048 MANUAL 47 P a g e 1 0 4 3 2 1 R E V Figure 15 Tap Here Figure 16 Figure 17 Figure 18 Figure 19...

Страница 48: ...MNROSIE7048 MANUAL 48 P a g e 1 0 4 3 2 1 R E V...

Страница 49: ...MNROSIE7048 MANUAL 49 P a g e 1 0 4 3 2 1 R E V...

Страница 50: ...MNROSIE7048 MANUAL 50 P a g e 1 0 4 3 2 1 R E V...

Страница 51: ...MNROSIE7048 MANUAL 51 P a g e 1 0 4 3 2 1 R E V...

Страница 52: ...MNROSIE7048 MANUAL 52 P a g e 1 0 4 3 2 1 R E V...

Страница 53: ...MNROSIE7048 MANUAL 53 P a g e 1 0 4 3 2 1 R E V...

Страница 54: ...Nominal output voltage AC 120 240VRMS Nominal output frequency 60Hz Max continuous output current AC 29 2ARMS Max continuous output power AC 7000VA Max output fault current duration AC 62 5AAC 5 secs...

Страница 55: ...MNROSIE7048 MANUAL 55 P a g e 1 0 4 3 2 1 R E V TECHNICAL SPECIFICATIONS DECAL SET...

Страница 56: ...ct MidNite Solar Inc 360 403 7207 Purchasers must prepay all delivery costs or shipping charges to return any defective MidNite Solar product under this warranty policy Except for the warranty that th...

Страница 57: ...cally agreed to in writing MidNite Solar Inc a Makes no warranty as to the accuracy sufficiency or suitability of any technical or other information provided in its manuals or other documentation b As...