background image

12                                                                 

Specifications subject to change without notice.                                                                         32801002001

Step 5 - Condensate Drains

The drainpipe is used to drain water away from the unit. Improper 

installation may cause unit and property damage.

NOTE: 

Installation requires adapting the locally sourced drain line to 

a 3/4” NPT female pipe thread connection.

INDOOR DRAINPIPE INSTALLATION

1. Cover the drainpipe with insulation, as required, to prevent 

condensation and leakage. These units operate with a positive 
pressure at the drain connection and a drain trap is required. The 
trap needs to be installed as close to the unit as possible. Ensure the 
top of the trap is below the connection to the drain pan to allow 
complete drainage of the pan.

Fig. 37 — Vertical Discharge

NOTE: 

Horizontal runs must also have a drain trap installed ahead 

of the horizontal run to eliminate air trapping.

Fig. 38 — Primary Drain

NOTES: When using an extended drainpipe, tighten the indoor 
connection with an additional protection tube to prevent it from 
pulling loose.

Figure 37 shows how to trap or plug all drains to provide a a vertical 
discharge. Figure 38 shows how to trap or plug all drains to provide a 
right-hand discharge.

Hand tighten the plug(s) for drain holes that are unused.
Incorrect installation could cause water to flow back into the unit and
flood.

2. Use a 2.5in (65mm) core drill to drill a hole in the wall. Make sure 

the hole is drilled at a slight downward angle, so that the outdoor 

end of the hole is lower than the indoor end by about 0.5in (12mm). 

This will ensure proper water drainage. Place the protective wall 

cuff in the hole. This protects the edges of the hole and helps seal 

the hole once the installation is complete.

Fig. 39 — Drill hole

NOTE: 

When drilling the hole, make sure to avoid wires, plumbing, 

and other sensitive components. 

3. Pass the drain hose through the wall hole. Make sure the water 

drains to a safe location where it will not cause water damage or a 

slipping hazard.

NOTE: The drainpipe outlet should be at least 2in(5cm) above the 
ground. If it touches the ground, the unit may become blocked 
and malfunction. If you discharge the water directly into a sewer, 
make sure that the drain has a U or S pipe to catch odors that 
might otherwise come back into the house. Follow the local 
plumbing codes.

• Insulate all piping to prevent condensation, which could lead to 

water damage. Check the local codes.

• If the drainpipe is bent or installed incorrectly, water may leak 

and cause a water-level switch malfunction.

• In 

HEAT

 mode, the outdoor unit may discharge water. Ensure 

that the outdoor drain will not contribute to damage and 
slippage.

• 

DO NOT

 pull the drainpipe forcefully. This could disconnect it.

CAUTION

VERTICAL DISCHARGE

PRIMARY DRAIN

Install a drain trap per the local codes

PRIMARY DRAIN

Wall

Indoor

Outdoor

≈ 0.5 in.(12mm) 

 

Содержание DLFLAA

Страница 1: ...work gloves Have a fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in the literature and attached to the unit Consult local building codes a...

Страница 2: ...allation parts and accessories to install the system Improper installation may result in water leakage electrical shock and fire or cause the equipment to fail Keep the installation manual in a safe p...

Страница 3: ...84 11 8 299 13 3 339 3 0 75 2 5 64 4 9 124 6 8 174 1 7 44 A HEIGHT 48 1 1222 C WIDTH 19 7 501 4 8 121 2 4 61 6 7 171 2 2 57 D DUCT 18 2 462 E DUCT 10 3 262 B DEPTH 21 1 535 0 8 21 0 5 13 0 6 16 18 4...

Страница 4: ...med according to the installation instructions Improper installation can cause water leakage electrical shock or fire In North America installation must be performed in accordance with the requirement...

Страница 5: ...t is installed over a finished ceiling and or living area building codes may require a field supplied secondary condensate pan to be installed under the entire unit Some localities may allow as an alt...

Страница 6: ...t 5 Install the drain lines Fig 7 Vertical Upflow Installations Fig 8 Horizontal Right Installations NOTE For a horizontal right installation secondary condensate pan field supplied must be installed...

Страница 7: ...d drain pan assembly 9 Reinstall the pipe temperature sensor in its original position Attach the room temperature sensor to the evaporator output pipe protection sleeve Fig 15 Reinstall the Pipe Tempe...

Страница 8: ...uipped with the electric auxiliary heat module please check the electric auxiliary heat module specification that is compatible with the unit to avoid unnecessary consequences caused by improper match...

Страница 9: ...into the opening made by removal of the sheet metal cover s Ensure the two support rod ends are on the opposite bulkhead Fig 24 Insert Heating Module 5 Use the 3 screws 6 screws for 15K or 20K remove...

Страница 10: ...quirements and local codes see Table 6 on page 11 Choose the power cord and the power cord installation location see Figure 30 Each circuit breaker group needs to connect to the power input line Where...

Страница 11: ...do not have a 90 degree elbow and 10ft 3m of main duct to first branch takeoff may require internal acoustical insulation lining As an alternative fibrous ductwork may be used if constructed and insta...

Страница 12: ...ood 2 Use a 2 5in 65mm core drill to drill a hole in the wall Make sure the hole is drilled at a slight downward angle so that the outdoor end of the hole is lower than the indoor end by about 0 5in 1...

Страница 13: ...g an airtight seal a After removing the burrs from the cut pipe seal the ends with PVC tape to prevent foreign materials from entering the pipe b Sheath the pipe with insulating material c Place flare...

Страница 14: ...nder to prevent kinking or damaging the tubing 6 After connecting the copper pipes to the outdoor unit wrap the power cable signal cable and the piping together with binding tape NOTE While bundling t...

Страница 15: ...ost positive way of assuring a system is free of air and moisture see Fig 49 NOTE DO NOT add a filter line drier Fig 49 Deep Vacuum Graph Triple Evacuation Method The triple evacuation method should b...

Страница 16: ...it would lose power A disconnect switch is not required on the indoor unit side on the wiring between the outdoor and indoor unit A 3 pole disconnect purchased separately may be used for extra protect...

Страница 17: ...e is a ground wire To minimize voltage drop the factory recommended wire size is 14 2 power stranded with a ground Communication Wiring A separate 2 wire cable stranded shielded copper conductor with...

Страница 18: ...0 5 0 20 120 36 5 0 42 250 48 5 0 65 400 3 S 1 L1 2 L2 208 230 1 60 Power Supply Main 1 L1 208 230 1 60 2 L2 3 S 1 L1 2 L2 CONNECTING CABLE OUTDOOR TO INDOOR Indoor Unit Power Supply 208 230 1 60 Indo...

Страница 19: ...Indoor Unit Control Box Sizes 36 48 LED Display The control displays active faults codes on the LED display When the control displays the fault code and the LED flashes quickly there is something wro...

Страница 20: ...nnected b Turn off the power to the indoor and outdoor units for 3 minutes c Turn the power back on Wait 1 minute and check the 24 volt Interface digital display If the display reads 00 then proceed I...

Страница 21: ...troller exits the MODIFICATION mode After you power OFF the unit power the unit ON again and the unit retains the setting value Fig 65 RG57 Remote Controller FP Activate Disable freeze protection func...

Страница 22: ...1 400 1 310 1 215 1 105 950 825 Low 1 525 1 450 1 372 1 280 1 190 1 074 935 785 650 36 SP1 High 1 335 1 270 1 165 1 062 950 810 645 450 240 Medium 1 185 1 100 990 845 685 520 335 Low 1 020 915 775 60...

Страница 23: ...Pressurein WC High Medium Low SP4 0 200 400 600 800 1 000 1 200 1 400 1 600 1 800 2 000 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Air ow CFM Sta cPressurein WC High Medium Low SP1 0 200 400 600 800 1 000 1...

Страница 24: ...M Sta cPressurein WC High Medium Low SP2 0 200 400 600 800 1 000 1 200 1 400 1 600 1 800 2 000 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Air ow CFM Sta c Pressurein WC High Medium Low SP3 0 200 400 600 800...

Страница 25: ...conditioner Turn off the main power switch and reinstall the test cover NOTE If the unit malfunctions or does not operate according to your expectations please refer to the Troubleshooting section of...

Страница 26: ...FF E0 Indoor unit EEPROM parameter error 2 times OFF E1 Indoor outdoor unit communication error 4 times OFF E3 The indoor fan speed is operating outside of the normal range 5 times OFF E4 Indoor room...

Отзывы: