3. Reset to factory defaults

– reset switch on the left side of the LAN port, 

press the switch, keep it pressed, apply power to the unit, wait 10 sec, release 
the switch, unit will be reachable on the 

default IP 192.168.1.2 

 
Username: 

admin

 

Default password: 

admin

 

  

4. OPTIONAL 5 WAY RELAY MODULE 

 

The 5 Relay expansion module connects to the Solar Monitor via a 10way ribbon 
cable supplied with the relay module

, Relay’s is rated at 10Amps 220Vac.

 

Relay 1,2,3 can only be toggled to activate for 10sec then return to the off position 
again and is used to reset devices. 

Relay 4 and 5 can be controlled to the ON or OFF position by the user and will keep 
the selected position until changed by the user.  

The status of all 5 relays is displayed on the home page of the unit by means of 
green dots.  

In the “Relay” control page the user can assign names to the relays to help 

remember what is connected to the relays at the remote site.  

 

 

 

 

 

 

Содержание Solar Monitor-ISO SNMP

Страница 1: ...s for 12V and 24V Battery systems With Optional external relay module INDEX 1 SYSTEM DESCRIPTION 2 SYSTEM CONNECTIONS 3 RESET TO DEFAULTS AND PASSWORDS 4 OPTIONAL 5 WAY RELAY MODULE 5 WEB PAGES 6 TFTP...

Страница 2: ...m changes any existing solar regulator into a smart monitoring device Solar Panel input current Battery charge current Load current battery voltage and temperature data is available via embedded web p...

Страница 3: ...al voltage for a 24V system if the 12V centre tap wire is connected see system connections page Solar Panel voltage not monitored Some Solar Regulators are common negative regulators where the positiv...

Страница 4: ...4 P a g e Solar Monitor ISO SNMP Mi 2 SYSTEM CONNECTIONS USING LOAD OUTPUT FROM REGULATOR SYSTEM CONNECTIONS NO LOAD OUTPUT USED FROM REGULATOR...

Страница 5: ...nected to a 24V battery system the centre tap blue wire in drawing have to be connected IMPORTANT NOTE The Alarm input is a potential free contact input only and NO voltages should be injected here Pe...

Страница 6: ...itor via a 10way ribbon cable supplied with the relay module Relay s is rated at 10Amps 220Vac Relay 1 2 3 can only be toggled to activate for 10sec then return to the off position again and is used t...

Страница 7: ...the status of Relays 5 to 1 is given and indicated by a green dot if the relay is active powered A module heartbeat indication by a yellow dot flashes once per second as the software runs through the...

Страница 8: ...olar Monitor ISO SNMP Mi STATUS PAGE Temperature sensor is displayed in degrees Celsius Solar panel input current Charge current Load current Battery 1 voltage Battery 2 voltage 24V system Total batte...

Страница 9: ...toggled for 10 second periods and is typically used to reset radios or routers without logging yourself out completely from the remote site after a relay was accidently switched relay 1 to 3 will ret...

Страница 10: ...ly be left unaltered NETWORK CONFIGURATION PAGE MAC address is displayed and cannot be changed Setup IP address Gateway and Subnet Mask and user password After the configuration was saved the Reboot i...

Страница 11: ...ger software OID table number of services 11 1 3 6 1 4 1 45501 1 3 1 0 Relay 4 status integer 0 off 1 on 1 3 6 1 4 1 45501 1 3 2 0 Relay 5 status integer 0 off 1 on 1 3 6 1 4 1 45501 1 3 3 0 Total Bat...

Страница 12: ...ng the equipment to indicate online offline status Graphing each device added will have its own graphical presentation of all measured data and is unit specific Email alerts Multiple email addresses c...

Страница 13: ...t consumption with LAN port active 110mA 12Vdc 50mA 24Vdc Current sensors on Charge Load and Solar panel 75 Amp isolated non invasive current sensors 9mm OD cables max current sensors accept 9mm cable...

Отзывы: