MICOM SWING SW & SWSP
Installation Manual
Page
34
Its connection is identical to that of the P9 connector, except that it can be carried out in the P8
connector.
9.11
P10 Connector: Closing Safety Sensor 1 (Security 1)
The P10 connector is used to connect the security sensor (or presence sensor) which protects from
possible obstruction in the door closing movement.
The connector consists of 4 poles:
●
Two poles are used to supply the sensor. The output is 24V DC.
●
The other two poles are the input to the sensor signal, which can be: free from voltage (relay
output, no polarity) or by transistor (with polarity).
The signal input comes programmed from the factory to act as a Normally Closed contact, although it
can be configured as a Normally Open contact as well
(see section “13.-PROGRAMMING
PARAMETRES” - Parameter Nº21”).