Rooftop ClimaCreator series
DM16‐01.01.27en
Service manual
111
necessary?
Does the condenser fan and indoor blower fan free without rubbing, and are they tight on the
shafts?
Are all covers and access panels in place to prevent air loss and safety hazards?
Starting the unit:
When the unit operates under cooling mode, please check the line voltage of the unit. The
voltage should be within the range shown on the unit nameplate.
If low voltage is encountered, check the size and the length of power supply wire from the mian
disconnect to the unit. The line may be undersized for the length of the run.
Shut-down the unit:
Place the system selector in the OFF position or reset thermostat (Wired controller) at a setting
above room temperature.
Do not de-energize the main power supply disconnect except when unit is to be serviced.
9. Safety control
Functions
Minutes delay for the compressor start-up:
At the beginning of energizing, 3-minutes delay should be taken to start the compressor. While
after the stop of the compressor, 7-minutes delay should be taken to restart the compressor.
Compressor discharge temperature protection:
When the temperature of compressor discharge is higher than 125°C (257°F), the compressor
will stop. Once the temperature is lower than 90°C (194°F), the compressor can be started
again.
Reverse phase protection relay:
The reverse phase protection relay will make the unit not start, when the power supply source is
in correctly conneted.
The checking of phase order is just carried out at the first time of electrifying. If malfunction
happens then the checking will be going on until the order of phase is right, and the error code
will be displayed on the board. If there is no problem in the first checking, then it will be omitted.
Содержание MRCT-062CWN1-R(C)
Страница 28: ...DM16 01 01 27en Rooftop ClimaCreator series 28 Service manual...
Страница 29: ...Rooftop ClimaCreator series DM16 01 01 27en Service manual 29 MRCT 085CWN1 R C MRCT 100CWN1 R C Unit mm...
Страница 30: ...DM16 01 01 27en Rooftop ClimaCreator series 30 Service manual...
Страница 31: ...Rooftop ClimaCreator series DM16 01 01 27en Service manual 31 MRCT 125CWN1 R C MRCT 150CWN1 R C Unit mm...
Страница 32: ...DM16 01 01 27en Rooftop ClimaCreator series 32 Service manual...
Страница 33: ...Rooftop ClimaCreator series DM16 01 01 27en Service manual 33 MRCT 175CWN1 R C MRCT 200CWN1 R C Unit mm...
Страница 34: ...DM16 01 01 27en Rooftop ClimaCreator series 34 Service manual...
Страница 35: ...Rooftop ClimaCreator series DM16 01 01 27en Service manual 35...
Страница 36: ...DM16 01 01 27en Rooftop ClimaCreator series 36 Service manual MRCT 250CWN1 R C MRCT 300CWN1 R C Unit mm...
Страница 37: ...Rooftop ClimaCreator series DM16 01 01 27en Service manual 37...
Страница 39: ...Rooftop ClimaCreator series DM16 01 01 27en Service manual 39 MRCT 085CWN1 R C...
Страница 40: ...DM16 01 01 27en Rooftop ClimaCreator series 40 Service manual MRCT 100CWN1 R C...
Страница 41: ...Rooftop ClimaCreator series DM16 01 01 27en Service manual 41 MRCT 125CWN1 R C...
Страница 42: ...DM16 01 01 27en Rooftop ClimaCreator series 42 Service manual MRCT 150CWN1 R C...
Страница 43: ...Rooftop ClimaCreator series DM16 01 01 27en Service manual 43 MRCT 175CWN1 R C...
Страница 44: ...DM16 01 01 27en Rooftop ClimaCreator series 44 Service manual MRCT 200CWN1 R C...
Страница 45: ...Rooftop ClimaCreator series DM16 01 01 27en Service manual 45 MRCT 250CWN1 R C MRCT 300CWN1 R C...
Страница 117: ...Rooftop ClimaCreator series DM16 01 01 27en Service manual 117 Low pressure protection Eeprom error...