MPM4760 pressure transmitter
:
Measure range
:
-100kPa…0kPa~10kPa…100MPa
Overpressure:1.5 times FS or 110MPa(Min. value is valid)
MDM4760 differential pressure transmitter
:
Measure range
:
0kPa~35kPa…3.5MPa
+overpressure
:
2 times FS
-overpressure
:
FS
Max.static pressure
:
≤20MPa
Total Accuracy
①
:±0.25%FS
Stability: ±0.2%FS/YEAR
Compensated Temp.: -10
℃
~70
℃
Working Temp: -30
℃
~80
℃
Storage Temp: -40
℃
~85
℃
Power Supply: 8V~28V DC or Battery supply
Output signal Standard: analog 4mA~20mA DC, 2-wire; digital RS485
interface
Battery Supply: None
Battery supply with RS485 output: digital RS485 interface
RS485 interface: ASCII agreement or MODBUS RTU, BUS with 99
transmitters.
Load Resistance (Ω)
:(
U-8V
)
/0.02A
U is power voltage
(
standard
)
Display Range
:
-19999~19999 LCD Display
Insulation: 50V, 100M
Shock: 20g, 20Hz~5000Hz
Impact: 20g, 11ms
Protection: IP65