21
medium, low and auto.
2)
Auto fan in cooling mode acts as follow:
8.5.7 Condenser high temperature protection function(in cooling and drying mode)
If T
3>
60
℃
for 5 seconds, compressor will stop immediately, and the machine will not resume until T
3<
52
℃
.
8.6 Drying mode
8.6.1 Indoor fan speed is fixed at breeze grade and can’t be changed. The horizontal angle is the same as in cooling
mode.
8.6.2 Room overlow temperature protection
In drying mode, if room temperature is lower than 10
℃
, compressor will stop and not resume until room
temperature climbs up to 12
℃
.
8.6.3 Evaporator anti-freezing protection, condenser high temperature protection and outdoor unit frequency limit are
valid, and they are the same as that in cooling mode.
8.6.4 Horizontal louver action is the same as that in cooling mode.
∆
T=(oom tem
p)
– (setting
Te
mp)
medium
4.0
3.0
1.5
1.0
high
low