10. Measure
Real time values as measured during the normal operation.
1
•
Press “
Menu
” for access to the main menu with icons.
2
•
Select “
Measure
” icon with pushbutton
“
Increase
” or “
Decrease
”.
•
Press “
Select
” for access.
3
•
Scroll the menu “
Measure
”
with pushbutton
“
Increase
” or
“
Decrease
” to display
the measurement.
•
Press “
Exit
” to go to the main menu.
Imx
(0
÷
99999)
A
Largest of the 3 phase-currents (Ia,Ib,Ic)
Ia
(0
÷
99999)
A
RMS value phase A current
Ib
(0
÷
99999)
A
RMS value phase B current
Ic
(0
÷
99999)
A
RMS value phase C current
Io
(0
÷
99999)
A
RMS value of Zero Sequence Current
I1
(0
÷
99999)
In
Positive sequence current
I2
(0
÷
99999)
In
Negative Sequence current
Tem
(0
÷
99999)
%T
Thermal status as % of the full load continuous operation temperature Tn
tst
(0
÷
99999)
s
Motor starting time
Ist
(0
÷
99999)
A
Max current during motor starting