    Installation and user manual                   

Version: 01/2022

 

Model:       DRY 300 METAL / SILVER 

DRY 400 METAL / SILVER 
DRY 500 METAL / SILVER 

 

Содержание DRY 300

Страница 1: ...POOL DEHUMIDIFIER Installation and user manual Version 01 2022 Model DRY 300 METAL SILVER DRY 400 METAL SILVER DRY 500 METAL SILVER...

Страница 2: ...addition to this User manual 1 WASTE DISPOSAL INFORMATION 3 2 SAFETY MEASURES 3 2 1 ELECTRICAL SAFETY 3 2 2 USAGE PRECAUTIONS 4 2 3 HANDLING PRECAUTIONS 5 3 PRODUCT DESCRIPTION 6 3 1 DESCRIPTION OF BA...

Страница 3: ...mming pool smaller swimming pool spa sauna use and alternatively in wash houses dryers and elsewhere See the technical data chart for model suitability for a pool room with a pool area It is necessary...

Страница 4: ...ust openings with clothes towels buckets canoes trees etc Do not install or store heaters near the suction grilles This could cause the dehumidifier to overheat and lead to malfunction or damage Do no...

Страница 5: ...t which may cause mechanical damage to the device Keep in vertical position for 2 hours Do not dry wet towels or swimsuits on the unit and do not put other objects on top of it e g boxes vases with fl...

Страница 6: ...ut minor damage may cause the unit to stop working properly in a short time In this case the unit must be inspected and its further use must be approved by the seller Please notify your reseller or di...

Страница 7: ...th model DRY SILVER 1x 8 Cleaning agent HG model DRY SILVER 1x Additional accessories on request Name code Picture Name code Picture 1 External wireless humidistat and thermostat DRY EASY 300 1x Part...

Страница 8: ...0 or above the capillary on the right side Dry500 see picture 1 5 air filter Installed inside the device 6 Mobile stand 1x Packaged separately 7 fresh air supply More information found in section 3 2...

Страница 9: ...ossible heating water supply from the right left side on request as accessory 6 Possible heating water supply from the back on request as accessory 7 Fresh air supply 100 mm on request as accessory 8...

Страница 10: ...ocated below the condenser which effectively heats the incoming fresh air due to heat recovery The metal fresh air connection is supplied already mounted on the dehumidifier but towards the inside Whe...

Страница 11: ...connection of the sensor is broken off Please control the cable S E Sensor failure The sensor is short circuited Please control the cable The illuminated dot indicates that the display shows the air...

Страница 12: ...ing HUMIDITY TEMPERATURE changing Manufacturer settings Press SET key for 10secs User setting TEMPERATURE changing menu User setting HUMIDITY changing menu TEMP HUMI display changing cycle setting men...

Страница 13: ...5 0 0 M e t a l S i l v e r V01 2022 1 3 Deviation correction and other service settings Press SET key for 10secs Displayed after 10 secs Press SET button shortly Displayed immediately 2 1 TEMPERATURE...

Страница 14: ...e TEMP output delay time setting TEMP output hysteresis type select TEMP output hysteresis setting Temperature sensor correction Setting the device address for communication with the superior system v...

Страница 15: ...g HUMI output delay time setting HUMI output hysteresis type select HUMI output hysteresis setting HUMI sensor correction Sensor heating set Change Change Change Heating enable Heating unenable HUMIDI...

Страница 16: ...troller on demand An external wireless humidistat and the DRY EASY 300 thermostat can be ordered for the pool dehumidifier which is equipped with a built in mechanical humidistat as standard Picture M...

Страница 17: ...midistat the backup humidistat will take over the room humidity control and in this case the dehumidifier will not respond to signals from the DRY EASY 300 remote humidistat Broadcast indication Exter...

Страница 18: ...the outside of it B For TTW version through the wall we recommend pulling the antenna into the pipe in the wall Follow the picture below 4 4 Humidity control by external wired humidistat EBERLE If yo...

Страница 19: ...higher accuracy At the same time the continuous operation of the fan mixes the air in the room better The fan control is set by the installation company according to the user s requirements DRY300 400...

Страница 20: ...e device must be in accordance with the STN 33 2000 7 702 standard It is recommended to place the device outside zones 0 1 and 2 When placing the device in zones 2 or 1 the STN must be observed It is...

Страница 21: ...platforms jumping boards and starting blocks and 2500 mm above the highest surface on which people are expected to be present if the unit is at a distance less than or equal to 1250 mm horizontally f...

Страница 22: ...eated air and this could delay its regulation Also placement above for example a radiator can cause the device to overheat malfunction or be damaged It is also not advisable to place the dehumidifier...

Страница 23: ...e device has a self supporting construction The axis of the mounting holes is 210 mm lower than the upper edge of the device The three mounting holes are 360 mm apart When the bracket is attached the...

Страница 24: ...template on the wall Before installing the Athmoss cleaner all construction work painting tiling heating drainage electricity etc must be completed 2 Using the mounting template and the spirit level...

Страница 25: ...2022 2 5 4 Drill the holes We recommend vacuuming the dust 5 Insert supplied dowels in the holes 0 3 6 Secure console with the supplied or other suitable screws The console must be in a horizontal po...

Страница 26: ...connect the power supply and condensate drain The cover can be removed after loosening 2 screws DRY 300 400 Wave or 3 screws DRY 500 Wave on the bottom part of the device 9 Pull the lower part of the...

Страница 27: ...us have access to the condensate Follow section Condensation drainage when installing the condensate hose 11 Connect he power cord For this purpose there s an adaptor formed on the back plate of the d...

Страница 28: ...collection tray Without active free condensate drainage the dehumidification process will not work Condensation water is drained from the dehumidifier by gravity downwards The condensing tray has the...

Страница 29: ...4 0 0 5 0 0 M e t a l S i l v e r V01 2022 2 9 Proper installation of condense hose Improper installation of condense hose CONDENSATE DRAIN Condensate drain Condensate drain Condensat e drain Bathtub...

Страница 30: ...500 with residual current device RCD with a rated residual current not exceeding 30 mA The main switch of the device must be located outside the pool hall The main switch of the appliance must be bipo...

Страница 31: ...via contactor Electric heating element connection Dehumidifier type El cable El insulation DRY 300 400 500 CYSY 3x 2 5 mm2 16A El connection of wire humidistat and thermostat Model El cable HYG6001 CY...

Страница 32: ...ICAL CONNECTION OF THE DEHUMIDIFIER 230V 50Hz 1f 3x 2 5mm2 CYSY breaker 16A type C circuit breaker 30mA Black box from the SIDE of the electrobox MAIN ELECTRICAL CONNECTION OF THE DEHUMIDIFIER 230V 50...

Страница 33: ...LECTRICAL CONNECTION OF THE DEHUMIDIFIER 230V 50Hz 1f 3x 2 5mm2 CYSY breaker 16A type C circuit breaker 30mA POTENCIAL FREE CONTACT POTENTIAL CONTACT NO opened normally If the air is heated then C clo...

Страница 34: ...re the 2 wheels on the front of the mobile stand against movement according to the following picture Mobile Stand Your dehumidifier can be used on a mobile stand Although the dehumidifier is primarily...

Страница 35: ...els can only be unlocked for the least possible time required for actual handling from place to place of Athmoss In all other cases the wheels must be locked 3 If the dehumidifier is ordered together...

Страница 36: ...lation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 3 6 Fixed stand Installation The dehumidifier is designed for placement on a surface with a height deviation of max 0 5 1...

Страница 37: ...this product If your dehumidifier is equipped with a hot water insert and your dehumidifier is designed without a remote wireless humidistat with a thermostat there is a risk of the dehumidifier overh...

Страница 38: ...r Brass CW 617 N 8 Spring Steel 9 Ring Stainless steel 10 Piston Stainless steel 11 Spring Steel 12 Support Stainless steel 13 Insulation NBR 14 Spring Steel 15 Cover Stainless steel 16 Membrane NBR 1...

Страница 39: ...the top of the dehumidifier during operation of the heater It is also forbidden for children to play with or with the dehumidifier Please note that children should be supervised by an adult at all tim...

Страница 40: ...for 2 or 3 defrost cycles to take place in succession 5 8 Air filter len na vy iadanie Your dehumidifier can be equipped with an air filter on request The air filter traps dust and other mechanical pa...

Страница 41: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 4 1 Dehumidifier 4 x screws Air vent Air filter...

Страница 42: ...OF DEHUMIDIFIER 230V 50Hz 1f 3x 2 5mm2 CYSY breaker 16A type C circuit breaker 30mA PERIPHREAL CONTROL 230V 50Hz 1f 3x 0 5 1mm2 CYSY Separate contactor with separate phase The contactor is supplied by...

Страница 43: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 4 3 Electric blinds SERVO d100 piping Fresh air adapter turn out of the unit Dehumidifier Wall...

Страница 44: ...ing starting current A 3 1 15 3 1 15 4 5 15 El insulation type C A 10 10 16 Power cord mm2 CYSY 3C x 1 5 CYSY 3C x 1 5 CYSY 3C x 2 5 Condensing pipe outer diameter mm d 20 d 20 d 20 Net dimensions wid...

Страница 45: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 4 5 6 1 1 EL CONNECTION SCHEME DRY 300 400 BASIC CONNECTION DRY 300 1...

Страница 46: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 4 6...

Страница 47: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 4 7...

Страница 48: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 4 8...

Страница 49: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 4 9 6 1 2 EL CONNECTION SCHEME DRY 300 400 ADVANCED CONNECTION DRY 300 2...

Страница 50: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 5 0...

Страница 51: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 5 1...

Страница 52: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 5 2 6 1 3 EL CONNECTION SCHEME DRY 500 BASIC CONNECTION DRY 500 1...

Страница 53: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 5 3...

Страница 54: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 5 4...

Страница 55: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 5 5...

Страница 56: ...and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 5 6 Note A1 phase A2 zero for control of cooperating elements for fresh outdoor air supply louver slats with servo drive and wall...

Страница 57: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 5 7 6 1 4 EL CONNECTION SCHEME DRY 500 ADVANCED CONNECTION DRY 500 2...

Страница 58: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 5 8...

Страница 59: ...r at least once a month to prevent the fan grease from solidifying after a few months the fan would not have to start at all 6 The manufacturer points out that during decommissioning of the dehumidifi...

Страница 60: ...0 ppm When cleaning the pool hall with superchlorination it must be remembered that the DRY300 400 500 must be switched off as the chlorine concentration during superchlorination reaches up to 24 ppm...

Страница 61: ...er was used incorrectly other than as described in this manual or in violation of this user manual resp against the safety precautions listed in this manual 2 The dehumidifier has been installed incor...

Страница 62: ...8 1 0 Maximum copper content ppm max 2 Aquamatic lone cleaner ppm max 2 Tarn clean cleaner ppm max 2 Sherwood cleaner ppm max 2 Tab Permitted chemical value TRANSPORTATION The dehumidifier must only b...

Страница 63: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 6 3...

Страница 64: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 6 4...

Страница 65: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 6 5 Notes...

Страница 66: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 6 6 Notes...

Страница 67: ...Installation and user manual D R Y 3 0 0 4 0 0 5 0 0 M e t a l S i l v e r V01 2022 6 7 Notes...

Страница 68: ...l v e r V01 2022 6 8 Manufacturer MICROWELL spol s r o SNP 2018 42 927 01 a a Slovakia tel 421 31 770 7082 e mail microwell microwell sk w w w m i c r o w e l l e u Made in EUROPEAN UNION SLOVAK REPU...