• Midspan must be connected using a grounded power cord, as defined in
• This ITE device must be connected to PoE (power supply over Ethernet) networks only, without routing to other
networks.
• The power cord must not be attached to the surface of the building or pass-through walls, ceilings, floors, and
similar openings in the building structure.
• Steps must be taken to prevent physical damage to the power cord, including proper routing.
• This product relies on building installation for short-circuit (over-current) protection. Use only a fuse or circuit
breaker not higher than 15 A for 120 V
AC
(U.S.) or 10 A for 230 V
AC
(international).
• All wiring and connections must conform to NFPA 70 (NEC).
• Do not work on the system or connect/disconnect cables during lightning storms.
• A voltage mismatch can damage the equipment and can pose a fire hazard. If voltage indicated on the label is
different from the power outlet voltage, do not connect Midspan to this outlet.
• For shelf-mounted equipment, verify that surface is stable and strong enough to support the equipment. Do not
stack more than
four
Midspan units.
• When disposing this product, follow all local laws and regulations.
•
Data
and
Data and Power
ports of the Midspan are shielded RJ45 data sockets. They cannot be used as Plain
Old Telephone Service (POTS) sockets. Only connect RJ45 data connectors to these sockets.
• Associated Ethernet wiring must be limited to the inside of the building.
1.5.3
Power Cord
Power cord replacement must meet the local requirements.
• To ensure a reliable connection to an AC mains supply, equipment provides an appliance IEC60320 inlet to
connect a detachable power supply cord.
• Power socket outlet must be located near Midspan and easily accessible.
Note:
The only way to power off the unit is to disconnect the power cord from the outlet.
• This unit operates under Safety Extra Low Voltage (SELV) conditions, according to IEC/EN60950-1 or ES1
according to IEC/EN 62368-1.
Conditions are maintained only if the equipment to which the unit is connected also operates under SELV/ES1
conditions.
1.5.4
Country-Wise Power Cord Specifications
U.S.A. and Canada
• Cord must be UL-approved or CSA certified.
• Minimum specification for flexible cord is:
– No. 18 AWG
– Type SV or SJ
– Three-conductors
• Cord set must have a rated current capacity of at least 13A for 9024G/ACDC/M/F
and PD-9024G/AC/F; and 10A for PD- 9024G/ACDC/M, PD-9024G/AC, PD-9012G/
ACDC/M
,
PD-9012G/AC, PD-9006G/ACDC/M
,
and PD-9006G/AC.
• The attachment plug must be an earth-grounding type with a NEMA 5-15P (15 A, 125
V) or NEMA 6-15P (15 A, 250 V) configuration.
Denmark
Supply plug must comply with section 107-2-D1, standard DK2-1a or DK2-5a.
Switzerland
Supply plug must comply with SEV/ASE 1011.
France and Peru
IT supplies cannot power this unit. If your supplies are an IT type, unit must be powered by
230 V (2P+T) via an isolation transformer with a 1:1 ratio, and with secondary connection
point labeled Neutral and connected directly to the ground.
U.K
PoE Midspan is covered by General Approval NS/G/12345/J/100003, for indirect
connection to a public telecommunications system.
PD-90XXG
Standards and Safety Guidelines
©
2021 Microchip Technology Inc.
and its subsidiaries
User Guide