Part I - Installation

CAUTION:  The  available  gas  pressure  should  be  within  the  limits  shown  in  Table  1  - 
SPECIFICATIONS  section.  Excessive  pressure  may  damage  electric  valves,  regulators 
and manual valves. If the supply pressure exceeds the 14.0″ W.C. maximum, a suitable 
high pressure regulator must be installed between the Main Manual Shut-Off  Valve and 
burner combination valve.

The burner gas supply piping should branch off  from the main line as close to the gas meter as 

possible. Do not connect to the bottom of a horizontal section. Use new black pipe and malleable 
fi ttings free of cutting and threading burrs or defects.

Piping must also comply with your local codes.

To obtain the maximum fi ring rate of the burner, the gas supply piping must be sized to provide a 

minimum pressure of 7.0″ W.C. (Natural) for 400 MBH to the inlet of the combination redundant valve 
when the burner and all other gas utilization equipment are on refer to Table # 3 for 350 MBH and 250 
MBH gas pressure requirements. The main regulator, if equipped, should be mounted upright and in 
a horizontal run of pipe, refer to regulator manufacturer’s installation instructions.

CAUTION: Because it is diffi

  cult to accurately control pressure during supply pipe leak 

testing, it is recommended that all low pressure 1/2 PSIG (14.0″ W.C. max.) components 
be disconnected during testing. Exposing low pressure regulators and valves, including 
manual valves, to pressures over 1/2 PSIG (14.0″ W.C.) will cause damage and void all 
warranties.

III               Piping

BELIMO

BELIMO

MAXIMUM INLET
PRESSURE = 1/2 PSIG

COMBINATION
GAS VALVE

MANIFOLD GAS
PRESSURE TAP

AIR PRESSURE
SWITCH 
(LOCATED INSIDE)

BLOWER MOTOR

DSI ELECTRONIC
CONTROL

COMBUSTION
DAMPER
ACUATOR

GAS VALVE ACTUATOR
WITH SPRING RETURN

LOW FIRE
BYPASS
LINE

LOW FIRE
ORIFICE

Figure 2 - 

Typical Piping Diagram

DANGER: Explosion hazard.

Do not use oxygen for pressure testing.

An explosion could occur during initial start up.

If  the  burner  piping  must  be  rearranged  because  of  space  limitation,  be  sure  to  carry  out  the 

general arrangement shown in Figure 2. Install the combination valve in any position except up-side 
down.

When the burner is installed in the vestibule of jacketed equipment, it is recommended that the 

Automatic  Safety  Shut-Off   Valve  be  left  adjacent  to  the  burner  within  the  vestibule  and  the  Main 
Manual Shut-Off  Valve be installed outside.

Содержание ECONOMITE RE 4400DS HTD

Страница 1: ...are used to identify hazards safety precaution of special notations and have standard meanings throughout this manual They are printed in all capital letters using a bold type face as shown below and...

Страница 2: ...l of the combustion chamber and to permit burner removal or as recommended by the equipment manufacturer CAUTION In no case should the burner tube be allowed to extend into the chamber because high co...

Страница 3: ...D VALVE BK BK Y R NO C NC BURNER OR Y BL W Y BK R NEUTRAL 120 1 60 HOT L1 G L2 2 10 VDC MODULATION INPUT SIGNAL BL R W Y BK Y R 120V INPUT BLOWER MOTOR 120 1 60 MTR GND SCR Y Y BK W BL 24V X BK Y 208V...

Страница 4: ...nd in a horizontal run of pipe refer to regulator manufacturer s installation instructions CAUTION Because it is di cult to accurately control pressure during supply pipe leak testing it is recommende...

Страница 5: ...y shown by 1 3 For higher permissible pressure drops consult your gas supplier Pipe Type Approximate Capacity MBH Size of Gas Pipe Length 10 20 40 75 100 3 4 Natural 200 150 1 Natural 400 275 200 150...

Страница 6: ...vel periodically purge the gas utilization equipment and or chimney as described in step 3 above 4 To make a preliminary setting of the burner input determine the manifold gas pressure required from T...

Страница 7: ...spark and ame rods are made from heat resistant alloys and can be expected to have a long service life They should be routinely inspected however for corrosion or loss of metal _______________________...

Страница 8: ..._________________ Startup instruction for RE 4400DS HTD 1 Set the operating control to o or thermostat below room temperature 2 Turn manual gas cock on 3 Turn burner power on 4 Set operating control t...

Страница 9: ...______________________ Part II Service Figure 4 Valve Train Assembly RE4400DS HTD Low Fire Bypass Line Modulating Butterfly Valve Butterfly Valve Green Handle Spring Return Gas Valve Actuator Combinat...

Страница 10: ...il returns midcointernational com b Protected from shipping damage c Received transportation pre paid at Midco International Inc Return Goods Dept 4140 West Victoria Street Chicago Illinois 60646 6727...

Страница 11: ...eplaced as instructed by the customer Products returned to the customer will be sent shipping charges collect Call factory for information 866 705 0514 Fill out form and fax to 866 580 8700 or copy an...

Страница 12: ...PLACE STAMP HERE FOLD LINE FOLD LINE Midco International Inc 4140 West Victoria Street Chicago Illinois 60646 toll free 866 705 0514 tel 773 604 8700 fax 866 580 8700 web www midcointernational com e...

Отзывы: