BBV, SBV Series Natural Vent Gas Fireplaces

TROUBLESHOOTING

STANDING PILOT IGNITION

SYMPTOM

1.  Spark igniter 

will not light pi-
lot after repeat-
ed triggering of 
piezo.

2.  Pilot will not 

stay lit after 
carefully fol-
lowing lighting 
instructions.

3.  Pilot burning, 

valve knob 
tuned to “ON”, 
switch is turned 
to “ON” or “RS”, 
but burner will 
not ignite.

4.  Frequent pilot 

outage prob-
lem.

5.  The pilot and 

main burner 
extinguish while 
in operation.

POSSIBLE CAUSE

A.  Wire disonnected.

B.  Defective igniter.

C. No gas or low gas 

pressure.

D. No Propane/LPG in 

tank.

A.  Defective thermocou-

ple.

B.  Defective valve.

A.  Defective switch, wall 

switch, remote control 
or wire.

B.  Pilot flame too small.

C. Defective or malfunc-

tioning thermopile.

D. Defective valve.

A.  Pilot flame may be too 

high or too low, caus-
ing pilot safety to drop 
out.

A.  Inner vent pipe leaking 

exhaust gases back 
into system.

B.  Horizontal vent improp-

erly pitched.

C. Improper vent cap 

installation.

ACTION

A.  Open door and check to make sure wire is connected to 

igniter.

B.  Check for spark at electrode and pilot. If no spark and elec-

trode wire is properly connected, replace pilot assembly.

C. Check remote/manual shut-off valve from fireplace. Low 

pressure can be caused by bent lines, restricted lines, low 
pressure line pressure. Consult with plumber or gas supplier.

D. Check Propane/LPG tank. Refill tank.

A.  Check that thermocouple flame impinges on thermocouple. 

Clean and/or adjust pilot for maximum flame impingement. 
Ensure that the thermocouple connection at the gas valve is 
fully inserted and tight.

  Disconnect the thermocouple from the valve, place one mil-

livolt lead wire on the tip of the thermocouple and the other 
meter lead wire on the thermocouple copper lead. Start the 
pilot and hold the valve knob in. If the millivolt reading is less 
than 15m V, replace pilot assembly.

B.  If thermocouple is producing more than 15m V, replace faulty 

valve.

A.  Check switch and wire for proper connection. Place jumper 

wires across terminals of switch. If burner comes on, replace 
defective switch. If the switch is OK, repeat the same proce-
dure on remote control. If burner comes on, replace remote 
control. Place jumper wire across wire at gas valves (termi-
nals marked TH and TP/TH). If burner comes on, wires are 
faulty or connections are bad. Replace wire.

B.  If pilot flame is not close enough to the thermopile, adjust 

pilot flame.

C. Check thermopile wire connections to make sure all are tight 

and that the thermopile is fully inserted into pilot assembly. 
Check thermopile with a millivolt meter. Connect leads to TP 
and TP/TH terminals on the control valve. If meter reading is 
below 325m V, replace pilot assembly.

D. Turn valve knob to “ON” and switch to “ON”. Take a reading 

at the thermopile leads (TP & TP/TH) on the valve. If the me-
ter reads greater than 175m V and the burner does not light, 
replace defective valve.

A.  Clean and adjust the pilot flame for maximum flame impinge-

ment on thermocouple.

A.  Check for flue product leak. Replace defective pipe section.

B.  Check horizontal-vent piping is running upward 1/4” per foot. 

Do not run the pipe level or downward.

C. Check for proper installation and freedom from debris or 

blockage.

Содержание BBV400

Страница 1: ...pplier WARNING Improper installation adjustment alteration services or maintenance can cause injury or property damage Refer to this man ual For assistance or additional information consult a qualifie...

Страница 2: ...ecautions 10 Installation Planning 10 Firestops 11 Termination 11 Outside Combustion Air 12 Combustion Air Assembly 13 Fireplace Installation 14 Check Gas Type 14 Installing Gas Piping to Fireplace Bu...

Страница 3: ...tions 4 Never install the fireplace in a recreational vehicle where curtains furniture clothing or other flam mable objects are less than 42 from the front top or sides of the fireplace in high traff...

Страница 4: ...approved for use with this fireplace 21 The fireplace is not intended for use with a thermo stat 22 This appliance must be installed with draft hood in same atmospheric pressure zone as the combustion...

Страница 5: ...00 feet 1 370 m GAS pressures Natural Propane LP Inlet Minimum 4 5 w c 11 0 w c Inlet Maximum 10 5 w c 13 0 w c Manifold Pressure 3 5 w c 10 0 w c Gas Specifications ORIFICE SIZE Max Input Min Input O...

Страница 6: ...6 7 7 8 m m 43 6 1102 mm 624037 400BBV dims 6 152 mm Figure 2 BBV400 Fireplace Dimensions and Framing FIREPLACE FRAMING Firebox framing can be built before or after the appliance is set in place Cons...

Страница 7: ...D Min Rough Opening Width 656O 165 mm 13 6QE 341 mm C E F G G 6 152 mm Figure 3 SBV400 SBV500 Fireplace Dimensions and Framing Ref SBV400 SBV500 A 40 1016 mm 46 1168 mm B 36 914 mm 42 1067 mm C 24ZC z...

Страница 8: ...ance Never obstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing Refer to Venting section found in this m...

Страница 9: ...ge 5 8 Nail Flange 5 8 Nail Flange FP2019 Figure 6 Secure Fireplace to Floor and Framing Studs FINISHING MATERIAL NOTE Any remote wiring i e remote control and wall switch must be done prior to final...

Страница 10: ...appliance collar The B vent outer wall will slip to the outside of the appliance collar Do not penetrate the pipe inner line with sheet met al screws Attach the initial flue section tot he top of the...

Страница 11: ...should be considered a combustible ma terial Maintain proper clearances to all combustible materials NOTICE Treatment of firestops and construction of the chase may vary from building type to buildin...

Страница 12: ...e the location cannot be accidentally blocked Locate assembly above snow line to prevent snow from blocking assembly 3 Never mount combustion air inlet assem bly in garage or storage area where com bu...

Страница 13: ...andard pocket knife Figure 12 WARNING DO NOT remove the cover if the outside air will not be connected WARNING Do not use a combustible duct Always use UL Listed Class 0 or 1 duct material If nec essa...

Страница 14: ...urner system regulator damage could occur Install external regulator with the vent pointing down as shown in Figure 14 Pointing the vent down protects it from freezing rain or sleet WARNING A qualifie...

Страница 15: ...f the gas to the fireplace Check your building codes for any special requirements for locating equipment shut off valve to fireplaces Apply pipe joint sealant lightly to male threads This will pre ven...

Страница 16: ...s from the gas meter to the fireplace for leaks Use a solution of 50 50 water and soap or a gas sniffer 4 To adjust flame height turn HI LO knob to HI to get maximum pressure to burner Turn HI LO knob...

Страница 17: ...nly be performed by a qualified licensed electrician Main power must be off when connecting to main electrical power supply or performing service All wiring shall be in compliance with all local city...

Страница 18: ...gram FP2027 REMOTE WALL SWITCH Position the wall switch Do not extend beyond the 15 of wire OPTIONAL DC REMOTE SYSTEMS These instructions replace the section entitled Hearth Mount in the Millivolt han...

Страница 19: ...and may lead to sooting LOG PLACEMENT Figure 19 1 Place rear log 1 on grate assembly Log should rest firmly on the two log mounting pins on the horizontal bars 2 Place top right log 2 on the rear log...

Страница 20: ...the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it Call a qualified service technicia...

Страница 21: ...r WARNING If using a soap and water solu tion to test for leaks DO NOT spray solution onto control body DANGER Never check for gas leaks with open flame NOTE Remove any excessive pipe compound from th...

Страница 22: ...the button is in the ON posi tion to light the main burner Figure 21 LIGHTING THE BURNER Depress and turn the knob counterclockwise to the ON position Fig ure 22 It will take less than four 4 seconds...

Страница 23: ...ce if any part of it has been under water Immediately call a qualified service technician to inspect the appliance and to replace any pat of the control system and any gas control that has been under...

Страница 24: ...y during normal operation The pilot flame must always be present when the fireplace is in operation Figure 26 The pilot flame has three distinct flames one engulfing the thermopile one engulfing the t...

Страница 25: ...uum surface of the logs with a brush attachment If logs must be removed for cleaning handle carefully by holding gently at each end Gloves are recom mended to prevent skin irritation from ceramic fibe...

Страница 26: ...62D4036 26 BBV SBV Series Natural Vent Gas Fireplaces REPLACEMENT PARTS FIREBOX COMPONENTS 4a 4b 4c 6 3 6 FIREBOX PARTS 1 2 3 5 6 7...

Страница 27: ...2016 4c Right Refractory 1 n a 62D1017 62D2017 Optional Field Installed Accessoriesd 5 Firebrick Assembly 1 F400BBVW n a n a 6 Outside Air Kit 1 OAC4 OAC4 OAC4 7 Black Glass Door Assembly 1 GD36BA GD3...

Страница 28: ...62D4036 28 BBV SBV Series Natural Vent Gas Fireplaces REPLACEMENT PARTS STANDING PILOT MILLIVOLT CONTROL 1 2 3 4 5 6 7 8 10 12 13 2T 2I 2C 9 11 6 3 6 CONTR PARTS...

Страница 29: ...3D6046 23D6046 23D6046 5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 6 Piezo Igniter 1 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 7 Injector 1 62D3006 62D3005 62D3004 20H3143...

Страница 30: ...62D4036 30 BBV SBV Series Natural Vent Gas Fireplaces REPLACEMENT PARTS ELECTRONIC IGNITION 1 2 3 4 5 6 7 9 8 10 11 12 6 3 6 ELECTRONIC IGNITION PARTS...

Страница 31: ...h Shut off Valve 1 23D6046 23D6046 23D6046 23D6046 23D6046 23D6046 5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 6 Injector 1 62D3006 62D3005 62D3004 20H3143 62D3003 62D0094 7 Burn...

Страница 32: ...mocouple connection at the gas valve is fully inserted and tight Disconnect the thermocouple from the valve place one mil livolt lead wire on the tip of the thermocouple and the other meter lead wire...

Страница 33: ...er ori es blocked B Check electrical connections between module and pilot operator on gas control C Check for 24VAC across PV MVPV terminals If voltage is correct replace gas control If voltage is not...

Страница 34: ...air pressure A Blockage or restriction in venting ACTION A Install log set per instructions Inspect the injector and air intake area Make sure this area does not have any blockage from debris and clea...

Страница 35: ...62D4036 35 BBV SBV Series Natural Vent Gas Fireplaces...

Страница 36: ...62D4036 36 BBV SBV Series Natural Vent Gas Fireplaces...

Страница 37: ...62D4036 37 BBV SBV Series Natural Vent Gas Fireplaces...

Страница 38: ...o comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Pl...

Страница 39: ...he Limited Lifetime Warranty will also be void if the appliance is not operated and main tained according to the operating instructions supplied with the appliance and does not extend to 1 firebox bur...

Страница 40: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: