Dinel, s.r.o.      ULM–70

   

S T A R T I N G

Dinel

®

11 .  OPERATION AND SETTING

Set the level meter using 3 buttons placed on the display module 

(see Chapter Set-up elements). After 5 min. of inactivity, the level 

meter automatically returns back to the measurement mode. If the 

password is active, the level meter will be also locked. The val-

ues that have not been confirmed using the button 

 will not be 

saved! After the meter is locked, you cannot change the setting! 

When you attempt to edit, the words "NO PASSWORD" will appear 

on the display. How to unlock the level meter is given on page 16. 

After connection of the supply voltage to the level meter the display 

shows the logo "Dinel" and the text "Starting" (approx. 15 s). Then, 

the level meter goes to the measuring mode and the display shows 

the current measured value.

11 .1 .  BASIC CONFIGURATION

MIN LEVEL and MAX LEVEL

You can freely define the 

minimum / maximum distance from the front surface of the 

level meter

 (item "LEVEL"for currents 4 / 20 mA). The "DISPLAY" is intended to set the value 

displayed on the display. Setting the units is done in the "UNITS".

If in the bottom of the display appears (when entering the values) the   inscription "OUT OF LIM

-

ITS", the value specified for the item "LEVEL" is outside the measuring range of the level meter. 

If the inscription "SPAN TOO SMALL" is shown, it must be specified a larger span between Min 

and Max values. For more information, see chapter "Specifications".

The decimal point position of the item 'LEVEL' is firmly set (according to the selected units), in 

the item "DISPLAY" it is freely adjustable

After the first start of the level meter it is necessary to perform the 

basic configuration (setting of the measuring range, choice of units 

and possibly damping). The settings are accessible in the basic 

menu by pressing 

the "BASIC SETTINGS". 

U N I T S

L E V E L :

m m

D I S P L A Y :

%

T E M P E R A T U R E

°C

M I N   L E V E L

M A X   L E V E L

U N I T S

D A M P I N G

S E N S I T I V I T Y

T E A C H I N G

M I N

ACTUAL LEVEL

0 2 8 7 0 m m

O U T P U T :

0 4 . 0 0 m A

L E V E L :

0 6 0 0 0

m m

D I S P L A Y :

0 0 0 0 0 %

M A X

ACTUAL LEVEL

0 2 8 7 0 m m

O U T P U T :

2 0 . 0 0 m A

L E V E L :

0 0 2 5 0

m m

D I S P L A Y :

0 0 1 0 0 %

ACTUAL LEVEL: Actual distance to 

level

OUTPUT: current 4 mA / 20 mA
LEVEL: Definition of the min / max 

level

DISPLAY: The value showed on the 

display

M I N   L E V E L

M A X   L E V E L

U N I T S

D A M P I N G

S E N S I T I V I T Y

T E A C H I N G

B A S I C   S E T T I N G S

S E R V I C E

D I A G N O S T I C

C L O N E   S E T T I N G S

P A S S W O R D

L A N G U A G E

I N F O

Содержание Dinel ULM-70

Страница 1: ...ished in this manual before the first use of the level meter Keep the manual at a safe place The manufacturer reserves the right to implement changes without prior notice INSTRUCTION MANUAL ultrasonic...

Страница 2: ......

Страница 3: ...he level meter with current output and MGU unit 13 8 4 Wiring diagram of the level meter with Modbus RS485 and MGU unit 13 8 5 Wiring diagram of the level meter with Modbus RS485 and PDU unit 13 9 Set...

Страница 4: ...vessels sumps reservoirs and open channels In case the level of bulk solid materials is measured the meas urement range is reduced The level meters can continuously measure levels of bulk solid ma ter...

Страница 5: ...70_ 02 Pg11 cable gland Ground terminal variant ULM 70 with protective conductor ULM 70_ 06 ULM 70_ 20 ULM 70_ 10 This procedure includes the following three steps INSTALLATION ELECTRIC CONNECTION SE...

Страница 6: ...essary to install the level meter so that the bin level cannot interfere with the dead zone when filled up to the maximum If the measured level in terferes with the dead zone the level meter will not...

Страница 7: ...meter installation outside the influence of filling In case the level of bulk solids is measured the measurement range is reduced Due to absorption of acoustic waves by a bulk me dium shortening of th...

Страница 8: ...level meter Fig 9 For such cases it is necessary to set up SENSITIV ITY mode to high or contact the manufacturer if need In case of a thin layer of foam it is also possible to use the directional hor...

Страница 9: ...o prevent penetration of humidity Then the rain and condensing water can flow off freely The cable bushing and connector have to be sufficiently tightened to prevent penetration of humidity To lower t...

Страница 10: ...e level meter with Modbus is involved as a terminal for RS 485 we recommend to avoid reflections on the line to connect 120 termi nation resistor This is done by moving a small lever of the switch mar...

Страница 11: ...14 15 R1 3 4 optional ACTIVE current output R2 n c n c optional optional Power supply depending on version 1 2 24V 10 11 12 13 14 15 3 4 OC1 OC2 OC1 OC4 Umax 30V DC Imax 30mA Pmax 100mW OC3 OC4 option...

Страница 12: ...10 Imax 100 mA PE n c PDU 420 W 230V input 4 20 mA Connection of PDU 420 W is valid for firmware version 6 00 or higher The older ver sions up to version 5 99 the terminal 9 of the IRU unit is connect...

Страница 13: ...als description OC type outputs 11 GND DATA DATA RS 485 Uo 24V 5 10 Imax 100mA 1 2 5 6 7 8 9 10 11 12 13 14 15 3 4 31 32 33 34 35 OC1 OC2 OC1 OC4 Umax 30V DC Imax 30mA Pmax 100mW OC3 OC4 optional opti...

Страница 14: ...ND MGU UNIT 12 13 14 18 19 A B _ S RS 485 Master 24V DC Imax 120 mA A YE B GN 0V WH U BN Cab Sh ULM 70N _ _ _ M A YE B GN 0V WH U BN Cab Sh MGU 800 without additional modules 8 4 WIRING DIAGRAM OF THE...

Страница 15: ...ntly TEACHING mode activation Symbol E 1 Lighting intermittently correct echo receiving of the reflected signal from the measured surface level Symbol 1 Lighting permanently level meter is locked agai...

Страница 16: ...ITS If in the bottom of the display appears when entering the values the inscription OUT OF LIM ITS the value specified for the item LEVEL is outside the measuring range of the level meter If the insc...

Страница 17: ...ssing the and button make the set tings of individual items 3 By pressing button save the data By next presses of the button leave the menu The level meter returns to measurement mode 1 To enter to th...

Страница 18: ...wn enter a value rather lower in the tolerance field as shown in Fig 19 3 After entering the SET LEVEL DISTANCE by pressing button the system starts teaching false reflection mapping During the mappin...

Страница 19: ...AR T FA CTORY DE FAULT R ESET MEDIUM TEMPERATURE YES 20 C Inactive compensation initial state the word NO appears on the display See the UNITS menu for tempera ture unit selection C or F After start o...

Страница 20: ...LT ARE YOU SURE FACTORY DEFAULT RUNNING FACTORY DEFAULT DONE PRESS ESC TO EXIT RESET ARE YOU SURE During the restart process RUN NING will be displayed Then the level meter will be automatically turne...

Страница 21: ...ng The CLONE SETTINGS mode transfers all data excluding setting of the Teaching and HART BASIC SETTINGS SERVICE DIAGNOSTIC CLONE SETTINGS PASSWORD INFO CLONE SETTINGS NOW CLONING CL ONE SE TTING S SEN...

Страница 22: ...e words NO PASSWORD will be displayed 2 Now you can edit the password The actual edited item is displayed inversely Press the but ton to move to the next position clockwise direction button serves to...

Страница 23: ...2 Protocol HART Universalcommunicationinterfacefordatacommunicationofperipheraldeviceswiththelevel meter Data transmission runs through the same line as the 4 20mA current loop without impact on analo...

Страница 24: ...onductor Set up elements D basic version with display L without display metal lid Performance N Normal usable in non explosive areas only Xi Ex proof suitable for explosive areas Maximum reach 15 Acce...

Страница 25: ...al conditions for safe use ULM 70Xi The device is designed for connection to the isolating repeater IRU 420 When the other ap proved supply unit is used whose output parameters satisfy above mentioned...

Страница 26: ...t 30 70 C a II 1 2 G Ex ia IIB T5 Ga Gb P 0 99 W I 132 mA i i C 370 nF L 0 9 mH i i FTZ 09 ATEX 0277X 1026 I 4 20 mA ULM 70Xi 06 G I B D IP67 1026 ULM 70Xi 10 G I B D IP67 1026 ULM 70Xi 20 F I B D IP6...

Страница 27: ...B D ULM 70N __ _ M _ _ Varianty zna en 01 02 06 10 20 D L B H G F Labels for type of ULM 70N _ _ _ M _ _ Example of label for type of ULM 70N 10 G M B D Symbol of producer logo Dinel Internet address...

Страница 28: ...T T I N G S S E R V I C E D I A G N O S T I C C L O N E S E T T I N G S P A S S W O R D L A N G U A G E I N F O M I N L E V E L M A X L E V E L U N I T S D A M P I N G S E N S I T I V I T Y T E A C H...

Страница 29: ...e ULM 70_ 02 06 ULM 70_ 10 20 30 70 C 30 60 C Short time temperature stress resistance 90 C 1 hour Max operation overpressure on transmission surface 0 1 MPa Sensitivity 3 steps low medium high Dampin...

Страница 30: ...module Display type Matrix OLED Resolution 128 x 64 pixel Character height Number of digits measured value 9 mm 5 Digits Display colour Yellow Buttons Membrane switch panel Ambient temperature range 3...

Страница 31: ...l indicates particularly important characteristics of the device Note This symbol indicates helpful additional information 21 Packaging shipping and storage The device DLM 35 is packaged in a polyethy...

Страница 32: ...002 003 e mail sale dinel cz www dinel cz The lastest version of this instruction manual can be found at www dinel cz Version 06 2019 This project was realised under financial support from the funds o...

Отзывы: