background image

15 

* The above airflow data for reference only. 

 The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this 

reason, the contractor should use only industry-recognized procedures. 

 Heat pump systems require a specified airflow. Each ton of cooling requires between 350 and 450 cubic feets of air per minute 

(CFM), or 400 CFM nominally. 

 Duct design and construction should be carefully done. System performance can be lowered dramatically through bad 

planning or workmanship. 

 Air supply diffusers must be selected and located carefully. They must be sized and positoined to deliver treated air along the 

perimerter of the space. If they are too small for their intended airflow, they become noisy. If they are not located properly, they 
cause drafts. Reture air grilles must be properly sized to carry air back to the blower. If they are too small, they also cause 
noise. 

 The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures a 

comfortable living space. 

 An air velocity meter or airflow hood can give a reading of system CFM. 

 When installation, installer should select the air speed according to the actual setting static pressure. Please refer to the 

Table

 

7-1 

AIRFLOW PERFORMANCE DATA.   

* In any stituation , the airflow of the unit should be in the range of 80% to 130% of 400CFM/Ton. 

Table 7-2 Duct Application(230v) 

0[0] 0.1[.02] 

0.2[.05] 

0.3[.07] 

0.4[.10] 0.5[.12] 0.6[.15]  0.7[.17] 

CFM(L/S) 
RPM 
Watts 
Amps 
CFM(L/S) 
RPM 
Watts 
Amps 
CFM(L/S) 
RPM 
Watts 
Amps 

CFM(L/S) 
RPM 
Watts 
Amps 
CFM(L/S) 
RPM 
Watts 
Amps 
CFM(L/S) 
RPM 
Watts 
Amps 
CFM(L/S) 
RPM 
Watts 
Amps 
CFM(L/S) 
RPM 
Watts 
Amps 
CFM(L/S) 
RPM 
Watts 
Amps 

Motor 

Speed 

Model 

Number 

48 

Low 

Middle 

High 

24 

Low 

Middle 

High 

External Static Pressure-Inches W.C.[kPa] 

 CFM(L/S)(Watts) 

60 

Low 

Middle 

High 

 

CFM(L/S) 
RPM 
Watts 
Amps 
CFM(L/S) 
RPM 
Watts 
Amps 
CFM(L/S) 
RPM 
Watts 
Amps 

36 

Low 

Middle 

High 

974(459)  

1312(619) 1280(604) 1243(586)  1197(565)  1143(539) 

770 817 863  902  943 
455 442 423  402  380 

1.98 1.92 1.85  1.76  1.67 

1376(649) 1323(624) 1257(593) 1176(554) 

1082(510) 

919 951 983 1011 

1039 

494 470 444  

418 

388 

2.17 2.07  1.97 

 

1.87 

1.75 

1451(684) 1372(647) 1279(603) 

1178(556) 1041(491) 

1005 1028 1050 

1069 1089 

563 533 502 

469 434 

2.5 2.38 

2.26 

2.14 

2.0 

509 591 671  737 
195 191 187  183 

0.85 0.83 0.81  0.79 

812 866 911 

949 

271 261 251 

240 

1.18 1.14 1.1 1.06 

960 

993 1023 

328 

314 299 

1.47 

1.41 1.36 

847(399) 

800 (378)  

754 (356)  

701(331)  

932(440)  

878(414)  

806(380)  

725(342)  

889(419)  

794(375)  

1676(790) 1623(766) 1568(740) 1510(712) 1443(681) 

751 793 833 870  903 
536 522 508 493  468 

2.42 2.37 

2.32 2.27 2.21 

1721(812) 1669(787)  1593(751) 1516(715) 

1429(674) 

891 922  948 973 

997 

608 591  670 550 

529 

2.82 2.76  2.69 2.62 

2.55 

1822(859) 1742(822) 

1661(784) 

1566(739) 1455(686) 

966 988 1007 

1025 

1046 

725 701 675 

650 623 

3.44 3.36 3.27 

3.20 3.12 

2037(961) 1984(936) 

1936(913) 1859(877) 1780(840) 

932 957 980 1001 1020 
721 700 676 651  625 

3.15 3.06 2.96 2.87  2.77 

1998(943) 1931(911)  1855(875) 1757(829) 

1654(780) 

1010 1027  1043 1056 1071 
729 706  677 651 

623 

3.24 3.14  3.04 2.94 

2.83 

2006(946) 1916(904) 1817(857) 

1710(807) 1582(746) 

1053 1065 1076 

1086 1097 

778 753 724 

694 661 

3.5 3.4 3.3 

3.19 

3.07 

Содержание MRC-24CWN1-M13L

Страница 1: ...e attempting installation or operation Failure to follow these instructions may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property d...

Страница 2: ...TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES...

Страница 3: ...e use of unauthorized components accessories or devices may adversely affect the operation of the heat pump and may also endanger life and property The manufacturer disclaimer any responsibility for s...

Страница 4: ...ransportation damage 1 1 INSPECTION Refer to Fig 2 2 2 3 for unit physical data and to Table 6 1 6 2 for electrical data If components are to be added to a unit they must meet local codes they are to...

Страница 5: ...AUTION Before lifting make sure the unit weight is distributed equally on the rigging cables so it will lift evenly Units may be moved or lifted with a forklift Slotted openings in the base rails are...

Страница 6: ...Unit Dimensions Low vlotage entrance 7 8 Dia High voltage conn 1 23 64 Dia Unit size 024 036 The above figure for reference purpose only Hi Lo pressure detected valve 1 4 SAE Side supply air opening S...

Страница 7: ...stalled outdoors Over hanging structure or shrubs should not obscure condenser air discharge outlet 2 The minimum clearance without economizer fresh air damper For distance with Economizer fresh air d...

Страница 8: ...ventilation air intake Flexible joints may be used in the supply and return duct work to minimize the transmission of noise When fastening duct work to the side duct flanges on the unit insert the sc...

Страница 9: ...devices may be either fuses or HACR type circuit breakers Two 1 3 8 knockouts on the back panel are provided for connection of power wiring to electric heater Power wiring is connected to the power te...

Страница 10: ...mpartment 6 3 CONTROL WIRING IMPORTANT Class 2 low voltage control wiring SHOULD NOT be run in conduit with main power wiring and must be separated from power wiring unless class 1 wire of proper volt...

Страница 11: ...connect Field supplied disconnect Single phase power supply Fig 6 2 Typical Field Power Wiring Diagram R G Y W C R G Y W1 W2 C 24 volt transformer THERMOSTAT UNIT CONTROL BOARD THERMINAL STRIP B wire...

Страница 12: ...ic Heat Option Max Fuse2 Breaker3 Size Amps Compressors each 18 7A 0 95A 2 84A 060L 5 0 208 230 1 60 21 5A Volt Size Tons MCA1 Amps 036L 3 0 208 230 1 60 14 0A 70A 024T 2 0 208 230 1 60 9 7A 34 8A 15...

Страница 13: ...17 17 17 17 Tube diameter inch 9 32 9 32 9 32 9 32 9 32 9 32 Circuitry type interlaced interlaced interlaced interlaced interlaced interlaced Refrigerant control Orifice Orifice Orifice Orifice Orifi...

Страница 14: ...76 360 343 326 1 88 1 81 1 73 1 66 1 58 1251 590 1206 569 1148 541 1080 509 989 466 869 910 949 983 1017 436 416 392 368 340 2 11 2 01 1 91 1 8 1 68 1345 634 1272 600 1192 562 1107 522 980 462 965 995...

Страница 15: ...17 CFM L S RPM Watts Amps CFM L S RPM Watts Amps CFM L S RPM Watts Amps CFM L S RPM Watts Amps CFM L S RPM Watts Amps CFM L S RPM Watts Amps CFM L S RPM Watts Amps CFM L S RPM Watts Amps CFM L S RPM...

Страница 16: ...53 370 388 414 441 467 493 228 249 270 291 312 333 351 368 386 412 439 465 491 226 247 268 289 310 331 349 366 384 410 437 463 489 224 245 266 287 308 329 347 364 382 408 435 461 487 222 243 264 285 3...

Страница 17: ...60 386 411 442 473 504 535 236 256 275 294 314 333 358 384 409 440 471 502 533 234 254 273 292 312 331 356 382 407 438 469 500 531 232 252 271 290 310 329 354 380 405 436 467 498 529 230 250 269 288 3...

Страница 18: ...358 376 394 423 451 480 508 225 247 270 293 315 338 358 378 398 425 452 479 506 223 245 268 291 313 336 356 376 396 423 450 477 504 221 243 266 289 311 334 354 374 394 421 448 475 502 219 241 264 287...

Страница 19: ...21 342 363 384 405 438 470 503 535 233 254 276 298 319 341 360 379 398 432 466 499 533 231 252 274 296 317 339 358 377 396 430 464 497 531 229 251 272 294 315 337 356 375 394 428 462 495 529 227 249 2...

Страница 20: ...onditions If the outdoor ambient temp is 37 4 F and the compressor stopped for more than three hours or the unit powered on once more the crank heater will be on Crankcase heater shut down conditions...

Страница 21: ...and T3 is 32 F and last for 40 minutes 2 Compressor keeps running when T4 is 28 4 F and T3 is 32 F and last for 50 minutes When defrosting actions if the electrical heater kit is installed the unit wo...

Страница 22: ...and outdoor fan instant OFF Blower fan delay 90 sec OFF 4 way valve instant ON Blower instant ON Compressor and outdoor fan instant ON Compressor and outdoor fan instant OFF Blower fan delay 90 sec O...

Страница 23: ...run 4 Turn fan switch to AUTO system switch to COOL and thermostat tem perature setting below room temperature Unit should run in COOLING mode Heating Startup After normal cooling run 1 Turn thermosta...

Страница 24: ...24 AC System W iring Diagram GMCC LG compressor 1 2 3 4 6 5 1 2 0...

Страница 25: ...25 HP System W iring Diagram GMCC LG compressor 1 2 3 4 6 5 1 2 0 3...

Отзывы: