18
5.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas
Liquid
MSAEAU-09HRFN1-QRD0GW +
MOBA31-09HFN1-QRDOGW
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
10
25
15
MSAEAU-09HRFNX-
MOBA31-09HFN1-QRDOGW
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
10
25
15
MSAEBU-12HRFN1-
MOB31-12HFN1-QRD0GW
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
10
25
15
MSAEBU-12HRFNX-
MOB31-12HFN1-QRD0GW
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
10
25
15
MSAEBU-12HRFN1-QRD0GW(B)+
MOB32-12HFN1-QRD0GW
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
5
10
25
15
MSAECU-18HRFN1-
MOB31-18HFN1-QRD0GW
1/2’’
(Ф12.7)
1/4’’
(Ф6.35)
5
20
30
15
MSAECU-18HRFN1-
MOB32-18HFN1-QRD0GW(S1)
1/2’’
(Ф12.7)
1/4’’
(Ф6.35)
5
20
30
15
MSAECU-18HRFNX-
MOB32-18HFN1-QRD0GW(S1)
1/2’’
(Ф12.7)
1/4’’
(Ф6.35)
5
20
30
15
MSAEDU-24HRFN1-
MOCA30-24HFN1-QRD0GW
5/8’’
(Ф15.9)
3/8’’
(Ф9.52)
5
25
50
30
MSAEDU-24HRFNX-
MOCA30-24HFN1-QRD0GW
5/8’’
(Ф15.9)
3/8’’
(Ф9.52)
5
25
50
30
MSAEDU-24HRFN1-QRD0GW(B)+
MOCA30-24HFN1-QRC8GW
5/8’’
(Ф15.9)
3/8’’
(Ф9.52)
5
25
50
30
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
Содержание MOB31-12HFN1-QRD0GW
Страница 1: ...All Easy 3D Inverter Series Service Manual 2017 ...
Страница 8: ...8 For MSAEAU 09HRFN1 QRD0GW MSAEAU 09HRFNX QRD0GW ...
Страница 10: ...10 For MSAEDU 24HRFN1 QRD0GW MSAEDU 24HRFN1 QRD0GW B MSAEDU 24HRFNX QRD0GW ...
Страница 11: ...11 3 2 Outdoor Unit ...
Страница 14: ...14 For MOCA30 24HFN1 QRD0GW MOCA30 24HFN1 QRC8GW ...
Страница 30: ...30 7 2 Outdoor Unit MOBA31 09HFN1 QRD0GW MOB31 12HFN1 QRD0GW MOB32 12HFN1 QRD0GW MOB32 18HFN1 QRD0GW S1 ...
Страница 31: ...31 MOB31 18HFN1 QRD0GW MOCA30 24HFN1 QRD0GW MOCA30 24HFN1 QRC8GW ...