D R Y S I R E N
U s e r ´ s a n d i n s t a l l a t i o n m a n u a l
|
63
P a g e 6 3 o f 6 8
V e r s i o n : 0 1 / 2 0 1 8
SW
IM
M
IN
G
P
O
O
L
D
EH
U
M
ID
IF
IE
R
D
R
Y
S
IR
E
N
Insufficient air flow.
DRY SIREN’s evaporator
or air flow is blocked by
dirt, objects, etc.
Please check the DRY SIREN’s ceiling unit
positioning for correct positioning 6.2
APPROPRIATE POSITION OF CEILING UNIT
.
Other
Other
Please call for service.
14.3
Maintenance
At least once a year it is necessary to have the unit checked to maintain its service and sustain
reliability. Following objects/items to be checked:
-
Ceiling unit fixation – threaded bars and nuts holding OK? No crack/damage/bend?...
-
Condensate drain – does it drain OK? Clean of dust? No waving? No leakage?...
-
Copper pipes – connection OK? No leak? Pressures OK?....
Unit is equipped with 24/7 protection system micr. Unless the unit shows error
message or unless manufacturer advises your supplier of an error or seeming malfunction,
the unit is fully operational and working in order.
14.4
Summer shut-down
Some swimming pool users use to shut the dehumidifier for the summer down. This is mainly due to
favorable weather conditions with dry and warm weather. In such case, good air ventilation / natural
air exchange does the job of humidity control for few weeks of the year. Although following rapid
change in weather (e.g. into rainy days) may result in high humidity in your pool.
In this case please make sure that:
1.
Dehumidifier's circuit breaker is off (i.e. dehumidifier does not have any power supply)
2.
Dehumidifier is cleaned of dust, fluff or other dirt that may harden / stiffen its structure during
the shutdown period making it hard to remove afterwards.
3.
Make sure air inlet and outlet are covered properly so no chlorine or other chemicals are not
input into dehumidifier body, especially ventilator bearings. Failing to do so may result in bearings
corrosion and failure of the dehumidifier.
4.
Manufacturer does not suggest any planned shutdown of the system because during shut down
period the humidity is not controlled effectively and automatically.
14.5
Super-chlorination cleaning
Although DRY SIREN is constructed from the most durable and chemically resistant materials,
chlorine is a very aggressive substance. Typical pool air chlorine content is up to 1.0ppm. DRY SIREN
is equipped with special anti-chlorine protections but cannot protect the unit in environment of
higher chlorine than 3.0ppm. When cleaning the pool hall premises by super chlorination please note
that DRY SIREN must be off as chlorine concentrations go beyond warranty 3ppm up to 24ppm
during super chlorination. The unit must be off and ideally covered.