background image

Method 2: Using a command prompt
 

1. Obtain the MAC Address from the label on the UPS-OLIPCARD.

  Each card has a unique MAC Address.

2. Use the ARP command to set the IP Address.

 Example:

  To assign the IP Address 

192.168.10.134

 on a card with a MAC

  Address of 

00-0C-15-00-FF-99

, type the following in to a command 

  prompt on a PC connected to the same network as the

 UPS-OLIPCARD: 

  a. Type: 

arp -s 192.168.10.134 00-0C-15-00-FF-99

  b. Press 

Enter

.

3. Use the Ping command to assign a size of 123 bytes to the IP Address:

  a. Type: 

ping 192.168.10.134 -l 123

 

  b. Press 

Enter

.

 

If replies are received, your computer can communicate with the IP

 Address.

 

   

.

8. If the IP Address change is 

  successful, a confirmation

  message appears as shown

  in Figure 4.

7. You will need to enter a User

  Name and Password for the 

  UPS-OLIPCARD in the 

  Authentication window, as

  shown in Figure 3.

  • Default user name: 

admin

  • Default password: 

admin

After logging in for the first time, 

the system forces you to change 

the default password for security 

purposes.

 

WEB INTERFACE 

Logging into the Accounts

You will need to enter a User name and Password to login to the interface.

There are two account types:

1. Administrator

  • Default user name: 

admin

   • Default password: 

admin

2. Viewer (Read Only)

  • Default user name: 

guest

   • Default password: 

guest

NOTE

:

• The administrator can access and control all functions, including enabling 

  and disabling the viewer account. The viewer account can read all functions 

  but with no ability to change any settings. 

• After logging in as the administrator for the first time, the system forces you 

  to change the default password for security purposes.

Troubleshooting

Problem

Unable to configure 

the UPS-OLIPCARD

using method 1 or 

method 2

 

Unable to ping the 

UPS-OLIPCARD

 

Forgotten user 

name and password

1. Check the LED status; the condition is normal

  when the yellow and green LEDs are both on.

 

If the green LED is off: 

  • Verify the UPS-OLIPCARD is properly seated 

 

in the device and the power is turned on.

  If the yellow LED is off:

  • Verify your network connection is working.

2. Verify the PC being used is on the same network

  subnet as the UPS-OLIPCARD you are trying to

  communicate with.

1. Use method 1 and/or method 2 to get or set a 

  correct IP address for the UPS-OLIPCARD.

2. If the PC being used is on a different network

  subnet from the UPS-OLIPCARD, verify the 

  setting fo the Subnet Mask and the IP Address 

  of the Gateway.

Refer to “Restoring Default Settings and Resetting 

Passwords” topic in the UPS Online IP Card User 

Manual at www.middleatlantic.com.

 

Federal Communications Commission (FCC) 

Compliance Statement

 

This device complies with Part 15 of the FCC Rules. Operation is subject to the 

following two conditions: 

1. This device may not cause harmful interference.

2. This device must accept any interference received, including interference 

  that may cause undesired operation.

NOTE

: This equipment has been tested and found to comply with the

limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. 

These limits are designed to provide reasonable protection against harmful 

interference when the equipment is operated in a commercial environment. 

This equipment generates, uses, and can radiate radio frequency energy 

and, if not installed and used in accordance with the instruction manual, 

may cause harmful interference to radio communications. Operation of 

this equipment in a residential area is likely to cause harmful interference 

in which case the user will be required to correct the interference at his 

own expense.

REMARQUE

: Cet équipement a été testé et jugé conforme aux limites de

la classe A des appareils numériques, conformément à la section 15 de la 

réglementation de la FCC. Ces limites sont conçues pour fournir une 

protection raisonnable contre les interférences nuisibles lorsque l'équipement 

est utilisé dans un environnement commercial. Cet équipement génère, 

utilise et peut émettre de l'énergie radiofréquence et, si non installé et utilisé 

conformément au manuel d'instruction, peut provoquer des interférences 

dans les communications radio. Le fonctionnement de cet équipement dans 

une zone résidentielle est susceptible de provoquer des interférences 

nuisibles, auquel cas l'utilisateur sera tenu de corriger les interférences à 

ses propres frais.

CAUTION

! Any changes or modifications not expressly approved by the 

manufacturer could void the user’s authority to operate the equipment.

ATTENTION

! Les changements ou modifications non expressément 

approuvés par le fabricant peuvent annuler le droit de l'utilisateur à utiliser 

l'équipement.

Figure 3. Authentication window.

Figure 4. Setup IP Address successfully message.

ICES-003 Class A Notice - Avis NMB-003, Classe A This Class A 

digital apparatus complies with Canadian ICES-003. Cet appareil 

numérique de la classe A est conforme à la norme NMB-003 du 

Canada.

Solution

 

WARRANTY

For warranty information, refer to 

http://www.middleatlantic.com/company/about-us.aspx#warranty

Corporate Headquarters

Voice: 973-839-1011 - Fax: 973-839-1976 - International Voice: +1 973-839-8821 - 

Fax: +1 973-839-4982 - www.middleatlantic.com - [email protected]

Middle Atlantic Canada

Voice: 613-836-2501 - Fax: 613-836-2690 - ca.middleatlantic.com - 

[email protected]

Middle Atlantic EMEA Technical Support

Voice: +31 (0) 495 726002 - [email protected] 

Factory Distribution

United States: New Jersey, California, Illinois - Canada: Ontario - The Netherlands: Weert

At Middle Atlantic Products we are always listening. Your comments are welcome.
Middle Atlantic Products is an ISO 9001 and ISO 14001 Registered Company.

Отзывы: