valve must delay 2 minutes compared with compressor if the compressor changed into non-heating
mode or turned off. 4-way valve doesn't delay in dehumidifying mode
11.7.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode,
except for the defrosting mode or the end of defrost
11.7.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for
4
minutes after starting and then judge temperature. Meanwhile other protections are still valid.
Tc-1
T1-Ts
Room temp. up
Room temp. down
Tc
Compressor and
outdoor fan off
Compressor and
outdoor fan on
Ts
Tc is the temperature of heating mode. The temperature will increase 4
℃
, 3
℃,
2
℃,
1
℃,
the unit choose
one with the jump JT1,JT2.
JT1 JT2
OFF
ON
OFF
1
℃
3
℃
ON
2
℃
4
℃
11.7.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function
prevails.
Anti-cold wind control function at heating mode (T=indoor exchanger temp.)