R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-12
82 Installation
Low static pressure 5.6
15.9(Flaring nut)
9.53(Flaring nut)
Thin duct type 7.1
12.7(Flaring nut)
6.4(Flaring nut)
A5 duct type 2.2~4.5
12.7(Flaring nut)
6.4(Flaring nut)
A5 duct type 5.6~8.0
15.9(Flaring nut)
9.53(Flaring nut)
A5 duct type 9.0~14.0
15.9(Flaring nut)
9.53(Flaring nut)
Console Type 2.2~4.5
12.7(Flaring nut)
6.4(Flaring nut)
Two-way Cassette Type 2.2~4.5
12.7(Flaring nut)
6.4(Flaring nut)
Two-way Cassette Type 5.6~7.1
15.9(Flaring nut)
9.53(Flaring nut)
Ceiling And Floor Type 3.6~4.5
12.7(Flaring nut)
6.4(Flaring nut)
Ceiling And Floor Type 5.6~16.0
15.9(Flaring nut)
9.53(Flaring nut)
Expose And Concealed Floor-standing type
2.2~4.5
12.7(Flaring nut)
6.4(Flaring nut)
Expose And Concealed Floor-standing type
5.6~8.0
15.9(Flaring nut)
9.53(Flaring nut)
Note: The maximum length of the branch pipe should not be longer than 15m.
Table 2: Indoor unit main pipes selection (L1~L5)
Total capacity of
downstream indoor units
(kW)
Main pipe size(mm)
Branch Pipe
Gas pipe
Liquid pipe
A
<
16.6
Φ15.9
Φ9.53
FQZHN-01D
16.6≤A
<
23
Φ19.1
Φ9.53
FQZHN-01D
Table 3: Main pipes selection (L1)
Total capacity of
outdoor units
(kW)
When the equivalent length of all liquid and air
pipes < 90m
When the equivalent length of all liquid and air
pipes ≥ 90m
gas side
(mm)
liquid side
(mm)
The first line
branch pipe
gas side
(mm)
liquid side
(mm)
The first line
branch pipe
A
<
16
Φ15.9
Φ9.53
FQZHN-01D
Φ19.1
Φ9.53
FQZHN-01D
16≤A
<
23
Φ19.1
Φ9.53
FQZHN-01D
Φ22.2
Φ9.53
FQZHN-02D
Note: Main pipe L1 can be selected form table 2 and table 3, the larger size should be finally selected.
The straight distance between copper pipe turning and the contiguous branch pipe is at least 0.5m.
The straight distance between the contiguous branch pipes is at least 0.5m.
The straight distance which the branch pipes connected to the indoor unit is at least 0.5m.
Table 4: Outdoor unit pipe connection
Piping side
MODEL
Outdoor unit pipe connection (mm)
Gas Side
Liquid Side
80 model
Φ15.9
Φ9.53
105 model
Φ15.9
Φ9.53
120 model
Φ15.9
Φ9.53
140 model
Φ15.9
Φ9.53
160 model
Φ19.1
Φ9.53
180 model
Φ19.1
Φ9.53
Outdoor Unit
Maximum Quantity of
Indoor unit
Total Capacity of Indoor unit
80 model
4
45%~130%
105 model
5
45%~130%
120 model
6
45%~130%
140 model
6
45%~130%
160 model
7
45%~130%
180 model
9
45%~130%
If ODU connect only one IDU, the capacity of IDU should be not more than ODU.
If ODU connect more than one IDU, the capacity of each IDU should be not more than 8kW for refrigerant uniform distribution.
When capacity of indoor unit greater than the sum of 100%, capacity of indoor unit will be attenuated.
When capacity of indoor unit greater than or equal to the sum of 120%, in order to ensure the effectiveness of machine, and then try
to open the indoor units at different time.
Содержание MDV-V105W/DN1
Страница 18: ...R410a Full DC Inverter Mini VRF MCAC VTSM 2013 12 18 Specifications Performance 5 Wiring Diagrams 8 105 model ...
Страница 19: ...MCAC VTSM 2013 12 R410a Full DC Inverter Mini VRF Specifications Performance 19 120 160 model ...
Страница 20: ...R410a Full DC Inverter Mini VRF MCAC VTSM 2013 12 20 Specifications Performance 180 model ...
Страница 21: ...MCAC VTSM 2013 12 R410a Full DC Inverter Mini VRF Specifications Performance 21 6 Field Wiring ...