MICROWATT DUNGS DMV 525 Скачать руководство пользователя страница 3

3 … 3

MC • Karl Dungs

, Inc.

 • 

Vent Line A

dapter f

or DMV • Edition 2016.02 • P/N 261432

Recommended Procedure to Pipe the Vent Line Adapter

•  Use new, properly reamed and threaded pipe.

•  Apply good quality pipe sealant, putting a moderate amount 

on the male threads only.

•  Do not overtighten the pipe. Follow the maximum torque 

values listed below.

•  After installation is completed, using a soapy solution leak 

test the vent line connection to confirm that no leakage 

occurs. The presence of bubbles indicates a leak.

The Vent Line must be properly installed . The 

use of a normally open vent valve is required . 

See installation manual for supply gas line 

connections and operation of the DMV valve .

Not a supply gas connection, Vent Line con-

nection ONLY .

Vent Line must terminate at a safe location as 

determined by the authority having jurisdiction .

Piping must comply with applicable local and 

national codes and ordinances, including the 

National Fuel Gas Code ANSI Z223 .1/NFPA 54 .

Vent Line Connection

18

19

Chrome Steel  

  Made in Germany

[

Ib-in

]

To an approved location

Recommended Torque

System Accessories

1“ 

NPT 

pipe

750

lb-in

Karl Dungs GmbH & Co . KG

P .O . Box 12 29

D-73602 Schorndorf, Germany

Phone  +49 (0)7181-804-0

Fax  +49 (0)7181-804-166

e-mail info@dungs .com

Internet http://www .dungs .com

Karl Dungs, Inc .

3890 Pheasant Ridge Drive NE

Suite 150

Blaine, MN 55449, U .S .A .

Phone 763 582-1700

Fax  763 582-1799

e-mail info@karldungsusa .com

Internet http://www .dungs .com/usa/

Normally

opened 

vent vale