Service manual 

 

8.4 

Air purging of the piping and indoor unit 

Required tools: 
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector. 
Note: 
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it will 
affect the compressor, reduce the cooling capacity, and could lead to a malfunction of unit. 
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it 
prevents the gas leakage from the refrigeration cycle. 
 

 

 

6. Set the 3-way valve to the opened 

position. 

Procedure 

1. Recheck the piping connections. 
2. Open the valve stem of the 2-way valve 

counterclockwise approximately 90’, wait 
10 seconds, and then set it to closed 
position. 

7. Mounted the valve stem nuts to the 2-way 

and 3-way valves. 

8. Check for gas leakage. 

 

At this time, especially check for gas leakage 
from the 2-way and 3-way stem nuts, and 
from the service port. 

 

Be sure to use a hexagonal wrench to operate 
the valve stem 

3. Check for gas leakage. 

 

 

Check the flare connection for gas leakage 

Caution: 

4. Purge the air from the system. 

If gas leakage is discovered in step (3) above, 
take the following measures. 

 

Set the 2-way valve to the open position and 
remove the cap from the 3-way valve’s 
service port. 

If the leaks stop when the piping connections are 
tightened further, continue working from step (4). 

 

Using the hexagonal wrench to press the 
valve core pin, discharge for three seconds 
and then wait for one minute. 

If the gas leaks do not stop when the connections 
are retightened, repair the location of the leak, 
discharge all of the gas through the service port, 
and then recharge with the specified amount of 
gas from a gas cylinder. 

5. Use torque wrench to tighten the service 

port cap to a torque of 1.8 kg.m. (18n.m) 

15 

 

Содержание MSV1-09HRDN1

Страница 1: ...Cover MSV1 09HRDN1 MSV1 12HRDN1...

Страница 2: ...ngth and the elevation 14 8 4 Air purging of the piping and indoor unit 15 8 5 Pumping down Re installation 16 8 6 Re air purging Re installation 17 8 7 Balance refrigerant of the 2 way 3 way valves 1...

Страница 3: ...it Error Display 31 13 2 Diagnostic chart 36 13 3 Resetting phenomenon often occurs during operation 38 13 4 Operation lamp flashes and Timer lamp off 38 13 5 Operation lamp flashes and Timer lamp on...

Страница 4: ......

Страница 5: ...very high and a door or a windows is left open Moisture may condense and wet or damage furniture Take care to ensure that power cable could not be pulled out or damaged during operation There is risk...

Страница 6: ...a precision refrigerant system There is risk of damage or loss of property Do not block the inlet or outlet of air flow It may cause product failure Use a soft cloth to clean Do not use harsh deterge...

Страница 7: ...n is turn to low speed cooling heating The unit will be turn off at the seventh hour Sleep mode auto control The function is usually used in rainy days in springtime or damp areas Independent dehumidi...

Страница 8: ...ly The hydrophilic fin can improve the heating efficiency at operation mode Hydrophilic aluminum fin It is only operated in the heating operation mode except defrosting operation Anti rust cabinet Val...

Страница 9: ...Service manual 3 Dimension 3 1 Indoor unit Vertu Dimension W H D 5 Mode 9K 795 270 165 12K 845 286 165 3 2 Outdoor unit Vertu Dimension W H D Mode 9K 760 590 285 12K 760 590 285...

Страница 10: ...min 1150 1000 850 1250 1050 900 m3 h 570 480 350 700 520 420 dB A 40 34 29 42 35 29 Model YDK24 6F YDK24 6F Brand Welling Welling Input W 56 56 Capacitor uF 2 5 2 5 Speed r min 800 800 m3 h 1700 1900...

Страница 11: ...Service manual 5 Refrigerant cycle diagram 7...

Страница 12: ...rom the continuous operation under constant air temperature conditions However excludes the initial pull down stage 6 2 Heating operation Indoor air temp DB Outdoor unit air temp DB Note The chart is...

Страница 13: ...Service manual 7 Schematic diagram and Wiring diagram 7 1 Schematic diagram 7 1 1 Display board 9...

Страница 14: ...Service manual 7 1 2 Indoor main PCB 10...

Страница 15: ...Service manual 7 1 3 Outdoor main PCB 11...

Страница 16: ...Service manual 7 1 4 Outdoor power PCB 12...

Страница 17: ...Service manual 7 2 Wiring diagram 7 2 1 MSV1 09HRDN1 MSV1 12HRDN1 13...

Страница 18: ...Unit 7K 9K 12K mm2 1 0 1 0 1 5 8 3 Pipe length and the elevation 14 Pipe size Capacity Btu h GAS LIQUID Standard length Max Max Additional Elevation Elevation refrigerant m B m B m g m 3 8 9 52 1 4 6...

Страница 19: ...nd 3 way valves 8 Check for gas leakage At this time especially check for gas leakage from the 2 way and 3 way stem nuts and from the service port Be sure to use a hexagonal wrench to operate the valv...

Страница 20: ...rge hose with the push pin to the gas service port 4 Air purging of the charge hose Open the low pressure valve on the charge set slightly to purge air from the charge hose 5 Set the 2 way valve to th...

Страница 21: ...minutes repeat 3 times After purging the air use a torque wrench to tighten the flare nut to on the 2 way valve 4 Check the gas leakage Check the flare connections for gas leakage 5 Discharge the refr...

Страница 22: ...service port 3 Open the valves Low side on the charge set and discharge the refrigerant until the gauge indicates 0 05 to 0 1 Mpa If there is no air in the refrigeration cycle the pressure when the ai...

Страница 23: ...s moved toward 0 1 Mpa 76 cmHg vacuum of 4 mmHg or less 3 Close the valve Low side on the charge set turn off the vacuum pump and confirm that the gauge needle does not move approximately 5 minutes af...

Страница 24: ...pecified amount of refrigerant if can be charged with a little at a time approximately 150g each time0 while operating the air conditioner in the cooling cycle however one time is not sufficient wait...

Страница 25: ...C Pressure kg cm2 34 0 33 5 32 0 31 0 28 0 27 0 18 C Pressure kg cm2 35 0 34 5 34 0 32 5 29 0 27 5 20 C Pressure kg cm2 36 5 36 0 35 5 33 5 30 0 28 5 22 C Pressure kg cm2 37 0 36 5 36 0 35 0 31 5 29...

Страница 26: ...56 1 51 1 39 1 37 1 30 Capacity kW 3 45 4 10 4 05 3 70 3 48 3 11 2 99 1 70 18 C Input kW 0 96 1 55 1 58 1 60 1 52 1 40 1 38 1 32 Capacity kW 3 44 4 05 2 87 3 69 3 47 3 00 2 86 1 69 20 C Input kW 0 96...

Страница 27: ...9 2 01 1 99 1 80 1 76 Capacity kW 4 801 6 09 5 58 5 02 4 39 4 10 3 59 3 27 18 C Input kW 1 6 2 18 2 39 2 20 2 16 2 09 1 83 1 81 Capacity kW 4 684 5 89 4 03 4 90 4 21 3 89 3 37 3 11 20 C Input kW 1 658...

Страница 28: ...osting automatically or when the warm air control feature is activated in heating mode 11 1 6 TURBO indication lamp Lights up when select TURBO function on cooling operation or on heating operation 11...

Страница 29: ...o signals in 4 minutes the unit stops and LED displays failure information and can t return to normal operation automatically 11 3 Fan only mode Fan speed is high mid low Auto 11 4 Cooling mode 11 4 1...

Страница 30: ...ing mode or turned off 4 way valve doesn t delay in dehumidifying mode 11 6 2 Generally the outdoor fan is turned off with the on off action of compressor in heating mode except for the defrosting mod...

Страница 31: ...ger remains consecutively lower than 3 c for more than 80 minutes and the temperature remains consecutively 2 c for more than 3 minutes 11 7 1 2 When outdoor temp is less than 0 Defrosting starts when...

Страница 32: ...l switch 11 10 1 Mode changes when push this button Cooing mode Auto mode Unit off Cooing mode 11 10 2 At Cooing mode after 30 minutes cooling operation whose fan speed is set as low the A C operates...

Страница 33: ...ates in accordance with selected running mode by auto mode 11 12 5 After 7 hours unit cancels this modes automatically 11 13 Auto restart function In case of a sudden power failure this function autom...

Страница 34: ...8 38 F3 45 48 45 48 F4 52 57 52 57 F5 57 66 57 66 F6 64 76 64 76 F7 74 84 74 84 F8 86 90 86 90 F9 92 94 92 94 F10 96 98 96 98 I1COOL 6 0 6 5 6 0 6 5 I2COOL 7 0 8 3 7 0 8 3 I3COOL 8 5 9 5 8 5 9 5 I1HEA...

Страница 35: ...ure sensor open or short circuit of P0 Module protection P1 Over voltage or too low voltage protection P2 Compressor top protection against temperature P3 Outdoor low temp protection P4 Inverter compr...

Страница 36: ...s defective Yes Yes Does the led on outdoor control board bright No YES Replace the module board The power supply of PCB is supplied by the module board Replace the outdoor power supply board Yes Is t...

Страница 37: ...r connection good Is voltage being applied to the fan motor rang 90v 160v between mid pin and N on CN1 No Indoor fan motor is defective Repair the connector No Yes Indoor PCB is defective Is connectio...

Страница 38: ...the wires to compressor right Check the inverter module If some component cracked or damaged Is it breakdown between P N P U P V N W N U N V At inverter module Check compressor Inverter module is defe...

Страница 39: ...circulation volume normal Gas charging Is abnormality the same after gas charging Check refrigerant system such as clogging of ill t Is protector normal Check the outdoor main PCB Replace protector N...

Страница 40: ...lighted and the air conditioner can t be operated Reconnecting Yes Replace outdoor main PCB If the problem can not be solved replace inverter module Replace inverter compressor No If the problem comes...

Страница 41: ...eck if AC 220V exists at the primary coil of transformer Yes YES No Check if AC 14 5V exists at the secondary coil of transformer Indoor PCB is defective Take off the secondary plug of transformer and...

Страница 42: ...er changing indoor PCB check if the failure realease Yes After changing indoor fan motor check if the failure realease Yes YES Yes Power supply circuit has problems Indoor PCB is defective 13 4 Operat...

Страница 43: ...changing the main control board check if the failure realease Power supply fault No Outdoor unit fault such as the compressor 13 7 Operation lamp on and Timer lamp flashes EEROM error indoor PCB is de...

Страница 44: ...10 52 3 1918 1 37 1988 26 9 5507 53 3 0707 0 35 2024 27 9 1245 54 2 959 1 33 3269 28 8 7198 55 2 8442 2 31 5635 29 8 3357 56 2 7382 3 29 9058 30 7 9708 57 2 6368 4 28 3459 31 7 6241 58 2 5397 5 26 877...

Отзывы: