Service manual 

- 24 - 

 

 

8.6 

Re-air purging (Re-installation) 

 

Procedure: 

1.  Confirm that both the 2-way and 3-way valves are set to the closed position. 

2.  Connect the charge set and a charging cylinder to the service port of the 3-way valve. 

§

 Leave the valve on the charging cylinder closed. 

3.  Air purging. 

§

 Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut 

on the 2-way valve approximately 45’ for 3 seconds then closing it for 1 minutes; repeat 3 times. 

§

 After purging the air, use a torque wrench to tighten the flare nut to on the 2-way valve. 

4.  Check the gas leakage. 

§

 Check the flare connections for gas leakage. 

5.  Discharge the refrigerant. 

§

 Close the valve on the charging cylinder and discharge the refrigerant until the gauge indicate 0.3 to 

0.5 Mpa. 

6.  Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to 

the open position. 

§

 Be sure to use a hexagonal wrench to operate the valve stems. 

7.  Mount the valve stems nuts and the service port cap.   

§

 Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m. 

§

 Be sure to check the gas leakage.

Содержание MSG-05CR

Страница 1: ...MSG 05CR MSG 07CR MSG 07HR MSG 09CR MSG 09HR MSG 12CR MSG 12HR MSG 16CR MSG 16HR MSG 18CR MSG 18HR MSG 21CR MSG 21HR...

Страница 2: ......

Страница 3: ...ails 21 8 1 Wrench torque sheet for installation 21 8 2 Connecting the cables 21 8 3 Pipe length and the elevation 21 8 4 Air purging of the piping and indoor unit 22 8 5 Pumping down Re installation...

Страница 4: ...40 10 12 Sleep mode 40 10 13 Auto restart function 41 10 14 Anion optional 41 11 Model and Parameters 42 12 Troubleshooting 43 12 1 Display board 43 12 2 Troubleshooting 44 12 3 Diagnostic chart 45 1...

Страница 5: ...n Be sure the installation area does not deteriorate with age If the base collapses the air conditioner could fall with it causing property damage product failure and personal injury n Do not let the...

Страница 6: ...ional n Do not expose the skin directly to cool air for long periods of time Do not sit in the draft This could harm to your health n Do not use the product for special purposes such as preserving foo...

Страница 7: ...r each operation mode The unit will decide the louver direction according to operation mode Two direction air vane The fan is turn to low speed cooling heating The unit will be turn off after seven ho...

Страница 8: ...unit run more quietly Low noise air flow system The hydrophilic fin can improve the heating efficiency at operation mode Hydrophilic aluminum fin It is only operated in the heating operation mode exce...

Страница 9: ...Service manual 5 3 Dimension 3 1 Indoor unit Dimension Mode W H L 5K 750 250 188 7K 750 250 188 9K 750 250 188 12K 750 250 188 16K 906 286 235 18K 906 286 235 21K 906 286 235...

Страница 10: ...unit Dimension Mode W H D L1 L2 L3 5K 700 535 235 458 280 540 7K 700 535 235 458 280 540 9K 700 535 235 458 280 540 12K 780 540 250 530 315 590 16K 780 540 250 530 315 590 18K 760 590 285 540 335 615...

Страница 11: ...60 900 1020 960 900 m3 h 300 270 240 380 350 320 380 350 320 dB A 32 30 28 32 30 28 32 30 28 Model YDK24 6T YDK24 6T YDK24 6T Brand WELLING WELLING WELLING Input W 70 70 70 Capacitor uF 3 3 3 Speed r...

Страница 12: ...50 m3 h 450 420 390 450 420 390 550 500 460 dB A 37 34 31 37 34 31 41 38 34 Model YDK24 6T YDK24 6T YDK24 6 Brand WELLING WELLING WELLING Input W 55 55 72 Capacitor uF 2 5 F 450V 2 5 F 450V 2 5 F 450V...

Страница 13: ...750 710 650 750 710 650 dB A 41 38 34 41 38 35 41 38 35 Model YDK24 6 YDK36 6 YDK36 6 Brand WELLING WELLING WELLING Input W 72 96 96 Capacitor uF 2 5 F 450V 2 5 F 450V 2 5 F 450V Speed r min 850 900 9...

Страница 14: ...00 760 700 dB A 41 38 35 41 38 35 41 37 33 Model YDK25 6H YDK25 6H YDK53 6 Brand WELLING WELLING WELLING Input W 96 96 100 Capacitor uF 2 5 F 450V 2 5 F 450V 2 5 F 450V Speed r min 900 900 640 m 3 h 2...

Страница 15: ...00 Capacitor uF 2 5 F 450V Speed r min 640 m 3 h 2200 dB A 54 g 1740 MPa 2 6 Liquid side Gas side mm 6 35 12 7 Max refrigerant pipe length m 20 Max difference in level m 10 17 30 7 45 m 2 34 49 Model...

Страница 16: ...Service manual 12 5 Refrigerant cycle diagram Cooling only Heat pump mode...

Страница 17: ...The chart is the result from the continuous operation under constant air temperature conditions However excludes the initial pull down stage 6 2 Heating operation Indoor air temp DB Outdoor unit air t...

Страница 18: ...Service manual 14 However excludes the initial pull down stage...

Страница 19: ...Service manual 15 7 Schematic diagram and Wiring diagram 7 1 Schematic diagram...

Страница 20: ...de MSG 05CR MSG 07CR MSG 09CR MSG 12CR 1 2 N C O M PR ESSO R C APAC I TO R R ED O U TD O O R U N I T O VER LO AD R ELAY Y G C O M PR ESSO R S C BLU E R BLAC K R ED BLAC K I N D O O R U N I T FAN C APA...

Страница 21: ...G 16CR 1 2 N C O M PR ESSO R C APAC I TO R R ED O U TD O O R U N I T O VER LO AD R ELAY Y G C O M PR ESSO R S C BLU E R BLAC K R ED BLAC K I N D O O R U N I T FAN C APAC I TO R R ED Y G FAN M O TO R Y...

Страница 22: ...E TR AN SFO R M ER DI SPLAY BO AR D S W I TC H B O A R D C N 12 C N 9 C O M PR ESSO R R ELAY C U R R E N T D E TEC TO R W H I TE C N 1 C N 4 B R O W N B LU E C N 14 C N 2 1 2 N C O M PR ESSO R C APAC...

Страница 23: ...Service manual 19 7 2 2 MSG 07HR MSG 09HR MSG 12HR...

Страница 24: ...Service manual 20 MSG 16HR MSG 18HR MSG 21HR...

Страница 25: ...5 2 5 Grade 8 3 Pipe length and the elevation Standard length Max Max Additional m Elevation Elevation refrigerant Btu h GAS LIQUID B m A m g m 3 8 9 52 1 4 6 35 5 5 10 30 1 2 12 7 1 4 6 35 5 5 10 30...

Страница 26: ...eck the flare connection for gas leakage 4 Purge the air from the system Set the 2 way valve to the open position and remove the cap from the 3 way valve s service port Using the hexagonal wrench to p...

Страница 27: ...charge hose with the push pin to the gas service port 4 Air purging of the charge hose Open the low pressure valve on the charge set slightly to purge air from the charge hose 5 Set the 2 way valve to...

Страница 28: ...1 minutes repeat 3 times After purging the air use a torque wrench to tighten the flare nut to on the 2 way valve 4 Check the gas leakage Check the flare connections for gas leakage 5 Discharge the r...

Страница 29: ...he service port 3 Open the valves Low side on the charge set and discharge the refrigerant until the gauge indicates 0 05 to 0 1 Mpa If there is no air in the refrigeration cycle the pressure when the...

Страница 30: ...has moved toward 0 1 Mpa 76 cmHg vacuum of 4 mmHg or less 3 Close the valve Low side on the charge set turn off the vacuum pump and confirm that the gauge needle does not move approximately 5 minutes...

Страница 31: ...e specified amount of refrigerant if can be charged with a little at a time approximately 150g each time0 while operating the air conditioner in the cooling cycle however one time is not sufficient wa...

Страница 32: ...Total capacity kW 2 13 2 04 1 90 1 80 1 68 1 55 17 C W Sensitive capacity kW 1 57 1 52 1 45 1 38 1 29 1 20 Input kW 0 67 0 71 0 74 0 80 0 88 0 91 27 C D Total capacity kW 2 27 2 17 2 05 1 94 1 81 1 66...

Страница 33: ...ive capacity kW 2 47 2 40 2 34 2 19 2 02 1 93 Input kW 0 95 1 00 1 04 1 12 1 25 1 29 OUTDOOR TEMPERATURE DRY 9 5 MSG 09HR SUMMER Cooling mode Indoor Conditions 25 C 30 C 35 C 40 C 45 C 50 C 21 C D Tot...

Страница 34: ...69 2 52 2 33 15 C W Sensitive capacity kW 2 46 2 36 2 21 2 05 1 92 1 80 Input kW 1 05 1 11 1 16 1 25 1 39 1 43 24 C D Total capacity kW 3 64 3 48 3 25 3 07 2 86 2 64 17 C W Sensitive capacity kW 2 68...

Страница 35: ...61 3 38 3 14 15 C W Sensitive capacity kW 3 30 3 17 2 97 2 75 2 58 2 41 Input kW 1 37 1 44 1 50 1 62 1 80 1 86 24 C D Total capacity kW 4 89 4 67 4 37 4 13 3 85 3 55 17 C W Sensitive capacity kW 3 59...

Страница 36: ...4 06 3 80 3 52 15 C W Sensitive capacity kW 3 71 3 56 3 33 3 09 2 90 2 71 Input kW 1 56 1 64 1 71 1 85 2 05 2 12 24 C D Total capacity kW 5 49 5 25 4 91 4 64 4 32 3 98 17 C W Sensitive capacity kW 4 0...

Страница 37: ...4 74 4 43 4 11 15 C W Sensitive capacity kW 4 32 4 15 3 89 3 60 3 38 3 16 Input kW 1 97 2 08 2 16 2 33 2 59 2 68 24 C D Total capacity kW 6 41 6 12 5 72 5 41 5 04 4 65 17 C W Sensitive capacity kW 4 7...

Страница 38: ...IRESTORE Amp self protection return value THDEFROST High wind defrosting temperature difference TMDEFROST Middle wind defrosting temperature difference TLDEFROST Low wind defrosting temperature differ...

Страница 39: ...ss Zero signal error warning If there is no Cross Zero signals in 4 minutes the unit stops and LED displays failure information and can t returns to normal operation automatically 10 4 5 The current p...

Страница 40: ...cooling mode Anti freezing control to indoor evaporator at cooling mode T evaporator temp 10 7 Dehumidifying mode 10 7 1 The 4 way valve is off in dehumidifying mode 10 7 2 Compressor and Indoor Fan...

Страница 41: ...1 Generally the 4 way valve is open in heating mode but it is closed in defrosting mode 4 way valve must delay 2 minutes compared with compressor if the compressor changed into non heating mode or tu...

Страница 42: ...The louver opens to Standard Angle ANGLHEAT when power is on for the first time 10 9 Defrosting mode available for heating mode Defrosting condition Defrosting starts when either of the following A a...

Страница 43: ...frost the fourth defrost time should be 10 minutes The circulation is as following Ending condition of defrosting If one of following conditions is satisfied end the defrost and turn into heating mode...

Страница 44: ...ose fan mode is set as low the A C operates at the DRY mode with a set temp of 24 10 11 3 All protections of remote control cooling are available at forced cooling operation 10 11 4 Forced Auto functi...

Страница 45: ...an only mode the condition will be the same after the air conditioner running under economic mode after 2 hours and during the next time the set temp do not change The total time is 7 hours after 7 ho...

Страница 46: ...200 200 200 200 200 ANGLHEAT 0 0 0 ANGLOFF 124 124 124 124 124 124 124 THDEFROST 16 C 14 C 14 C TMDEFROST 17 C 15 C 15 C TLDEFROST 18 C 16 C 16 C Model MSG 16CR MSG 16HR MSG 18CR MSG 18HR MSG 21CR MS...

Страница 47: ...icator illuminates then TIMER is set ON PRE DEF indicator For cooling heating mode only The air conditioner starts defrosting automatically if outdoor unit frosts in heating operating At this time PRE...

Страница 48: ...or occurs 4 times X EEROM error On No over zero signal r Extinguish Flash at 5Hz For heat pump mode Failure phenomenon Operation lamp Timer lamp Defrosting lamp Over current protection of the compress...

Страница 49: ...Service manual 45 12 3 Diagnostic chart After energizing no indicator is lighted and the air conditioner can t be operated...

Страница 50: ...s less than 4 5V Check according to the following procedure Resetting phenomenon often occurs during operation After changing indoor PCB check if the failure realease Yes After changing indoor fan mot...

Страница 51: ...12 8 Operation lamp on and Timer lamp flashes EEROM error indoor PCB is defective 12 9 Operation lamp flashes Timer lamp flashes This is alarm signal when the main chip can t detect over zero signal...

Страница 52: ...25 10 52 3 1918 1 37 1988 26 9 5507 53 3 0707 0 35 2024 27 9 1245 54 2 959 1 33 3269 28 8 7198 55 2 8442 2 31 5635 29 8 3357 56 2 7382 3 29 9058 30 7 9708 57 2 6368 4 28 3459 31 7 6241 58 2 5397 5 26...

Отзывы: