9.7.5 Remove the switch box cover
NOTE
Unit
4kW
6kW
8kW
10kW
12kW
14kW
16kW
12kW 3-PH
14kW 3-PH
16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
18
18
19
19
30
30
30
14
14
14
Wiring size(mm
2
)
4.0
4.0
4.0
4.0
6.0
6.0
6.0
2.5
2.5
2.5
MCA :
Max. Circuit Amps. (A)
TOCA :
Total Over-current Amps. (A)
MFA :
Max. Fuse Amps. (A)
MSC :
Max. Starting Amps. (A)
RLA :
In nominal cooling or heating test condition
,
the input Amps of compressor where MAX. Hz
can operate Rated Load Amps. (A);
KW :
Rated Motor Output
FLA :
Full Load Amps. (A)
Unit
4kW
6kW
8kW
10kW
12kW
14kW
16kW
12kW 3-PH
14kW 3-PH
16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
31
31
32
32
43
43
43
27
27
27
Wiring size(mm
2
)
6.0
6.0
8.0
8.0
10.0
10.0
10.0
4.0
4.0
4.0
Unit
8kW
10kW
12kW
14kW
16kW
12kW 3-PH
14kW 3-PH
16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
32
32
43
43
43
27
27
27
Wiring size(mm
2
)
8.0
8.0
10.0
10.0
10.0
4.0
4.0
4.0
1-phase 8-16kW and 3-phase 12-16kW standard with backup heater 9kW(3-phase)
1-phase 4-16kW and 3-phase 12-16kW standard with backup heater 3kW (1-phase)
1-phase 4-16kW stadard and 3-phase 12-16kW standard
The ground fault circuit interrupter must be a high-speed type breaker of 30 mA (<0.1 s).
Please use 3-core shielded wire.
NOTE
UNIT POWER SUPPLY
1-phase
L
N
L N
LPS
F
USE
XT1
UNIT POWER SUPPLY
3-phase
LPS
F
USE
L1
N
L2 L3
C N
B
A
XT1
UNIT POWER SUPPLY
3-phase
LPS
F
USE
L1
N
L2 L3
C N
B
A
XT1
Содержание M-thermal Mono Series