MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
155
14) Ambient temperature sensor malfunction
Ambient
temperature
sensor
malfunction.
Inform
the
customer service
center.
PCB mistakes to alarm.
The circuit of ambient temperature
sensor is broken.
Replace PCB.
Replace temperature sensor.
The circuit of ambient temperature
sensor is shorten.
Replace temperature sensor.
The joint of ambient temperature
sensor is loose.
Fixed joint.
No
Yes
Yes
Yes
Yes
Yes
No
No
No