E1/EL01 – Comms Error
If all is ok with field cabling and wiring
•
Use your multimeter to measure the dc voltage between terminals S
& N (black tester S / red tester N)
•
Voltage should flucate b and - values
•
If the voltage is fixed it is the indoor board at fault
•
If the voltage fluctuates but only with positive values it is the outdoor
board at fault
•
Check spade connections onto boards. If all is good, condemn the
applicable PCB