Installation
Page 102
6. Refrigerant Pipe Installation
6.1 Maximum length and drop height
Ensure that the length of the refrigerant pipe, the number
of bends, and the drop height between the indoor and
outdoor units meets the requirements shown in the
following table.
Capacity(k
Btu/h
)
Max. Length
(m/ft)
Max. Elevation
(m/ft)
18
30/98.4
20/65.6
24
50/164
25/82
36~55
65/213.3
30/98.4
caution:
• The capacity test is based on the standard length and
the maximum permissive length is based on the system
reliability.
• Oil traps
If the indoor unit is installed higher than the outdoor unit:
-If oil flows back into the outdoor unit’s compressor, this
might cause liquid compression or deterioration of oil
return. Oil traps in the rising gas piping can prevent this.
An oil trap should be installed every 10m(32.8ft) of vertical
suction line riser.
The indoor unit is installed higher than the outdoor unit
If the outdoor unit is installed higher than the indoor unit:
-It is recommended that vertical suction risers not be
upsized. Proper oil return to the compressor should be
maintained with suction gas velocity. If velocities drop
below 7.62m/s(1500fpm (feet per minute)), oil return
will be decreased. An oil trap should be installed every
6m(20ft) of vertical suction line riser.
The outdoor unit is installed higher than the indoor unit.
6.2 The procedure of connecting pipes
1.Choose the pipe size according to the specification table.
2.Confirm the cross way of the pipes.
3.Measure the necessary pipe length.
4.Cut the selected pipe with pipe cutter
•
Make the section flat and smooth.
Oblique
Rough
Warped
90
5. Insulate the copper pipe
•
Before test operation, the joint parts should not be
heat insulated.
6. Flare the pipe
•
Insert a flare nut into the pipe before flaring the
pipe
•
According to the following table to flare the pipe.
Содержание MUE-42HRFNX-QRD0
Страница 15: ...Specifications Page 15 4 Centre of gravity MOB30U 18HFN8 QRD0 MOCA30U 24HFN8 QRD0...
Страница 16: ...Specifications Page 16 MOD30U 30HFN8 QRD0 MOD30U 36HFN8 QRD0 MOD30U 36HFN8 RRD0 MOD30U 42HFN8 QRD0...
Страница 17: ...Specifications Page 17 MOE30U 48HFN8 RRD0 MOE30U 55HFN8 RRD0...
Страница 32: ...Specifications Page 32 MOE30U 48HFN8 RRD0 MOE30U 55HFN8 RRD0...