ENGLISH

Connecting to a network

On delivery, Access™ BMU is connected to a
factory set network.

The charging parameters and other settings in
Access™ BMU must be set correctly for the
battery in question.
The settings are made with the Access™ Service
tool, which must be connected to the appropriate
Access™ BMU.
Some settings for Access™ BMU can also be
made using the menu system on the Access™
battery charger when they are connected to each
other.

Caution

Incorrectly set charging parameters can damage
the battery.

Connect to the existing
network with the associated
Access™ Battery charger

1. Set the charger’s charging parameter

Source

in the menu

Service/Charging parameter

to

BMU

or another BMU option.

2. Activate

Join enable

on the charger.

3. Connect the charger to the battery that has the

relevant Access™ BMU fitted.

4. If charging starts within 1 minute the Access™

BMU has succeeded in connecting to the
network.
Battery ID is shown on Access™ the battery
charger’s display.

Connect to an existing (not
factory set) network only with
other Access™ BMU units

The Access™ BMU that is to be connected to the
network must be reset to the factory set network.
This is to make

Activate connection

possible.

See

Resetting the factory set network.

.

Activate

Join enable

on the Access™ BMU that is

connected to the correct network:

1. Hold a strong magnet over the magnetic switch

.

The network status indicator

starts to flash

and the unit has

Join enable

activated.

Activate

Activate connection

on the Access™

BMU to be connected on the network:

2

Hold a strong magnet over the magnetic switch

.

The network status indicator

starts to flash

and the unit searches for and connects to the
network that has

Join enable

activated.

Connect new Access™ BMU
units to the factory set network

New Access BMU units connect directly to the
factory set network during installation.

Start and connect to the new
specific network with the
Access™ Service tool

The Access™ BMU that is to be connected to the
network must be reset to the factory set network.
This is to make

Activate connection

possible.

See

Resetting the factory set network.

.

1. Start the Access™ Service tool.

2. Select

Start a network

.

3. Activate

Join enable

.

Activate

Activate connection

on the Access™

BMU to be connected on the network:

4

Hold a strong magnet over the magnetic switch

.

The network status indicator

starts to flash

and the unit searches for and connects to the
network that has

Join enable

activated.

5

A new network has now been started where
only the current Access™ BMU and Access™
Service tool are connected. Additional units can
be added to this network.

Resetting the factory set
network.

1. Hold a strong magnet over the magnetic switch

on the battery monitoring unit’s control

panel.

The network status indicator

starts flashing.

2. Hold the magnet over the magnetic switch and

restart the battery monitoring unit by
disconnecting and then connecting the red

6

Содержание Access BMU PRO UL

Страница 1: ...Access BMU Battery Monitoring Unit BMU PRO UL WET Soldered EN Instruction for use 3 Figures 9 Approvals 10 Doc 09912018 rev 5 Print PN 6515062...

Страница 2: ......

Страница 3: ...he rear of the unit Safety Warning information Hazardous situations and precautionary measures are presented in the text as set out below Warning Situations that may result in severe personal injury o...

Страница 4: ...y Rinse the eye immediately and thoroughly for at least 10 minutes seek medical attention Wear protective equipment such as safety glasses and gloves to avoid contact with the electrolyte Note Install...

Страница 5: ...3 cells from the current sensor s connection point in order for the sensor to work correctly 6 Drill a 12 mm 0 472 inch hole in the top of the battery cell for the electrolyte level and battery temper...

Страница 6: ...etic switch The network status indicator starts to flash and the unit has Join enable activated Activate Activate connection on the Access BMU to be connected on the network 2 Hold a strong magnet ove...

Страница 7: ...cted to the battery s negative terminal d Check the set parameters for the current sensor position and indication level through Accessthe Service tool Flashes Time and date set incorrectly Set the tim...

Страница 8: ...Do not touch uninsulated battery terminals connections or other live parts Contact a service technician Warning Access BMU must not be cleaned with a high pressure washer 1 Check that the battery mon...

Страница 9: ...Figures Fig 1 Access BMU installed on the battery Fig 2 Access BMU Fig 3 Battery cross section 4 10 8 7 9 3 2 1 5 6 00069 4 2 1 3 00053 9 1 2 3 4 5 6 00055...

Страница 10: ...operated keeping the radiator at least 20 cm or more away from person s body excluding extremities hands wrists feet and ankles Avertissement Les changements modifications non approuv s par le parti r...

Страница 11: ...ty and Radio spectrum Matters EMR ElectroMagnetic Compatibility EMC and standard for radio equipment and services Part 3 Specific conditions for Short Range Devices SRD operating on frequencies betwee...

Отзывы: