MIV V4+ Indoor Units
DM12-01.01.02-06en
6
Middle Static Pressure Duct Type MVM-A-VA1
Model MVM80A-VA1
MVM90A-VA1
MVM112A-VA1
MVM140A-VA1
Power supply
V- Ph-Hz
220-240V~, 1Ph, 50Hz
Cooling
Capacity kW
8 9
11.2
14
Input W
198 200 313 274
Rated current
A
1
1
1.8
1.8
Heating
Capacity kW
9 10
12.5
15.5
Input W
198 200 313 274
Rated current
A
1.16
1.16
1.65
1.8
Indoor fan
motor
Model
YSK100-4P YSK100-4P YSK200-4P YSK180-4P
Type
AC MOTOR
Brand
Welling
Input W
179
179
300
255
Capacitor
μ
F
10UF/450V 10UF/450V 10UF/450V 10UF/450V
Speed (hi/mid/lo)
r/min
935/810/700/620 935/810/700/620 1130/1000/870/770 1080/960/830/710
Indoor coil
Number of rows
4
4
4
4
Tube
pitch(a)*rowpitch(b)
mm
21X13.5 21X13.5 21X13.5 25.4X22
Fin spacing
mm
1.5
1.5
1.5
1.5
Fin type
Hydrophilic
aluminum
Tube outside
diameter and type
mm
Ф
7
inner groove tube
length * height * width
mm
955*54*336
955*54*336
955*54*336
103088*457.2
Number of circuits
5 8 8 8
Indoor air flow ( (SH)/H/M/L)
m
3
/h
(1400)1226/101
8/861
(1400)1226/101
8/861
(1750)/1752/15
52/1389
(2138)/
1918/1539/1250
Indoor external static pressure (Hi)
Pa 20(10~50)) 20(10~50)) 40(10~80)) 40(10~80)
Indoor noise level (Hi/Mid/Lo)
dB(A)
45.4/39.8/37 45.4/39.8/37 48.0
/41.9/38 47.7/43.2/39.0
Indoor unit
Dimension (W×H×D)
mm
1140*270*710
1140*270*710
1140*270*710
1200*300*800
Packing (W×H×D)
mm
1355*350*795
1355*350*795
1355*350*795
1385*375*920
Net/Gross weight
kg
38/46.5 40/48 40/48 49/58
Fresh Air intake hole diameter (round)
mm
Ф
125
Ф
125
Ф
125
Ф
125
Refrigerant type
R410A
Throttle
Type
Removable EXV (screw connection)
Model BD24FKS(L)
Design pressure
MPa
4.4/2.6
Refrigerant piping
Liquid / Gas
mm
Ф
9.53/
Ф
15.9 9.53/
Ф
15.9
Ф
9.53/
Ф
15.9
Ф
9.53/
Ф
15.9
Connecting wiring
Power wiring
mm
2
3
×
2.5(L
≤
20m); 3
×
3.5(L
≤
50m)
Signal wiring
mm
2
3*0.75
Drainage water pipe diameter
Ф
32 (ID
Ф
25, OU
Ф
32)
Controller
Wireless remote controller (RM05/BG(T)E-A) - Standard
KJR-12B/DP(T)-E/ KJR-10B/DP(T)-E (6 m connection wire) - optional
Operation temp
℃
Cooling
:
17
~
32
;
Heating:10
~
28
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temp. : 27°CDB, 19°CWB, outdoor
temp.:35°CDB,equivalent ref. Piping: 8m(horizontal)
2. Nominal heating capacities are based on the following conditions: return air temp.: 20°CDB,outdoor temp.:
7°CDB,6°CWB,equivalent ref. Piping: 8m(horizontal)