CONTROL SETTINGS

Press once to view the current

overtemp alarm setting.

Each additional push will raise

the overtemp alarm setting

by 1

O

 

.

To toggle between Fahrenheit

and Celsius, press and hold for

3 seconds.

PUSH

ALARM SET POINT BUTTON:
- To change display from Fahrenheit to Celsius, press and hold Alarm Set Point Button for 3 seconds. 
- To view alarm set point, simply press and release the Alarm Set Point Button once.  
- To change the factory preset alarm set point, repeatedly press the Alarm Set Point Button until 
   desired temperature is displayed. Factory preset overtemp alarm set point is 100

O

F (37

O

C). 

   Adjustment range is from 95

O

 to 115

O

F (35

O

 to 46

O

C)

FAN FAULT / OVERTEMP ALARM OUTPUT:
These normally open dry contact closures will provide an alarm to an external (remote) monitoring
system if your enclosure experiences a fan fault or overtemp condition.

5V DC INPUT JACK: Power supply connector

TEMPERATURE PROBE: Remote temperature sensor (9' long).

FAN FAULT ALARM OUTPUT

5V DC INPUT JACK

OVERTEMP ALARM OUTPUT

TEMPERATURE PROBE

REAR VIEW

SIDE VIEW

ALARM SET POINT BUTTON

OVER

TEMP

ALARM

(N.O.)

5VDC 

2A

FAN

FAULT

ALARM

(N.O.)

DO NOT OPEN. NO USER SERVICEABLE PARTS INSIDE.

Содержание UQFP Series

Страница 1: ...asing the UQFP Series Ultra Quiet Fan Panel Please read these instructions thoroughly before installing this product PRODUCT FEATURES Reliable cooling with minimal noise Local and remote status notifi...

Страница 2: ...Speed 310 mA 5V DC UQFP 2D IUQFP 2D RPM 1900 Full Speed Noise 24 dB Full Speed UQFP 4 UQFP 4D IUQFP 4 IUQFP 4D Current Draw 510 mA 5V DC UQFP 4 IUQFP 4 Airflow 100 CFM Full Speed 560 mA 5V DC UQFP 4D...

Страница 3: ...ack temperature reaches 100O F 37O C this LED will light indicating an over temperature condition within the rack OVERTEMP ALARM OUTPUT This normally open dry contact closure will provide an alarm to...

Страница 4: ...t Button instructions below to change the overtemp alarm setting DISPLAY The display will indicate the rack temperature and provide a read out of the following fault codes during one of these conditio...

Страница 5: ...the Alarm Set Point Button until desired temperature is displayed Factory preset overtemp alarm set point is 100O F 37O C Adjustment range is from 95O to 115O F 35O to 46O C FAN FAULT OVERTEMP ALARM...

Страница 6: ...o toggle between Fahrenheit and Celsius press and hold for 3 seconds OVER TEMP ALARM N O 5VDC 2A FAN FAULT ALARM N O PUSH CONTROL SETTINGS Press once to view the current overtemp alarm setting Each ad...

Страница 7: ...vent at the top of side panels Do not place vent panels within six rackspaces below fan panel Cover any of these spaces If heat producing equipment is in the middle of the rack use a 3 space vent pane...

Страница 8: ...ANY KIND EITHER EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO THE MAXIMUM EXTENT PERMITTED BY APPLICABLE LAW IN NO EV...

Отзывы: