Page 5
CONTROL SETTINGS
Press once to view the current
overtemp alarm setting.
Each additional push will raise
the overtemp alarm setting
by 1
O
.
To toggle between Fahrenheit
and Celsius, press and hold for
3 seconds.
PUSH
ALARM SET POINT BUTTON:
- To change display from Fahrenheit to Celsius, press and hold Alarm Set Point Button for 3 seconds.
- To view alarm set point, simply press and release the Alarm Set Point Button once.
- To change the factory preset alarm set point, repeatedly press the Alarm Set Point Button until
desired temperature is displayed. Factory preset overtemp alarm set point is 100
O
F (37
O
C).
Adjustment range is from 95
O
to 115
O
F (35
O
to 46
O
C)
FAN FAULT / OVERTEMP ALARM OUTPUT:
These normally open dry contact closures will provide an alarm to an external (remote) monitoring
system if your enclosure experiences a fan fault or overtemp condition.
5V DC INPUT JACK: Power supply connector
TEMPERATURE PROBE: Remote temperature sensor (9' long).
FAN FAULT ALARM OUTPUT
5V DC INPUT JACK
OVERTEMP ALARM OUTPUT
TEMPERATURE PROBE
REAR VIEW
SIDE VIEW
ALARM SET POINT BUTTON
OVER
TEMP
ALARM
(N.O.)
5VDC
2A
FAN
FAULT
ALARM
(N.O.)
DO NOT OPEN. NO USER SERVICEABLE PARTS INSIDE.