Micha Solar
MSRx Charge Controller
User Operation Manual
Page 31 of 46
Document: 802440-30.doc
Date: December 2020
www.micha.co.uk
5.7. Menu F – Change Settings
Menu F
Screen Change Settings Description
Change Settings:
Accept ? -> SEL
0
Press Select to Accept any changes made
Press Menu to ignore any changes made
Change Settings:
1 Fulmen -> SEL
1
Press Select to program Fulmen Battery Setting into memory
Press Menu to ignore any changes made
Change Settings:
2 Vented -> SEL
2
Press Select to program Vented Battery Setting into memory
Press Menu to ignore any changes made
Change Settings:
3 VRLA -> SEL
3
Press Select to program VRLA Battery Setting into memory
Press Menu to ignore any changes made
Change Settings:
4 Absolyte > SEL
4
Press Select to program Absolyte Battery Setting into memory
Press Menu to ignore any changes made
Change Settings:
5 Gel/OPzV > SEL
5
Press Select to program Gel/OPzV Battery Setting into memory
Press Menu to ignore any changes made
Load 1 Disable
Output: Inactive
6
Load 1 Disable Output Function:
Inactive: Load Output control is normal / Active: Load is Disabled
Load 2 Disable
Output: Inactive
7
Load 2 Disable Output Function:
Inactive: Load Output control is normal / Active: Load is Disabled
CAUTIONS:
The customer should ensure that the battery settings are suitable for the type of battery and the
application.
Setting the wrong battery settings may reduce the life of the battery
If Select is not pressed, then the changes will revert to the previous values within 60 seconds
See Section 7 for the Battery Settings that are held in memory
Menu F Screen 6 & 7 – Load 1 & 2 Disable Output Function:
Inactive: Load Output control is normal
Active: Load is Disabled – i.e. Load is disconnected
This setting can be controlled using the Keypad or by Modbus communication