Service manual
28
11. Electronic
function
11.1 Proper symbols and their meaning
TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
I
3sec
: Self-protection amp of compressor, continue three seconds until turns off the compressor.
I
5MIN
: Self-protection amp of compressor, continue five minutes until turns off the compressor.
I
FAN
: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
I
RESTORE
: Amp self-protection return value
TH
DEFROST
: High wind, defrosting temperature difference
TM
DEFROST
: Middle wind, defrosting temperature difference
TL
DEFROST
: Low wind, defrosting temperature difference
TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
11.2 Function
Remote receiving
Testing and forced running
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at cooling mode
11.3 Protection
11.3.1 3 minutes delay at restart for compressor.
11.3.2 Sensor protection at open circuit and breaking disconnection
11.3.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than 2100RPM)or too low(lower
than 300RPM)for 50 seconds, the unit stops and LED displays failure information and can’t returns to normal
operation automatically.
11.3.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED
displays failure information and can’t returns to normal operation automatically.
Содержание MSF3-07CRN2
Страница 1: ...Cover MSF3 07CRN2 MSF3 07HRN2 MSF3 09CRN2 MSF3 09HRN2 AAC 09ESCH MSF3 12CRN2 MSF3 12HRN2 AAC 12ESCH...
Страница 11: ...Service manual 8 5 Refrigerant cycle diagram Cooling only Heat pump mode...
Страница 14: ...Service manual 11 7 2 Wiring diagram MSF3 07CRN2 MSF3 09CRN2 MSF3 12CRN2...
Страница 15: ...Service manual 12 MSF3 07HRN2 MSF3 09HRN2 MSF3 12HRN2...