PROBLEM

POSSIBLE CAUSE

REMEDY

No power display on

panel or any one of the

buttons failure.

Power failure

Check the power supplier if the power supplier is supplied to the

unit. Check the power cord and correct if damaged.

Transformer (Discharge

transformer before

testing)

Check resistance between the two input/output lines on transformer.

Replace the transformer if either of the input/output is open or the

transformer is damaged.

Display board or main

PCB failure

Check the voltage on display board. Replace the display board if it

is +5V else replace the main PCB.

Fan motor runs

intermittently

Cycles on overload.

Check voltage. Call an electrician if not within limits.

Test capacitor.          Replace if not /-10% of manufacture's

rating.

Check bearings. Replace the motor if the blower wheel cannot

rotate freely.

Pay attention to any change from high speed to low speed. Replace

the motor if the speed does not change.

Compressor stops

instantly after startup.

Refrigerant

The amount of the refrigerant is too much, making the compressor

load too big. Recycle and recharge the refrigerant after checking for

the reason.

Compressor

The compressor is blocked inside. Replace after checking for the

reason.

Fan motor will not run.

No power

Check voltage at electrical outlet. Correct if none.

Water alarm

Check and correct if water alarm happens.

Power supply cord

Check voltage at the power cord terminal on Main PCB. Replace

the power cord if none.

Transformer (Discharge

transformer before

testing)

Check resistance between the two input/output lines on transformer.

Replace the transformer if either of the input/output is open or the

transformer is damaged.

Wire disconnected or

connection loose

Connect wire. Refer to wiring diagram for terminal identification.

Repair or replace loose terminal.

Main PCB failure

Select fan speed and Check the voltage on main PCB. Replace the

main PCB if no voltage in anyone.

Capacitor (Discharge

capacitor before testing)

Test capacitor. Replace if not /-10% of manufacture's rating.

Replace if shorted, open or damaged.

Fan motor noise.

Fan blower

Replace the fan blower if cracked, out of balance, or partially

missing.

Loose screws

Tighten them.

Worn bearings

Replace the motor if knocking sounds continue when running or

loose, or the motor hums or noise appears to be internal while

running.

Содержание MDT1-08DEN3-QA3

Страница 1: ...08DEN3 QA3 EU CF0 4BD N3 T1 A3 MDT1 10DMN3 QA3 EU CFK0 4BD N3 T1 A3 MDT1 10DKN3 QA3 EU CFZ0 4BD N3 T1 A3 MDT1 10DEN3 QA3 EU CFK0 6BD N3 T1 A3 MDT1 16DKN3 QA3 EU CFZ0 6BD N3 T1 A3 MDT1 16DEN3 QA3 EU CF...

Страница 2: ...ns 9 7 2 Electric part assembly condition that use 9 7 3 PCB working environment 9 7 4 Protection function 10 7 5 Set humidity operation 11 7 6 Continually dehumidify operation 11 8 Basic test procedu...

Страница 3: ...ll the panel and the cover of control box securely There is risk of fire of electric shock Always install a dedicated circuit and breaker Improper wiring or installation may cause fore or electric sho...

Страница 4: ...ck Do not allow water to run into electric parts It may cause fire failure of the product or electric shock Do not store or use flammable gas or combustible near the product There is risk of fire or f...

Страница 5: ...erant leakage after installation or repair of product Low refrigerant levels may cause failure of product Install the drain hose to ensure that water is drained away properly A bad connection may caus...

Страница 6: ...itioner and could cause product malfunction or damage Do not insert hands or other object through air inlet or outlet while the product is operated There are sharp and moving parts that could cause pe...

Страница 7: ...CF0 4BD N3 T1 A3 MDT1 10DMN3 QA3 EU CF0 8BD N3 T1 A3 MDT1 20DMN3 QA3 EU CFZ0 3BD N3 T1 A3 MDT1 08DEN3 QA3 EU CFZ0 4BD N3 T1 A3 MDT1 10DEN3 QA3 EU CFZ0 6BD N3 T1 A3 MDT1 16DEN3 QA3 EU CFZ0 8BD N3 T1 A...

Страница 8: ...Display Continue pad Humidity set control pads 3 Dimension T1 Series T2 Series Dimension Mode W mm H mm D mm T1 8L 10L 350 452 275 T1 16L 20L 397 502 297 T2 10L 350 395 350 4 Refrigerant Cycle Diagra...

Страница 9: ...EU CF0 4BD N3 T1 A3 MDT1 10DMN3 QA3 EU CF0 6BD N3 T1 A3 MDT1 16DMN3 QA3 EU CF0 8BD N3 T1 A3 MDT1 20DMN3 QA3 2 EU CFK0 3BD N3 T1 A3 MDT1 08DKN3 QA3 EU CFK0 4BD N3 T1 A3 MDT1 10DKN3 QA3 EU CFK0 6BD N3 T...

Страница 10: ...8 3 EU CFZ0 3BD N3 T1 A3 MDT1 08DEN3 QA3 EU CFZ0 4BD N3 T1 A3 MDT1 10DEN3 QA3 EU CFZ0 6BD N3 T1 A3 MDT1 16DEN3 QA3 EU CFZ0 8BD N3 T1 A3 MDT1 20DEN3 QA3 EU CFZ0 4BD N3 T2 A3 MDT2 10DEN3...

Страница 11: ...TE Temperature of evaporator TH Humidity of ambient TS The set humidity S1 Switch 1 7 2 Electric part assembly condition that use 1 Scope of application of voltage of the power 220 240VAC 50Hz 1phase...

Страница 12: ...on the top of water tank S1 a At running status if the water level of water exceeds the safety water level and the S1 closed the unit will protect by itself It will shut down all of load and back to w...

Страница 13: ...lly unless there is a water full protection or sensor fault protection The Setting humidity operation is unapplied 8 Basic test procedure 8 1 Defective compressor Compressors are single phase 220 240v...

Страница 14: ...must and the other probe in turn to each compressor terminal If a reading is obtained the compressor is grounded and must be replaced 8 1 3 Checking the compressor efficiency The reason for compresso...

Страница 15: ...overload 2 Allow time for overload to reset before attempting to test 3 Apply ohmmeter probes to terminals on overload wires There should be continuity through the overload 8 1 6 Terminal overload int...

Страница 16: ...to high side of the system 4 Accurately weighing the refrigerant charge actually introduced into the system 5 Facilities for flowing nitrogen through refrigeration tubing during all brazing processes...

Страница 17: ...f 10 11 Break vacuum by charging system from the high side with the correct amount of refrigerant specified This will prevent boiling the oil out of the crankcase NOTE If the entire charge will not en...

Страница 18: ...ithout the use of a capillary tube will cause damage to the discharge valve of the rotary compressor NOTE All inoperative compressors returned to Friedrich must have all lines properly plugged with th...

Страница 19: ...t 1 Remove capacitor from unit 2 Check for visual damage such as bulges cracks or leaks 3 For dual rated apply an ohmmeter lead to common C terminal and the other probe to the compressor HERM terminal...

Страница 20: ...0459 7 52 2438 20 12 6431 47 3 8867 6 49 3161 21 12 0561 48 3 7348 5 46 5725 22 11 5 49 3 5896 4 44 23 10 9731 50 3 451 3 41 5878 24 10 4736 51 3 3185 2 39 8239 25 10 52 3 1918 1 37 1988 26 9 5507 53...

Страница 21: ...nd recharge the refrigerant after checking for the reason Compressor The compressor is blocked inside Replace after checking for the reason Fan motor will not run No power Check voltage at electrical...

Страница 22: ...ssis by open the drainage hose on the chassis Water depth sensing structure Check and replace or realign if the structure is failure Dehumidifier does not dry the air as it should Air filter Clean or...

Страница 23: ...7 Drain stopper 1 1 3 Filter 1 8 Handle 1 1 4 Filter guide II 1 10 Water tank assembly 1 2 Display box assembly 1 10 1 water tank 1 2 1 Control panel 1 10 2 cover for water tank 1 2 2 Display board as...

Страница 24: ...r guide II 1 10 Water tank assembly 1 2 Display box assembly 1 10 1 water tank 1 2 1 Control panel 1 10 2 cover for water tank 1 2 2 Display board assembly 1 10 3 Dobber 1 2 6 knob 1 11 Water drain pa...

Страница 25: ...1 9 2 Water drain pan 1 2 2 Filter guide I 1 10 Compressor 1 2 3 Filter 1 11 Display box assembly 1 2 4 Filter guide II 1 11 1 Control panel 1 3 Exhaust scroll assembly 1 11 2 Display board assembly 1...

Страница 26: ...2 1 Front panel 1 9 1 Micro Switch 1 2 2 Filter guide I 1 9 2 Water drain pan 1 2 3 Filter 1 10 Compressor 1 2 4 Filter guide II 1 11 Display box assembly 1 3 Exhaust scroll assembly 1 11 1 Control p...

Страница 27: ...nt panel assembly 1 9 1 Micro Switch 1 2 1 Front panel 1 9 2 Water drain pan 1 2 2 Filter guide I 1 10 Compressor 1 2 3 Filter 1 11 Display box assembly 1 2 4 Filter guide II 1 11 1 Control panel 1 3...

Страница 28: ...9 1 Micro Switch 1 2 1 Front panel 1 9 2 Water drain pan 1 2 2 Filter guide I 1 10 Compressor 1 2 3 Filter 1 11 Display box assembly 1 2 4 Filter guide II 1 11 1 Control panel 1 3 Exhaust scroll asse...

Отзывы: