Silent Four-way Cassette MCAC-VTSM-2017-01
97
8. Electrical characteristics
Model
Indoor unit
Power supply
IFM
Hz
Voltage
Min.
Max.
MCA
MFA
kW
FLA
MDV-D28Q4/N1-E
50
220-240
198
264
0.31
15
0.026
0.248
MDV-D36Q4/V1-E
50
220-240
198
264
0.31
15
0.026
0.248
MDV-D45Q4/N1-E
50
220-240
198
264
0.41
15
0.026
0.328
MDV-D56Q4/N1-E
50
220-240
198
264
0.41
15
0.026
0.328
MDV-D71Q4/N1-E
50
220-240
198
264
0.41
15
0.03
0.328
MDV-D80Q4/N1-E
50
220-240
198
264
0.48
15
0.037
0.384
MDV-D90Q4/N1-E
50
220-240
198
264
0.67
15
0.05
0.536
MDV-D100Q4/N1-E
50
220-240
198
264
0.72
15
0.065
0.576
MDV-D112Q4/N1-E
50
220-240
198
264
0.72
15
0.065
0.576
MDV-D140Q4/N1-E
50
220-240
198
264
0.75
15
0.065
0.6
Remarks:
MCA:
Min. Current Amps. (A)
MFA:
Max. Fuse Amps. (A)
kW:
Fan Motor Rated Output (kW)
FLA:
Full Load Amps. (A)
IFM:
Indoor Fan Motor
Note:
1) Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above
listed range limits.
2) Maximum allowable voltage unbalance between phase is 2%.
3) MCA
MCA = 1.25 × FLA
4) Select wire size based on the MCA.
5) Instead of fuse, use Circuit Breaker.