Midea R410A Full DC Inverter Split Type Series Technical Manual MCAC-UTSM-201406
53
9.4 Duct type indoor unit malfunction and protection codes
Names of indicators in receiving kit (When selecting remote controller)
Display content
Fault or protection meaning
Timer lamp flashing
or show [
E1
]
Communication error between indoor and outdoor unit.
Operation lamp flashing
or show [
E2
]
T1, room temperature sensor error.
Operation lamp flashing
or show [
E3]
T2, pipe temperature sensor error.
Operation lamp flashing
or show [
E4
]
T2B, temperature sensor error.
Timer lamp flashing slowly
or show [
E6
]
Fan protection
Defrost lamp flashing slowly
or show[
E7
]
Eeprom error.
Alarm flashing slowly or
show [
Ed
]
Outdoor unit error.
Notes: the LED error code display is also available for weekly wired controller.