Safety 

Precautions

 Page 7

 

and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % 

maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of 

detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and 

corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished. 

If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from 

the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. 

Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the 

brazing process.  

When breaking into the refrigerant circuit to make repairs or for any other purpose conventional 

procedures shall be used. However, it is important that best practice is followed since flammability is a 

consideration. The following procedure shall be adhered to:

Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the 

circuit by cutting or brazing.   

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed 

with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or 

oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system 

with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and 

finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. 

When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable 

work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take 

place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is 

ventilation available.

 

 

10.Detection of flammable refrigerants

The following leak detection methods are deemed acceptable for systems containing flammable 

refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity 

may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a 

refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for 

the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant 

11.Leak detection methods

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or 

any other adverse environmental effects. The check shall also take into account the effects of aging or 

continual vibration from sources such as compressors or fans.

9.Cabling

12.Removal and evacuation

13.Charging procedures

In addition to conventional charging procedures, the following requirements shall be followed. Ensure

that contamination of different refrigerants does not occur when using charging equipment. Hoses or 

lines shall be as short as possible to minimise the amount of refrigerant contained in them. 

Cylinders shall be kept upright.

Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.

Label the system when charging is complete (if not already).

Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it 

shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior 

to commissioning. A follow up leak test shall be carried out prior to leaving the site.

Under no circumstances shall potential sources of ignition be used in the searching for or detection 

of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

 

Содержание MDDM20

Страница 1: ...DEHUMIDIFIER Owner s Manual Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new machine Make sure to save this manual for future reference MDDM20...

Страница 2: ...r features 13 Clean the grille and case 17 Clean the bucket 17 Troubleshooting Tips 18 Clean the air filter 17 When not using the unit for long time periods 18 Caster installation and disassembly inst...

Страница 3: ...or combustibles such as gasoline benzene thinner etc Do not drink or use the water drained from the unit Do not take the water bucket out during operation Do not use the unit in small spaces Do not pu...

Страница 4: ...n damaged contact a technician or customer service for assistance In a thunderstorm the power must be cut off to avoid damage to the machine due to lightning Do not run cord under carpeting Do not cov...

Страница 5: ...of such waste separately for special treatment is necessary It is prohibited to dispose of this appliance in domestic household waste For disposal there are several possibilities When using this dehu...

Страница 6: ...manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants The appl...

Страница 7: ...able material 4 Checking for presence of refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work to ensure the technician is aware of potentially flamma...

Страница 8: ...supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing t...

Страница 9: ...ions on the pipe work are to take place Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available 10 Detection of flammable refrigerants The fo...

Страница 10: ...order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered re...

Страница 11: ...ehumidifier up pull out the power code and rotate 90 clockwise 3 Place the dehumidifier into the water bucket gently according to the ALIGN label until it clicks in place Do never install it rudely NO...

Страница 12: ...help prevent moisture damage The dehumidifier must be operated in an enclosed area to be most effective Close all doors windows and other outside openings to the room A dehumidifier operating in a bas...

Страница 13: ...less Mode Wireless light Fresh light Filter clean light Auto deforst light Pump light In Setting dehumidifying mode on some models the set indicator light illuminates On some models the unit without s...

Страница 14: ...ted time will register in 5 seconds and the system will automatically revert back to display the previous humidity setting Turning the unit ON or OFF at any time or adjusting the timer setting to 0 0...

Страница 15: ...esumes Smart dehumidifying mode On some models Continuous dehumidifying mode At continuous dehumidifying mode the unit dehumidify continuously and cannot select humidity Press mode button to exit cont...

Страница 16: ...plug before moving the unit 3 The overall height of the tube should be lower than the drain to avoid water backflow and ensure smooth discharge X X 10cm or more NOTE At the Bucketless mode the hight...

Страница 17: ...2 For some models When the unit is on if the bucket is full the compressor turns off and the fan turns off after 30 seconds for drying the water of the condenser then the unit will beep 8 times and th...

Страница 18: ...not being used remove the pump drain hose from the outlet Press the pump drain hose outlet in and take the pump drain hose out from it Take the pump hose out from the unit Make sure do not let the wat...

Страница 19: ...et must be in place and securely seated for the dehumidifier to operate The air filter behind the two flanks grille should be checked and cleaned at least every two weeks or more often if necessary NO...

Страница 20: ...ead of upright as it should be The floor surface is not level Hose to connector or hose connection may be loose Intend to use the bucket to collect water but the back drain plug is removed This is nor...

Страница 21: ......

Страница 22: ...ations are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website pl...

Страница 23: ...USER MANUAL OF SMART KIT IMPORTANT NOTE Read the manual carefully before connecting your Smart kit Wireless module Make sure to save this manual for future reference...

Страница 24: ...CONTENTS SPECIFICATION PRECAUTIONS DOWNLOAD AND INSTALL APP USER REGISTRATION NETWORK CONFIGURATION HOW TO USE APP SPECIAL FUNCTIONS APP DECLARATION 1 2 3 4 5 6 7 8 1 1 2 2 3 8 9 11...

Страница 25: ...ption WPA PSK WPA2 PSK encryption is recommended Due to different network situation control process may return time out sometimes If this situation occurs the display between board and APP may not be...

Страница 26: ...o Wi Fi Wireless router Also the Wi Fi Wireless router has already connected to Internet before doing user registration and network configuration It is better to log in your email box and active your...

Страница 27: ...ce has already been connected to the Wi Fi Wireless network which you want to use Also you need to forget other irrelevant Wi Fi Wireless network in case it influences your configuration process 1 2 A...

Страница 28: ...Code Choose the network configuration method 6 Choose the Scan the QR code method Sacn the QR code on the unit 7 Or choose the Manual Setup method 8 Please enter password 9 Network configuration is s...

Страница 29: ...forget other irrelevant Wi Fi Wireless network in case it influences your configuration process 1 2 Activate the AP mode Read the WIRELESS MODE IN OWNER S MANUAL for detailed operations Using iOS devi...

Страница 30: ...Connect to the Wi Fi Wireless network 6 Please enter password 7 Network configuration is successful 8 6 Follow the above steps to enter AP mode 5...

Страница 31: ...e device status still display offline If this situation occurs it is necessary to pull and refresh the device list on the APP and make sure the device status become online Alternatively user can turn...

Страница 32: ...con to activate Press again to deactivate 6 Anti mould mode on some models Click Anti mould icon to activate Press again to deactivate 8 Pure mode on some models Click Pure icon to activate Press agai...

Страница 33: ...l to find more information 7 SPECIAL FUNCTIONS Including Timer on Timer off Share device NOTE If the dehumidifier do not support the above function the function will be hided from the function list Sc...

Страница 34: ...be controlled by multi users at the same time by Share Device function Click Share device 1 QR code display 2 The other users must log in the Midea Air APP then click Add Shared Device and scan the QR...

Страница 35: ...limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not install...

Страница 36: ...CD003IU APWIFI OBM...

Отзывы: