CDV7 Series Gas Fireplace
69D2027
13
VENtING INStallatIoN INFoRMatIoN
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
G =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
F =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
G
Balcony -
with no side wall
M =
Combustible &
Noncombustible
12" (305 mm)
M
Balcony -
with perpendicular side wall
M =
24" (610 mm)
P =
20” (508 mm)
M
F
Alcove Applications*
C
D
C
E
V
V
Combustible &
Noncombustible
V
V
V
E
= Min. 6” (152 mm) for
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O
= 8’ (2.4 m) Min.
O
P
584-15
No.
of Caps
D
Min.
C
Max.
1
3’ (914 mm) 2 x D
Actual
2
6’ (1.8 m)
1 x D
Actual
3
9’ (2.7 m)
2/3 x D
Actual
4
12’ (3.7 m)
1/2 x D
Actual
D
Min.
= # of Termination caps x 3
C
Max.
= (2 / # termination caps) x D
Actual
*NotE:
Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or
non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a
termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must
be a minimum of 1’ (305 mm) below the termination cap.
GENERal INFoRMatIoN aSSEMBlING VENt pIpES
Only venting components manufactured by MHSC may
be used in Direct Vent systems.
Flex Vent pipes
Before joining the flex vent pipe to the unit, apply a bead
of high temperature sealant* (provided) to the 4” (102
mm) pipe exiting the fireplace. Secure flex vent pipe in
place with a hose clamp (provided).
*Be sure the flex pipe overlaps at least 1” (25 mm) onto
the collars of the fireplace and termination. If the termina-
tion has an internal bead, be sure to overlap and secure
1” (25 mm) past the bead.
* Be sure the vent is actually crushed before proceeding.
Apply a tug to be sure the vent will not slip off the collars.
Repeat process with 7” (178 mm) flex vent pipe. The same
procedure must be performed on the vent side.
FP2290
flex vent
Apply High Temperature
Sealant
Hose Clamp
FP2290
Figure 9 -
Apply high temperature sealant to 4” (102 mm) and 7”
(178 mm) pipes.
Figure 8 -
Termination Clearances