7.3
FOR SERVICEMAN Menu
FOR SERVICEMAN
allows installers to input the system configuration and set
the system parameters. To enter
FOR SERVICEMAN
, go to
MENU
>
FOR
SERVICEMAN
.
Enter the password, using
◄
►
to navigate between digits and using
▼
▲
to
adjust the numerical values, and then press
OK
. The password is 234. Refer to
Figure 3-7.2
Then the following pages will be displayed after putting the password. Refer
to Figure 3-7.3
Figure 3-7.3: FOR SERVICEMAN menu
7.4
DHW MODE SETTING Menu
7.4.1
DHW MODE SETTING menu overview
MENU
>
FOR SERVICEMAN
>
DHW MODE SETTING
Figure 3-7.4: DHW MODE SETTING menu
In
DHW MODE SETTING
the following parameters should be set.
DHW MODE
enables or disables DHW mode. For installations with DHW tanks, select
YES
to enable DHW mode. For
installations without DHW tanks, select
NON
to disable DHW mode.
DISINFECT
sets whether or not the disinfection operation is performed.
DHW PRIORITY
sets whether domestic hot water heating or space heating/cooling takes priority. If
NON
is selected in the
DHW PRIORITY
mode, when it is available and the space heating/cooling is
OFF
, the heat pump will heat the water as
required. If space heating/cooling is
ON
, the water will be heated as required when the immersion heater is unavailable.
OK
ENTER
FOR SERVICEMAN
1. DHW MODE SETTING
2. COOL MODE SETTING
3. HEAT MODE SETTING
4. AUTO MODE SETTING
5. TEMP.TYPE SETTING
6. ROOM THERMOSTAT
1/3
7. OTHER HEATING SOURCE
8. HOLIDAY AWAY MODE SET
TING
9. SERVICE CALL SETTING
10. RESTORE FACTORY SETTINGS
11. TEST RUN
12. SPECIAL FUNCTION
OK
ENTER
FOR SERVICEMAN
2/3
OK
ENTER
FOR SERVICEMAN
13. AUTO RESTART
14. POWER INPUT LIMITATION
15. INPUT DEFINE
16. CASCADE SET
17. HMI ADDRESS SET
3/3
1 DHW MODE SETTING
YES
YES
YES
YES
NON
ADJUST
1.2 DISINFECT
1.3 DHW PRIORITY
1.4 DHW PUMP
1.5 DHW PRIORITY TIME SET
1/5
5
°C
10°C
43°C
-10°C
5 MIN
1 DHW MODE SETTING
1.6 dT5_ON
1.7 dT1S5
1.8 T4DHWMAX
1.9 T4DHWMIN
1.10 t_INTERVAL_DHW
2/5
ADJUST
5
°C
5 °C
30 MIN
65°C
15MIN
1 DHW MODE SETTING
1.11 dT5_TBH_OFF
1.12 T4_TBH_ON
1.13 t_TBH_DELAY
1.14 T5S_DI
1.15 t_DI HIGHTEMP.
ADJUST
3/5
210
MIN
30 MIN
120 MIN
YES
5 MIN
1 DHW MODE SETTING
1.16 t_DI_MAX
1.17 t_DHWHP_RESTRICT
1.18 t_DHWHP_MAX
1.19 DHWPUMP TIME RUN
1.20 PUMP RUNNING TIME
4/5
ADJUST
NON
1 DHW MODE SETTING
1.21 DHW PUMP DI RUN
5/5
ADJUST
Figure 3-7.2: FOR SERVICEMAN password screen
Please input the password:
ADJUST
OK
ENTER
0
0 0
FOR SERVICEMAN
Midea CAC Confidential