background image

24

 32801000302

Specifications  subject to change without notice.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment
damage or improper operation.

Never use the system compressor as a vacuum pump.

CAUTION

!

Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used if the procedure outlined below
is followed. Always break a vacuum with dry nitrogen.

Final Tubing Check

IMPORTANT:

 

Check to be certain factory tubing on both indoor and

outdoor unit has not shifted during shipment. Ensure tubes are not
rubbing against each other or any sheet metal. Pay close attention to
feeder tubes, making sure wire ties on feeder tubes are secure and tight.

START−UP

Test Operation

Perform test operation after completing gas leak and electrical safety
check (see Fig. 49).

Infrared receiver

Timer indicator

Alarm indicator

PRE-DEF 
(pre-heating/defrost) 
indicator  

Manual button

Operation indicator

LED display

Fig. 49

 - 

IR Receiver Display Panel

1. Press MANUAL on the IR receiver located in the control box to

begin testing.

NOTE:  A protection feature prevents air conditioner from being
activated for approximately 3 to 4 minutes.

2. Push  MODE, select COOLING,  HEATING,  FAN  mode to

check if all functions work correctly.

3. To run the test using the MANUAL button in the indoor unit:

(3.) Open front panel of the indoor unit;

(4.) Push the manual switch once to energize the unit.  The

set conditions of manual operation are as follows:
· Preset set point: 76

_

F (24

_

C)

· Fan speed: AUTO
· Discharge air direction: Pre−set position based on
operation in “Cool” or “Heat” mode.

4. Be sure to set the manual switch to OFF (by pushing it twice

again) after finishing the test operation.

SYSTEM CHECKS

1. Conceal the tubing where possible.

2. Ensure the drain tube slopes downward along its entire length.

3. Ensure all tubing and connections are properly insulated.

4. Fasten tubes to the outside wall, when possible.

5. Seal the hole through which the cables and tubing pass.

INDOOR UNIT

1. Do all remote control buttons function properly?

2. Do the display panel lights work properly?

3. Does the air deflection louver function properly?

4. Does the drain work?

Explain Following Items To Customer (with the aid of the Owner’s
Manual):

1. How to turn air conditioner on and off; selecting COOLING,

HEATING and other operating modes; setting a desired
temperature; setting the timer to automatically start and stop air
conditioner operation; and all other features of the remote
control and display panel.

2. How to remove and clean the air filter.

3. How to set air deflection louver.

4. Explain care and maintenance.

5. Present the owner’s manual and installation instructions to cus-

tomer.

FAN MOTOR MAINTENANCE

The rear ventilated panel is used as an example.

Motor Maintain:

1. Take off the ventilated panel.

2. Take off the blower housing.

3. Take off the motor.

Motor

Blower housing

Ventilated panel

Fig. 50

 - 

Maintain the Motor

Содержание DLFLDA

Страница 1: ...mages are for illustration purposes only Actual models may differ slightly TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 INSTALLATION CLEARANC...

Страница 2: ...ill result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal i...

Страница 3: ...llustration purposes only Notes If the outdoor unit is higher than the indoor unit prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connection...

Страница 4: ...EMF area and communication issues exist a 14 2 stranded shielded wire can be used to replace L2 and S between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only Sizes...

Страница 5: ...2 29 2 14 2 3 3 5 5 3 3 3 3 40 mm 700 200 506 450 137 537 30 152 599 186 50 741 360 84 140 84 84 18 1 18 In 34 65 8 27 26 54 23 62 5 51 27 80 1 97 5 35 30 79 7 48 1 57 36 22 20 3 07 5 83 3 46 4 41 54...

Страница 6: ...6 32801000302 Specifications subject to change without notice DIMENSIONS CONT Airflow Airflow Fig 5 Indoor Unit Sizes 58K...

Страница 7: ...ess Panel 17 7 in 45cm x 17 7 in 45cm 7 8 in 20cm 11 81 in 30cm 4 in 10cm Bottom Return Blower Motor Service Clearance Filter Service Clearance Blower Motor Service Clearance PCB Board Service Clearan...

Страница 8: ...ling grid is supported separately from the unit The ceiling grid must not be supported by any part of the unit or any associated wiring or piping work CAUTION MOUNTING THE UNIT 1 INSTALLING HANGER BOL...

Страница 9: ...he condensate piping should be as close to the unit as possible see Fig 17 S Condensate piping should slope downward in the direction of condensate flow with a minimum gradient of 1 100 S When multipl...

Страница 10: ...with clamps on both ends c Connect the drainpipe to the connector D see Fig 20 d Plug the power cable of the external pump to CN13 PUMP pin and plug the water level sensor cable to the CN5 WATER to en...

Страница 11: ...T PUMP AND DRAINAGE TEST Follow these steps to perform the test 1 Remove the test cover by rotating it counter clockwise as shown in Fig 27 2 Using a piece of tubing or pipe fill the condensate lift p...

Страница 12: ...lection either SP or AF NOTE T1 T2 T26 T3 T4 are sub menus for thermistors Do not select for setting external static pressure Fig 30 Wired Controller Menu Selection 1 If setting the external static pr...

Страница 13: ...40 Pa 24 42 72 98 0 100 24 In WG 0 10 0 216 0 336 0 528 0 0 64 Pa 25 54 84 132 0 160 36 In WG 0 168 0 312 0 48 0 62 0 0 64 Pa 42 78 120 155 0 160 48 In WG 0 18 0 404 0 616 0 64 0 0 64 Pa 45 101 154 1...

Страница 14: ...14 32801000302 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 32 Fan Performance 40MBDQ09...

Страница 15: ...32801000302 15 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 33 Fan Performance 40MBDQ12...

Страница 16: ...16 32801000302 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 34 Fan Performance 40MBDQ18...

Страница 17: ...32801000302 17 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 35 Fan Performance 40MBDQ24...

Страница 18: ...18 32801000302 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 36 Fan Performance 40MBDQ36...

Страница 19: ...32801000302 19 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 37 Fan Performance 40MBDQ48...

Страница 20: ...20 32801000302 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 38 Fan Performance 40MBDQ58...

Страница 21: ...5 0 56 420 48 3 2 0 75 560 58 3 65 0 952 1000 LEGEND FLA Full Load Amps CONNECTION DIAGRAMS Fig 39 Connection Diagrams sizes 09 to 24 Fig 40 Connection Diagrams sizes 36 and 58 Fig 41 Control and Powe...

Страница 22: ...Table 9 for the flare nut spaces Table 9 Flare Nut Spacing OUTER DIAM mm A mm Max Min 1 4 6 35 0 05 1 3 0 03 0 7 3 8 9 52 0 06 1 6 0 04 1 0 1 2 12 7 0 07 1 8 0 04 1 0 5 8 15 88 0 09 2 2 0 08 2 0 Bar C...

Страница 23: ...a wireless remote controller is used relocate the IR receiver within line of sight of remote location using the 6 ft cable included The factory location of the IR receiver is inside the control box s...

Страница 24: ...Open front panel of the indoor unit 4 Push the manual switch once to energize the unit The set conditions of manual operation are as follows Preset set point 76_F 24_C Fan speed AUTO Discharge air dir...

Страница 25: ...F6 Compressor low pressure protection H 4 times X E3 Indoor fan speed has been out of control H 5 times X E4 Indoor room temperature sensor T1 open circuit or short circuit H 6 times X E5 Evaporator...

Страница 26: ...26 32801000302 Specifications subject to change without notice Copyright 2018 International Comfort Products CMNA 1025 Cobb Place Blvd NW Kennesaw GA 30152...

Отзывы: