MC30-BC
Doc. N°
MO-0365-ING
Copyright 2008
FW 980.09.01.X
Date
15.06.2022
Rev.
1
Pag.
31
of
37
Display
Description
Setting Range
Step
Function
Type
Variable
Default
Value
Unit
IoH
(3F51N)
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
Options
→
BI
Disable
Operation controlled by Blocking Digital Input
Enable/Disable
-
Trg
Enable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
IoH
2.00
Ion
Trip level of Earth Fault protection
0.01
–
9.99
0.01
Timers
→
tIoH
0.10
s
Trip time delay
0.05
–
60.00
0.01
BF
(F51BF)
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
Options
→
TrR
Relay1
Output relay operated on BF tripping
Relay1- Relay2
Relay3- Relay4
-
TripLev
→
No Parameters
Timers
→
tBF
0.20
s
Time delay for Breaker Failure alarm
0.05
–
0.75
0.01
BC
FuncEnab
→
Disable
Enable of the protection function
Enable/Disable
-
Options
→
Trg
Enable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
BC>
10.00
%
Ratio between inverse sequence current and direct
sequence current.
10
–
100
%
Timers
→
tBC>
0.20
s
Trip time delay
0.05 - 60
s
F86
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
Options
→
1I>
Enable
Block first overcurrent element
Enable/Disable
-
2I>
Enable
Block second overcurrent element
Enable/Disable
-
IH
Enable
Block third overcurrent element
Enable/Disable
-
1Io
Enable
Block first earth fault element
Enable/Disable
-
2Io
Enable
Block second earth fault element
Enable/Disable
-
IoH
Enable
Block third earth fault element
Enable/Disable
-
T>
Enable
Block Thermal Image element
Enable/Disable
-
BC
Enable
Block Broken Conductor element
Enable/Disable
-
IRF
Enable
Block Internal Relay Fault
Enable/Disable
-
TripLev
→
No Parameters
Timers
→
No Parameters
S Sel
FuncEnab
→
Disable
Enable of the protection function
Enable/Disable
-
Options
→
Md
HourSE
Ratio between inverse sequence current and direct
sequence current.
HourSE
–
InputSE
-
No Parameters
TripLev
→
No Parameters
Timers
→
No Parameters
IRF
FuncEnab
→
No Parameters
Options
→
Opl
NoTrip
Operation of output Relays on detection of
Internal Relay Fault
NoTrip
–
Trip
-
No Parameters
TripLev
→
No Parameters
Timers
→
No Parameters
Osc
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
Options
→
Trg
Trip
Trigger operation mode
Disable
Start
Trip
Ext.Inp
-
TripLev
→
No Parameters
Timers
→
tPre
0.30
Recording time before Trigger
0.10
–
0.50
0.1
→
tPost
0.30
Recording time after Trigger
0.10
–
1.50
0.1
CBMng
FuncEnab
→
Options
→
TripLev
→
No Parameters
Timers
→
tcmd
0.10
C/B closing output command duration
0.10
–
5.00
0.1
→
tC
0.10
Maximum admissible delay for detection of status
signal after C/B operation.
0.10
–
5.00
0.1
Comm
FuncEnab
→
No Parameters
Options
→
LBd
9600
Local Baud Rate
(Front panel RS232 communication speed)
9600 - 19200
38400 - 57600
-
RBd
9600
Remote Baud Rate (Rear panel terminal blocks
RS485 communication speed)
9600 - 19200
-
Mod
8,n,1
Remote mode (communication parameters)
Note
: any change of this setting became valid at
the next power on
8,n,1
8,o,1
8,e,1
-
RPr
Modbus
Remote Protocol
Iec103-Modbus
-
TripLev
→
No Parameters
Timers
→
No Parameters
LCD
FuncEnab
→
No Parameters
Options
→
Key
BeepON
Buzzer “Beep” on operation of Keyboard buttons.
BeepON-
BeepOFF
-
BkL
Auto
LCD Backlight continuously “ON” or
switched-on
Automatically on operation of Keyboard buttons.
Auto - ON
-
TripLev
→
No Parameters
Timers
→
No Parameters
Settings can also be programmed via the serial communication ports.