• Midspan must be connected using a grounded power cord, as defined in 

1.5.3  Power Cord

.

• This ITE device must be connected to PoE (power supply over Ethernet) networks only, without routing to other

networks.

• The power cord must not be attached to the surface of the building or pass-through walls, ceilings, floors, and

similar openings in the building structure.

• Steps must be taken to prevent physical damage to the power cord, including proper routing.
• This product relies on building installation for short-circuit (over-current) protection. Use only a fuse or circuit

breaker not higher than 15 A for 120 V

AC

 (U.S.) or 10 A for 230 V

AC

 (international).

• All wiring and connections must conform to NFPA 70 (NEC).
• Do not work on the system or connect/disconnect cables during lightning storms.
• A voltage mismatch can damage the equipment and can pose a fire hazard. If voltage indicated on the label is

different from the power outlet voltage, do not connect Midspan to this outlet.

• For shelf-mounted equipment, verify that surface is stable and strong enough to support the equipment. Do not

stack more than 

four

 Midspan units.

• When disposing this product, follow all local laws and regulations.

Data

 and 

Data and Power

 ports of the Midspan are shielded RJ45 data sockets. They cannot be used as Plain

Old Telephone Service (POTS) sockets. Only connect RJ45 data connectors to these sockets.

• Associated Ethernet wiring must be limited to the inside of the building.

1.5.3 

Power Cord

Power cord replacement must meet the local requirements.

• To ensure a reliable connection to an AC mains supply, equipment provides an appliance IEC60320 inlet to

connect a detachable power supply cord.

• Power socket outlet must be located near Midspan and easily accessible.

Note: 

 The only way to power off the unit is to disconnect the power cord from the outlet.

• This unit operates under Safety Extra Low Voltage (SELV) conditions, according to IEC/EN60950-1 or ES1

according to IEC/EN 62368-1.
Conditions are maintained only if the equipment to which the unit is connected also operates under SELV/ES1
conditions.

1.5.4 

Country-Wise Power Cord Specifications

U.S.A. and Canada

• Cord must be UL-approved or CSA certified.
• Minimum specification for flexible cord is:

– No. 18 AWG
– Type SV or SJ
– Three-conductors

• Cord set must have a rated current capacity of at least 13A for 9024G/ACDC/M/F

and PD-9024G/AC/F; and 10A for PD- 9024G/ACDC/M, PD-9024G/AC, PD-9012G/
ACDC/M

PD-9012G/AC, PD-9006G/ACDC/M

and PD-9006G/AC.

• The attachment plug must be an earth-grounding type with a NEMA 5-15P (15 A, 125

V) or NEMA 6-15P (15 A, 250 V) configuration.

Denmark

Supply plug must comply with section 107-2-D1, standard DK2-1a or DK2-5a.

Switzerland

Supply plug must comply with SEV/ASE 1011.

France and Peru

IT supplies cannot power this unit. If your supplies are an IT type, unit must be powered by
230 V (2P+T) via an isolation transformer with a 1:1 ratio, and with secondary connection
point labeled Neutral and connected directly to the ground.

U.K

PoE Midspan is covered by General Approval NS/G/12345/J/100003, for indirect
connection to a public telecommunications system.

 PD-90XXG

Standards and Safety Guidelines

©

 2021 Microchip Technology Inc.

and its subsidiaries

 User Guide

DS50003153B-page 5

Содержание PD-90 G Series

Страница 1: ...r mode according to the new PoE standard IEEE 802 3at DC power is supplied over the spare pairs of wires within a cable 4 5 and 7 8 to terminal units PoE Midspan normally powers devices that are PoE e...

Страница 2: ...g Kit Contents 10 4 3 Rack Mounting Brackets 11 4 4 Installation Factors 11 4 5 Connecting Ethernet Cables 11 4 6 Connecting Power Cables 11 4 7 Powering Up the Unit 12 5 Troubleshooting 13 5 1 Prelim...

Страница 3: ...tomer Support 24 Microchip Devices Code Protection Feature 24 Legal Notice 25 Trademarks 25 Quality Management System 26 Worldwide Sales and Service 27 PD 90XXG 2021 Microchip Technology Inc and its s...

Страница 4: ...ard Approvals Microchip meets the following safety standards UL IEC EN 62368 1 Consult Microchip for a complete list of safety certifications 1 4 CE Marking CE marking on this product indicates that t...

Страница 5: ...ments To ensure a reliable connection to an AC mains supply equipment provides an appliance IEC60320 inlet to connect a detachable power supply cord Power socket outlet must be located near Midspan an...

Страница 6: ...ure du b timent Des mesures doivent tre prises pour viter tout dommage physique au cordon d alimentation y compris un acheminement appropri Ce produit d pend de l installation lectrique de l immeuble...

Страница 7: ...imum distance from Ethernet switch must not exceed 100 meters 328 ft Power over Ethernet Midspan is guaranteed to work only within this distance as specified in IEEE 802 3at standard Figure 3 1 Front...

Страница 8: ...r Port Load Conditions Port Voltage Off Inactive load or unplugged port Power to port is disconnected No DC voltage present on port output lines Green Active load is plugged in and complies with norma...

Страница 9: ...ed units 8 data bits no parity and 1 stop bit Figure 3 2 Connecting to Midspan 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 RJ IN RJ OUT Ethernet Switch PD RJ45 RJ45 Data Midspan Ch...

Страница 10: ...lations require Midspan to be rack mounted Figure 4 1 Typical Installation 4 2 Verifying Kit Contents Unpack kit and verify that the following items are included PoE Midspan Mounting brackets for 19 i...

Страница 11: ...verloading Consider the connection of the equipment to a supply circuit and the effect overloading of the circuits might have on over current protection and supply wiring Appropriate consideration of...

Страница 12: ...t POST which takes less than 10 seconds During POST all ports are disabled and indicators illuminate in the following sequence Port indicators and power indicators illuminate in green Power indicator...

Страница 13: ...d Midspan did not detect a PD 2 Verify PD is designed for PoE operation 3 Verify you are using a standard Category 5 5e 6 straight wired cable with four pairs 4 If an external power splitter is in use...

Страница 14: ...Specifications for PD 9024G ACDC M Parameter Value AC Input Voltage 100 to 240 VAC at 50 60 Hz Input Current 100 VAC Input Current 240 VAC 12 A max 6 A max Nominal Output Voltage 50 to 57 VDC Total O...

Страница 15: ...r PD 9024G ACDC M PD 9012G ACDC M and PD 9006G ACDC M Parameter Value DC Input Rated Voltage 53 57 VDC Input DC Maximum Current 20 A PD 90XXG Specifications 2021 Microchip Technology Inc and its subsi...

Страница 16: ...her details refer to Microchip s PowerView Pro Web Manager User Guide Figure 7 1 Management Deployment PowerView Pro provides a number of unique features for Midspan management Remote Web Management o...

Страница 17: ...continue to operate without any effect on the connected PDs Power redundancy mode is available in the following midspans PD 9024G ACDC M F PD 9024G ACDC M PD 9012G ACDC M PD 9006G ACDC M PD 9524G ACDC...

Страница 18: ...9012G ACDC M 8 3 Connectors Power backup and power redundancy connectors are located on the back panel of the Midspan PD 90xxG power backup and power redundancy have two connectors as shown in the fo...

Страница 19: ...ack wires and one yellow green wire as shown in Figure 8 2 4 Connect COM cable 5 Connect Midspans to AC outlet 6 Verify Power Indicator LED is ON Green LED Note When connecting a midspan to midspan co...

Страница 20: ...us field shows both internal and external power supply statuses green indication for OK and red indication for Fail Figure 8 3 PD 90XXG View Status in NMS Note Midspan provides another power fail indi...

Страница 21: ...Figure 8 4 PD 90XXG Front Panel LED Indication PD 90XXG Power Backup and Power Redundancy Connection 2021 Microchip Technology Inc and its subsidiaries User Guide DS50003153B page 21...

Страница 22: ...blems while installing or using this product visit the Microchip website at www microchip com support or call USA Canada 1 877 480 2323 PD 90XXG Technical Support 2021 Microchip Technology Inc and its...

Страница 23: ...mation en mati re de s curit section Updated Figure 3 2 Updated dimension and Midspans PD Part numbers in 6 1 Physical Specifications A 04 2021 Initial Revision PD 90XXG Revision History 2021 Microchi...

Страница 24: ...listing of sales offices and locations is included in this document Technical support is available through the website at www microchip com support Microchip Devices Code Protection Feature Note the f...

Страница 25: ...esigner QTouch SAM BA SenGenuity SpyNIC SST SST Logo SuperFlash Symmetricom SyncServer Tachyon TimeSource tinyAVR UNI O Vectron and XMEGA are registered trademarks of Microchip Technology Incorporated...

Страница 26: ...nagement System For information regarding Microchip s Quality Management Systems please visit www microchip com quality PD 90XXG 2021 Microchip Technology Inc and its subsidiaries User Guide DS5000315...

Страница 27: ...men Tel 86 592 2388138 China Zhuhai Tel 86 756 3210040 India Bangalore Tel 91 80 3090 4444 India New Delhi Tel 91 11 4160 8631 India Pune Tel 91 20 4121 0141 Japan Osaka Tel 81 6 6152 7160 Japan Tokyo...

Отзывы: