Chapter 3: Using the Web Interface
50
2.
Click the desired sensor (required), and then click Edit Thresholds.
3.
Make changes as desired.
•
To enable any threshold, select the corresponding checkbox.
•
Type a new value in the accompanying text box.
•
Or, use spin controls
to dial in values.
For concepts of thresholds, deassertion The PDU and assertion timeout, see
(on page 50).
4.
Click Save.
Sensor Threshold Settings
This section explains the thresholds settings for a numeric sensor.
Thresholds, Sensor States, and Colors
A numeric sensor has four thresholds: Lower Critical, Lower Warning, Upper Warning and Upper Critical.
The threshold settings determine how many sensor states are available for a certain sensor and the range of each sensor
state. The diagram below shows how each threshold relates to each state.