Instruction of Installation and Use 

1. The product has adopted structure compliance with EN50022; suitable for 

DIN  rail  mounting  NS35/7.5,  NS35/15.  Installation  steps  are  as  following 
(please reference to dimensional drawing):   

Step 1: Immobilize one side of product‘s mounting trough to the DIN 

mounting rail; 

Step 2: Pull out the spring clasp; 
Step 3: Place whole mounting trough to the DIN mounting rail properly; 
Step 4: Release spring clasp to make sure the installation.   

2.

 

The product has calibrated before out of factory. After correctly wiring, it 
can  be  powered  and  used  immediately.  But  for  further  precise  signal 
sampling, user needs to warm-up the product for 3 minutes before use. 

3.

 

The  auxiliary  power  requires  isolation  voltage≥2000VAC,  DC  current 
output ripple

10mV. 

4.

 

Multiple transducers can share with one set auxiliary power together., and 
the  wire  shared  between  the  transducers  and  power  should  be  short.  It's 
better to connect each transducer to the auxiliary power individually. 

5.

 

Wiring in terms of the terminal identification drawing strictly. 

6.

 

Basic testing method for accuracy 

(1)

 

According  to  the  terminal  definition  table  to  connect  the  testing 
circuit; 

(2)

 

The testing must to be done by under the following conditions

 

Auxiliary power:

 

 

24V

±

5

%,

ripple

5mV 

Ambient temperature:

 25

℃±

5

 

Relative humidity

: RH(45

75)

 

Accuracy for Signal Power Source instrument:

 0.05 

 

 

Содержание WBI417S91

Страница 1: ...ng WB Series Electric Isolated Transducer and Digital Electrical Transducer since 1989 USER MANUAL WBI417S91 AC current transducer www mywbdz com alex827 qq com Tel 86 0816 2971265 Fax 86 0816 2281934 ISO9001 ISO14000 ISO18000 Certified ...

Страница 2: ...l damage Before working in the terminal strip area the equipment must be isolated Proper and safe operation of the equipment depends on appropriate shipping and handling proper storage installation and commissioning and on careful operation maintenance and servicing The operating manual for the equipment gives instructions for its installation commissioning and operation However the manual cannot ...

Страница 3: ... magnetic field immunity test according to IEC 61000 4 8 1993 Product Description andApplication WBI417S91 converts AC input current into a load independent output signal RMS 0 4 20mA It has adopted electromagnetic isolation principle for real time measurement ofAC current from electric net or electric circuit The product has certain advantages of total galvanic isolation between input output high...

Страница 4: ...5Hz 1kHz 5 Linear Range 0 120 of nominal input 6 Responding Time 300ms 7 Over Load Capacity 30 times of nominal input 5 seconds 8 Auxiliary Power 12VDC 24VDC 9 Current consumption for static status 6V 10 Isolation Voltage Input Output 2500Vdc for 1 minute 11 Output Ripple 4mV root mean square value output load is 250Ohm 12 Drifting by Temperature 50 10 6 13 Ambient Temperature Commercial grade 0 5...

Страница 5: ...d before out of factory After correctly wiring it can be powered and used immediately But for further precise signal sampling user needs to warm up the product for 3 minutes before use 3 The auxiliary power requires isolation voltage 2000VAC DC current output ripple 10mV 4 Multiple transducers can share with one set auxiliary power together and the wire shared between the transducers and power sho...

Страница 6: ...itoring meter V2 to measuring the output voltage Uo of the transducer the basic introduced errorγof the transducer should be calculated as γ Uo Iz 250Ω 20mA 4mA 250Ω 100 6 Repeating step 4 5 if calculated absolute value is less than the given accuracy value of the transducer it shows the transducer s accurate grade is qualified Caution 1 Pay attention to the auxiliary power information especially ...

Страница 7: ... wire and the output signal wire should be as short as possible For product intensive installation the space between each product should not be smaller than 10mm 5 Only use identified terminals 6 There is no lightening strike prevention circuit design in this product For out door and hazardous environment using please add protective alternatives 7 This product uses fire prevent ABS crust its tempe...

Отзывы: