B-Vent Specialty Gas Fireplaces

GAS LINE INSTALLATION

CHECK GAS TYPE

Use proper gas type for the fireplace you are installing. If you have conflicting gas types, do not 

install fireplace. See dealer where you purchased the fireplace for proper fireplace for your gas 

type.

INSTALLING GAS PIPING TO FIREPLACE LOCATION

INSTALLATION ITEMS NEEDED

Before installing, make sure you have the items listed below:

•  

External regulator (supplied by installer) 

•  

Tee Joint

•  

Piping (check local codes) 

•  

Pipe wrench

•  

Sealant (resistant to propane/LP gas)

•  

Test gauge connection*

•  

Sediment trap (optional but recommended)

•  

Approved flexible gas line with gas connector (if allowed by 

local codes - not provided)
*A  CSA  design-certified  equipment  shutoff  valve  with  1/8” 

NPT tap is an acceptable alternative to test gauge connec-

tion.  Purchase  the  CSA  design-certified  equipment  shutoff 

valve from your dealer.
For  propane/LP  connections  only,  the  installer  must  supply  an  external  regulator.  The  external 

regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 

11 and 13 inches of water. If you do not reduce incoming gas pressure, burner system regulator 

damage could occur. Install external regulator with the vent pointing down as shown in 

Figure 11

Pointing the vent down protects it from freezing rain or sleet.

W

ARNING

A  qualified  installer  or  service  person 

must connect appliance to gas supply. 

Follow all local codes.

Use only new black iron or steel pipe. Inter-

nally tinned copper or copper tubing can 

be  used  per  National  Fuel  Code,  section 

2.6.3, providing gas meets hydrogen sul-

fide  limits,  and  where  permitted  by  local 

codes. Gas piping system must be sized 

to provide minimum inlet pressure (listed 

on  data  plate)  at  the  maximum  flow  rate 

(BTU/hr). Undue pressure loss will occur 

if the pipe is too small.

External regulators may be necessary for 

natural  gas.  One-  or  two-pound  systems 

will damage this appliance and may cause 

fire hazard.

&0
EXTERNALREGULATOR

External 

Regulator

100 gal. 

(min) 

Propane/

LP Supply 

Tank

Vent 

Pointing 

Down

FP1977

Figure 11 - 

External Regulator with Vent Pointing Down 

(Propane/LP Only)

When using copper or flex connectors use only fittings approved for gas connections. The 

gas control inlet is 3/8” NPT.

For  propane/LP  units,  never  connect 

fireplace  directly  to  the  propane/LP 

supply. This burner system requires an 

external regulator (not supplied). Install 

the external regulator between the burn-

er system and propane/LP supply.

CAUTION

CAUTION

W

ARNING

Содержание BVPNSC

Страница 1: ...installation adjustment alteration services or maintenance can cause injury or property damage Refer to this man ual For assistance or additional information consult a qualified installer service agen...

Страница 2: ...Precautions 8 Installation Planning 8 Firestop Installation 8 Vertical Termination 9 Outside Combustion Air 11 Fireplace Installation 12 Check Gas Type 12 Gas Line Installation 13 Electrical Wiring 14...

Страница 3: ...touch any electrical switch do not use any phone in your building immediately call your gas supplier from a neigh bor s phone Follow the gas supplier s instruc tions 4 Never install the fireplace in...

Страница 4: ...23 For Massachusetts Residents Only This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massa chusetts Flexline installation must not exceed 3...

Страница 5: ...500 feet 1 370 m GAS pressures Natural Inlet Minimum 4 5 w c Inlet Maximum 7 0 w c Manifold Pressure 3 5 w c Gas Specifications ORIFICE SIZE Min Input Max Input Orifice Model Fuel BTU h BTU h Size BVS...

Страница 6: ...local building codes To install the fireplace facing flush with the finished wall position the framework to accommodate the thickness of the finished wall It is not necessary to install a hearth exte...

Страница 7: ...th and depth of the fireplace Provide adequate ventilation air Provide adequate accessibility clearance for servicing and operating the fireplace Never obstruct the front opening of the fireplace 856O...

Страница 8: ...N PLANNING B VENT PIPE See venting installation instructions provided by the B Vent manufacturer NOTE This APPLIANCE MUST BE INSTALLED using B vent type pipe that has been listed by a nationally recog...

Страница 9: ...what is shown FP1022 Typical Straight Up Installation 1 26 00 djt H X 12 Listed Vertical Termination Cap Listed Gas Vent Lowest Discharge Opening Roof Pitch is x 12 H Min Minimum Height from Roof to L...

Страница 10: ...PIPE Attach 6 B Vent Pipe to Transition using Four 4 Sheet Metal Screws Attach Transition to Flue Collar using Three 3 Sheet Metal Screws Units Flue Collar FP2208 Figure 7 6 Min 4 Max FP2009a vent w e...

Страница 11: ...accidentally blocked Locate assembly above snow line to prevent snow from blocking assembly 3 Never mount combustion air inlet assembly in garage or storage area where combustible fumes gasoline migh...

Страница 12: ...r system regulator damage could occur Install external regulator with the vent pointing down as shown in Figure 11 Pointing the vent down protects it from freezing rain or sleet WARNING A qualified in...

Страница 13: ...be installed upstream of the appliance Figure 5 IMPORTANT Install main gas valve equipment shut off valve in an accessible locations The main gas valve is for turning on or shutting off the gas to th...

Страница 14: ...ervice All wiring shall be in compliance with all local city and state codes The appliance when installed just be electrically grounded in accordance with local codes or in the absence of local codes...

Страница 15: ...th the Signature Control valve which operates on 6 volts The 6 volt DC adapter plugs into the fireplace junction box A C power supply Four 4 AA batteries are used for back up during power outages 2 Th...

Страница 16: ...o not extend beyond the 15 ft wire cable provided If a longer distance is required the 15 ft may be extended up to 30 ft maximum by using two 2 SCSWEK cables plugged together Route the wire from junct...

Страница 17: ...ut Pilot Gas Tubing Valve Spill Switch ELECTRICAL INSTALLATION CAUTION Electrical connections should only be performedbyaqualified licensedelectrician Main power supply must be turned off before conne...

Страница 18: ...the front burner ports for best performance and effect Blockage of the burner ports may create increased soot and carbon build up Figure xx LG1027 bvent designer rock wool Metal Lip Metal Lip Ember M...

Страница 19: ...right side of log against far right grate bar Place notch on lower left of log on far left grate bar Rest log 2 on burn er assembly Note orientation of valve Figure xx LG1029 bv dsgnr log 3 Valve Log...

Страница 20: ...g 2 Fig ure xx 5 Place Log 5 by placing holes in bottom of log onto pin on log 1 and pin on log 2 Note orientation of log 5 and location of valve Figure xx 6 Place Log 6 by placing hole in bottom of l...

Страница 21: ...p in front of grate Do not place lava rock on the burner WARNING Do not sprinkle the lava rock or ember chunks on top of the burner This may cause potential sooting glass breakage and a fire hazard CU...

Страница 22: ...gas supplier s instruc tions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not function by hand...

Страница 23: ...to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indi cates the system is ready 5 Press ON button Sparker will spark and pilot flame will light...

Страница 24: ...ON OFF NG LP Conversion To Thermopile To Sensor To Sparker To Command Center To Stepper Motor To Valve Battery Door Master Switch ON LED OFF Control Board Command Center Figure 18 Signature Command Sy...

Страница 25: ...tended You may disable this feature if you wish NOTE By disabling this feature your fireplace may continue to operate unattended 2 When the master switch is in the ON position pressing the ON button a...

Страница 26: ...en Off 3 Hold the OFF button anytime for three seconds or by turning off the wall switch These two commands of OFF are Memory Off the system will remember all last settings before turning off The next...

Страница 27: ...ppliance may pro duce carbon soot during operation This carbon soot may collect on some logs some areas of the grate and on the fireplace and vent Slight carbon build up is acceptable The following is...

Страница 28: ...free from combustible materials gasoline and other flammable vapors and liquids 14 Do follow the lighting and operation procedures given in this manual 15 Do periodically inspect the pilot and burner...

Страница 29: ...tter 2 Clogged burner ports 2 Clean ports 3 Misaligned orifices 3 Realign or replace burner 4 Clogged vent system 4 Clean Floating flame 1 Blocked venting 1 Clean 2 Insufficient primary air 2 Adjust a...

Страница 30: ...ough Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Chec...

Страница 31: ...ront Y 1 074268 4 Log Back 1 074266 5 Log Front 1 074265 6 Log Middle 1 074267 7 Front Door Assy 2 20304161 8 Handle Package 1 037438 9 End Door Assy 2 20304162 10 Hearth Pan Ptd 1 071584 11 Burner As...

Страница 32: ...27D0435 6 Flexline w Shut off 1 69D0030 7 Injector 1 27D0433 8 Wire Valve Control not shown 1 80D0010 9 Wire Command Ctr Control Box 2 not shown 1 80D0008 10 A C Adapter 6 volt 1 80D0041 Accessories...

Страница 33: ...20301938 33 B Vent Specialty Gas Fireplaces ACCESSORIES ACCESSORIES Outside Air Kit 6AK Back Refractory Look Panel DBVFBB Side Refractory Look Panel DBVFBS CONVERSION KIT 6CSC LP Conversion Kit BVCKPS...

Страница 34: ...20301938 34 B Vent Specialty Gas Fireplaces...

Страница 35: ...ited Lifetime Warranty will also be void if the ap pliance is not operated and maintained according to the operating instructions supplied with the appli ance and does not extend to 1 firebox burner a...

Страница 36: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: